Page 5
SPECIFICATIONS
General
Data
Model No.
ML16XP1-042
ML16XP1-048
ML16XP1-060
Nominal Tonnage
3.5
4
5
1
Sound Rating Number (dBA)
79
80
80
Connections
(sweat)
Liquid line (o.d.) - in.
3/8
3/8
3/8
Vapor (Suction) line (o.d.) - in.
7/8
7/8
1-1/8
Refrigerant
2
R-410A charge furnished
10 lbs. 12 oz.
10 lbs. 7 oz.
10 lbs. 4 oz.
Outdoor
Coil
Net face area- sq. ft.
Outer coil
29.1
29.1
29.1
Inner coil
28.2
28.2
28.2
Tube diameter - in.
5/16
5/16
5/16
No. of rows
2
2
2
Fins per inch
22
22
22
Outdoor
Fan
Diameter - in.
26
26
26
No. of blades
3
3
4
Motor hp
1/3
1/3
1/3
Cfm
4150
4150
4250
Rpm
820
820
820
Watts
216
216
245
Shipping Data -
lbs. 1 pkg.
263
263
268
ELECTRICAL DATA
Line voltage data - 60hz - 1 ph
208/230V-1ph
208/230V-1ph
208/230V-1ph
3
Maximum overcurrent protection (amps)
40
40
50
4
Minimum circuit ampacity
25
25.8
30.4
Compressor
Rated load amps
15.9
18.5
22.2
Locked rotor amps
112.3
124
127.9
Power factor
0.99
0.99
0.99
Outdoor Fan Motor
Full load amps
2.6
2.6
2.6
OPTIONAL ACCESSORIES - ORDER SEPARATELY
iComfort
®
M30 Smart Wi-Fi Thermostat
15Z69
•
•
•
Remote Outdoor Temperature Sensor
X2658
•
•
•
Compressor Crankcase Heater
93M05
•
•
•
Compressor Hard Start Kit
LG
88M91
•
•
Copeland
10J42
•
•
Compressor Sound Cover
69J03
•
•
•
Compressor Low Ambient Cut-Off
45F08
•
•
•
Freezestat
3/8 in. tubing
93G35
•
•
•
5/8 in. tubing
50A93
•
•
•
Indoor Blower Off Delay Relay
58M81
•
•
•
Loss of Charge Switch Kit
84M23
•
•
•
5
Low Ambient Kit
54M89
•
•
•
Mild Weather Kit
11B97
•
•
•
Monitor Kit - Service Light
76F53
•
•
•
Outdoor
Thermostat Kit
Thermostat
10Z23
•
•
•
Mounting Box
31461
•
•
•
Refrigerant Line Sets
L15-65-30 L15-65-40
L15-65-50
•
•
Unit Stand-Off Kit
94J45
•
•
•
NOTE - Extremes of operating range are plus 10% and minus 5% of line voltage.
1
Sound Rating Number rated in accordance with test conditions included in AHRI Standard 270.
2
additional refrigerant charge required.
3
HACR type breaker or fuse.
4
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
5
Crankcase Heater and Freezestat are recommended with Low Ambient Kit
Содержание ML16XP1 Series
Страница 28: ...Page 28 Wiring and Sequence of Operation FIGURE 15 Typical Unit Wiring 018 thru 030 units ...
Страница 29: ...Page 29 FIGURE 16 Typical Unit Wiring 036 thru 060 units ...
Страница 30: ...Page 30 FIGURE 17 Typical Factory Wiring 018 thru 030 units ...
Страница 31: ...Page 31 FIGURE 18 Typical Factory Wiring 036 thru 060 units ...