Page 6
BLOWER DATA
ML296UH090XV48C BLOWER PERFORMANCE (less filter)
BOTTOM RETURN AIR, RETURN AIR FROM BOTH SIDES OR RETURN AIR FROM BOTTOM AND ONE SIDE
0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
“ADJUST”
Switch
Positions
Speed Switch Positions
Second Stage “HEAT” Speed - cfm
Second Stage “COOL” Speed - cfm
D
1
C
B
A
D
C
B
1
A
+
1230
1310
1360
1605
1165
1375
1580
1770
1
NORM
1115
1195
1255
1455
1075
1265
1440
1645
—
1005
1070
1130
1335
935
1145
1320
1465
“ADJUST”
Switch
Positions
First Stage “HEAT” Speed - cfm
First Stage “COOL” Speed - cfm
D
1
C
B
A
D
C
B
1
A
+
1165
1250
1315
1520
840
1005
1155
1315
1
NORM
1075
1140
1195
1405
780
915
1045
1190
—
935
1030
1065
1285
690
835
955
1070
1
Factory default jumper setting.
NOTES - The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately
91%
of the same second stage HEAT speed position.
First stage COOL (two-stage air conditioning units only) is approximately
70%
of the same second stage COOL speed
position.
Continuous Fan Only speed is approximately
38
%
of the same second stage COOL speed position - minimum
500 cfm.
Lennox Harmony III™ Zoning System Applications - Minimum blower speed is 453 cfm.
BLOWER DATA
ML296UH090XV48C BLOWER PERFORMANCE (less filter)
SINGLE SIDE RETURN AIR
0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
“ADJUST”
Switch
Positions
Speed Switch Positions
Second Stage “HEAT” Speed - cfm
Second Stage “COOL” Speed - cfm
D
1
C
B
A
D
C
B
1
A
+
1210
1275
1320
1555
1140
1340
1525
1725
1
NORM
1115
1175
1230
1400
1040
1235
1395
1565
—
990
1070
1125
1295
910
1120
1275
1400
“ADJUST”
Switch
Positions
First Stage “HEAT” Speed - cfm
First Stage “COOL” Speed - cfm
D
1
C
B
A
D
C
B
1
A
+
1140
1230
1280
1455
820
1005
1135
1290
1
NORM
1040
1135
1180
1370
755
880
1025
1150
—
910
1000
1075
1250
680
815
925
1065
1
Factory default jumper setting.
NOTES - The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately
91%
of the same second stage HEAT speed position.
First stage COOL (two-stage air conditioning units only) is approximately
70%
of the same second stage COOL speed
position.
Continuous Fan Only speed is approximately
38
%
of the same second stage COOL speed position - minimum
500 cfm.
Lennox Harmony III™ Zoning System Applications - Minimum blower speed is 453 cfm.