Printed in U.S.A. © 2006 by LENNOX HEARTH PRODUCTS

P/N  775,540M  REV. A   04/2006 

Page 2 of 2

Indoor / Outdoor Wood Fireplaces

MP-36OD

Typical Installation - Outdoors

Chimney Section
(FTF8-48)

*Air Inlet
(Provided)

Flashing

(Locally

Fabricated)

Storm Collar

(FSC)

Metal Safety Strips

And Hearth Extension

Required When Installed

On Combustible Floor

Or In Proximity To

Combustible

Floor/Covering.

Outside

Combustion

Air Kit

(Optional)

Chimney and

Termination

* Outside Air Kit  (provided) 
must be installed in 
outdoor installation. 

Use Only Non-Combustible Materi-
als From Top Of Spacers Down And 
Within 1/2" Min. To Side Frame.

Outside Air Kit installa-

tion is optional unless 

mandated by local build-

ing codes. 

Notes:   
• Framing is shown as reference only.  It can differ according to design and local building codes.
• Fireplace is shown for illustration purposes only. It may differ from actual model.

7' 3" Min. (using one 4' section)

Termination (FTF8-CTD/CTDT)

Outdoor fi replace 
system less than 15 
feet height must be a 
minimum of 10 feet 
away from a building or 
combustible structure. 
If installed closer than 
10 feet, the 10 Foot 
Rule applies (see Ten 
Foot Rule Summary in 
Installation Manual).

Side Frame

CLEARANCES

Minimum clearance to combustibles for the appliance 
is as follows: sides and back - 1” (25 mm), fl oor - 0” 
(0 mm), adjacent wall - 12” (305 mm), ceiling - 37 
1/2” (953 mm).

Note:

 Clearance at the nailing tab is 0" (0mm)

Note:

  Adjacent wall considerations are for an adjacent 

wall on only a single side.  Walls should not be placed 
at minimum distance at both sides of the fi replace.

Frame Surface Not to Be Covered
With Combustible Materials

12"

Wall
Covering

45°

12"

1"

Door

Opening

Safe

Zone

12"*

Min. 9-5/8"*

Min.

Fireplace

Opening

Spacer

Combustible

Mantel

and Trim

12"

Max.

1 1/2"

Finished

Wall

Header

*Both Of These Dimensions Must Be At Least 18”
When An Unvented Gas Log Set Rated At 26,000
BTU Or Higher Is Used.  (Maximum 40,000 BTU).

❂ 

1-5/8" Min.

❂ 

The shaded gray area showing 1-5/8" Min. 

indicates non-combustible materal is required.

Fireplace

Opening

Top Spacer
on Appliance

Combustible

Mantel

8" Max.

(203mm)

Finished

Wall

Header

18" Max.

❂ 

1-5/8" Min.

(457mm)

❂ 

The shaded gray area showing 1-5/8" Min. 

indicates non-combustible materal is required.

CANADIAN INSTALLATION

USA INSTALLATION

MANTEL CLEARANCES

A

B

D

C

C

Hearth Extension Dimensions

A

16"

B

30"

C

8"

D

46"

Wall Shield Required

Where Less Than 12"

A

B

C

C

30"

24"

D

“k” & “r” Value Requirements (see installation manual for details)

k (per inch)

r (per inch)

Listed Min.Thickness

.84

1.19

1

"

TYPICAL FRAMING INSTALLATIONS

Typical Installation - Indoors

Hearth Extensions and Wall Shields

Thermal Conductivity and Resistance Requirements