background image

INSTALLATION INSTRUCTION & 

SERVICE INFORMATION

©

2022 Lennox Industries Inc. 

Dallas, Texas, USA

WARNING

Improper installation, adjustment, alteration, ser vice 

or maintenance can cause property damage, personal 

injury or loss of life.
Installation and service must be performed by a li­

censed professional HVAC installer (or equivalent) or a 

service agency.

CAUTION

In order to avoid injury, take proper precaution when 

lifting heavy objects.

General

Refer to the Product Specifications bulletin (EHB) for more 

product information. These instructions are intended as 

a general guide and do not supersede local or national 

codes in any way. Authorities having jurisdiction should 

be consulted before installation.
This wall­mounted indoor unit is matched with an outdoor 

heat pump unit to create a mini­split system that uses 

HFC­410A refrigerant.

Use of Mini-Split System During 

Construction

Lennox does not recommend the use of its mini­split 

systems during any phase of construction. Very low return 

air temperatures, harmful vapors and operation of the unit 

with clogged or misplaced filters will damage the system.

However, mini­split systems may be used for cooling of 

buildings under construction, if the following  conditions 

are met:

• 

Air filter must be installed in the system and must be 

maintained during construction.

• 

Air filter must be replaced upon construction comple

­

tion.

•  The indoor wall unit assembly must be thoroughly 

cleaned following final construction clean-up.

• 

 All mini-split operating conditions must be verified ac

­

cording to these installation instructions.

MHB and MWHB Series Units

SINGLE-ZONE MINI-SPLIT SYSTEM 

 

(115V and 208/230V)  

508243­01 1/2022 

Table of Contents

General ..........................................................................1

Use of Mini-Split System During Construction ..........1

Included Parts ...............................................................2

Model Number Identification

 .......................................3

Typical System Components .......................................4

System Dimensions .....................................................4

Outdoor Units ..............................................................4

Indoor Units .................................................................5

Indoor Unit Wall Mounts ..............................................5

System Clearances.......................................................5

Outdoor Unit ................................................................5

Indoor Unit ...................................................................5

Multiple Outdoor Units .................................................6

Torque Requirements for Caps and Fasteners ..........6

Indoor Unit Installation ................................................6

Unit Placement Considerations ...................................6

Determining Wall Mounting Plate Location ..................7

Installation of Wall Mounting Plate...............................7

Installation of Wall Sleeve............................................7

Installation of Indoor Unit on Wall Mounting Plate .......8

Indoor Unit Condensate Piping Connections ...............8

Outdoor Unit Installation .............................................8

Installing Drain Connector and Seal ............................8

Placement Considerations ...........................................9

Direct Sunlight, Rain and Ice Protection ......................9

Buried Refrigerant Pipe Protection ............................10

Securing the Outdoor Unit .........................................10

Refrigerant Piping Connections ................................11

Leak Test and Evacuation ..........................................13

Leak Test ...................................................................13

Triple Evacuation Procedure......................................13

Wiring Connections ....................................................13

Outdoor Unit  .............................................................13

Indoor Unit .................................................................13

Unit Start-Up ...............................................................15

Service Information ....................................................16

Indoor Unit Alert Codes and Outdoor Unit LED .........16

Test Run ....................................................................16

Double-Check Line Set Connections .........................16

Ambient Temperature is Below 60

º

F (16

º

C) ..............17

Indoor Unit Wiring Diagrams .....................................18

Outdoor Unit Wiring Diagrams ...................................19

THIS MANUAL MUST BE LEFT WITH THE OWNER 

FOR FUTURE REFERENCE

Содержание MWHB Series

Страница 1: ...indoor wall unit assembly must be thoroughly cleaned following final construction clean up All mini split operating conditions must be verified ac cording to these installation instructions MHB and M...

Страница 2: ...ing of refrigerant CFCs HCFCs and HFCs as of July 1992 Approved methods of recovery recycling or reclaiming must be followed Fines and or incarceration may be levied for non compliance CAUTION As with...

Страница 3: ...n 012 1 ton 018 1 5 tons 024 2 tons Refrigerant Type 4 HFC 410A Minor Design Sequence 1 1st Revision M H B 009 S 4 S 1 P Series Type M Mini Split OUTDOOR SINGLE ZONE HEAT PUMP UNITS Cooling Efficiency...

Страница 4: ...14 11 1 4 286 30 7 8 784 21 7 8 556 17 3 4 451 30 1 8 765 2 3 4 70 2 3 8 60 3 5 8 92 11 7 8 302 Figure 2 9K and 12K Outdoor Unit Dimensions Inches mm DRAIN HOLE bottom of unit FRONT VIEW SIDE VIEW TOP...

Страница 5: ...mm inch Indoor unit outline Right rear side refrigerant pipe inlet 2 1 2 64 diameter 18K 3 1 2 90 24K Left rear side refrigerant pipe inlet 2 1 2 64 diameter 18K 3 1 2 90 24K 1 7 8 48 18K 2 1 8 54 24K...

Страница 6: ...Rc Rockwell scale minimum Fully insert the wrench into the valve stem recess Service valve stems are factory torqued from 9 ft lbs 12 N m for small valves to 25 ft lbs 34 N for large valves to prevent...

Страница 7: ...se a carpenter s level or measuring tape to verify the wall mounting plate is horizontally level 2 Secure the wall mounting plate to the wall using the provided screws and screw anchors NOTE It is imp...

Страница 8: ...r unit 3 Drain should be as short as possible and should not have any droops or kinks that would restrict condensate flow and shall be approved resistant pipe There must be a 2 inch 51 mm space betwee...

Страница 9: ...ne security system or intercom Electrical interference and radio frequencies from any of these sources may affect operation Since water drains from the outdoor unit during vari ous stages of operation...

Страница 10: ...earing wall or area of the roof that can adequately support the unit Consult local codes for rooftop applications CAUTION Roof Damage This system contains both refrigerant and oil Some rubber roofing...

Страница 11: ...nto the refrigerant piping before it is connected 10 CAREFULLY adjust refrigerant piping connections to suit the application 11 Slowly loosen one of the flare nuts to release the factory nitrogen char...

Страница 12: ...sible and must be insulated to prevent condensation OUTDOOR UNIT OUTDOOR UNIT INDOOR UNIT INDOOR UNIT Maximum Line Set Length Maximum Line Set Length Maximum Elevation Outdooor Unit BELOW Indoor Unit...

Страница 13: ...port connections liquid and gas line pipes until a positive pressure is achieved 3 Evacuate the system to a reading of 5000 Microns 5 Torr 4 Break the vacuum by allowing nitrogen into the port connec...

Страница 14: ...ingle Zone Wiring IMPORTANT This unit must be properly grounded and protected by a circuit breaker The ground wire for the unit must not be connected to a gas or water pipe a lightning conductor or a...

Страница 15: ...line service valves to release the refrigerant charge contained in outdoor unit into the system 5 Replace the stem caps and tighten to the value listed in Table 1 Torque Requirements on page 6 6 Check...

Страница 16: ...Anti cold Air Flow n a cF Remote On Off n a CP ECO mode n a On display 3 seconds Outdoor Unit LED Slow flash Flashing at 1Hz Fast flash Flashing at 2Hz Test Run Pre Checks Only perform test run after...

Страница 17: ...is below 60 F 16 C In this instance you can use the MANUAL CONTROL button on the indoor unit to test the COOL function 1 Lift the front panel of the indoor unit and raise it until it clicks in place 2...

Страница 18: ...18 Indoor Unit Wiring Diagrams Figure 34 MWHB 09K 12K and 18K 115V and 208 230VAC Indoor Unit Wiring Diagram 16022000C27182 Figure 35 MWHB 24K 208 230VAC Indoor Unit Wiring Diagram...

Страница 19: ...19 Outdoor Unit Wiring Diagrams Figure 36 MHB 9K and 12K 115VAC Outdoor Unit Wiring Diagram Figure 37 09K 12K and 18K 208 230VAC Outdoor Unit Wiring Diagram...

Страница 20: ...20 Figure 38 MHB 24K 208 230VAC Outdoor Unit Wiring Diagram...

Отзывы: