background image

MINIAIR-IOM-0310-E 7 

 

 

 

7

 

 

S

TANDARD 

M

AINTENANCE

 

 

 

 

 

It is the responsibility of the User to carry out all types of maintenance operations. 

 

Only personnel previously trained and qualified may carry out maintenance operations. 

 

Should the unit require disassembly, hand protection is required  

 
Periodical maintenance 

 

Air filters 

 
Monthly at least and according to the real air quality at suction, check filter condition. Filter section can be entered through 
side removable panel as well as bottom turnable panel; following the 

figure 11

, in the first case, the filter frame 1 is moved 

together the side panel, in the second case, it’s necessary to dismount the bottom filter frame 2 also.

 

 
For the cleaning, utilize a vacuum cleaner or wash with normal detergent and warm water, allow to dry well. Remember to 
assemble the filter before operating the unit; replace a new filter after max 3 cleaning cycles. In case of soft bag filter 
(option), replace it when dirty. 
 
 

Fans & motors 

 
Yearly at least, check fan and motor efficiency and their resistance-free rotation; for belt driven fan type units, also check belt 
tension by adjusting the railed motor plate. Following 

figure 12

, fan section can be entered through bottom removable panel 

if direct driven fan or front removable panel if belt driven fan; in this last case, the dismounting of the bottom panel means 
the whole dismounting of the fan-motor group also.

 

 
 

Water coils 

 
Every two years at least, check that coil heat exhange surface is clean and free from dusty; this checking can be done by 
dismounting filter panel (upstream) and fan-motor panel (downstream). In case that water coil shall be removed, follow the 
above instructions and see 

figure 13

 : 

1)  remove all water connections to the units (water inlet/outlet and condensation discharge) 
2)  dismount all bottom panels 
3)  dismount the drain tray, by unscrewing the fixing upstream and downstream screws 
4)  unscrew the fixing screws on the coil frame, move the coil to the connection-free side and extract it from the 

bottom. 

 
 

Electrical equipment 

 
Yearly at least, check the fixing of all electrical connections. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

BEFORE FOLLOWING ANY TYPE OF MAINTENANCE OPERATION, BE CERTAIN THAT THE UNIT MAY NOT 
CASUALLY OR ACCIDENTALLY BE CONNECTED TO THE ELECTRICAL MAINS SUPPLY. THERFORE IT IS 
NECESSARY TO SHUTDOWN THE UNIT’S POWER SUPPLYAD PRIOR TO MAINTENANCE. 

Содержание MINIAIR

Страница 1: ...lennoxemeia com MINIAIR Installation operating and maintenance Compact air handling unit 2 44 kW 500 7400 m3 h MINIAIR IOM 0310 E...

Страница 2: ......

Страница 3: ...ENTION AUTHORIZED PERSONNEL ONLY 1 INTRODUCTION PAG 2 2 DIMENSIONS AND WEIGHTS PAG 2 3 INSTALLATION CONFIGURATIONS PAG 3 4 TRANSPORTATION PAG 3 5 INSTALLATION CONNECTION PAG 3 6 WIRING DIAGRAMS PAG 6...

Страница 4: ...t or indirect caused by the incorrect installation or for damages caused by the installation being effectuated by inexperienced or unauthorised personnel Verify upon acquisition that the apparatus is...

Страница 5: ...the unit is intact and complete and no damage has been sustained during transport Any eventual damage revealed must be communicated to the carrier demonstrating the reserve clause within the transport...

Страница 6: ...flammable or toxic gas Preliminary operations Check the perfect condition of the various components of the unit Control that contained within the packing there are the installation accessories and do...

Страница 7: ...on outlet connection The system of drainage must provide an adequate trap able to allow the condensation run off on underpressure conditions The trap must be designed as shown on the figure 6 The trap...

Страница 8: ...WIRING DIAGRAMS Direct connection for models 10 and 20 Follow diagram on the figure 7 Direct connection for model 25 up to 50 Follow diagram on the figure 8 Direct connection for model 60 Follow diagr...

Страница 9: ...ype units also check belt tension by adjusting the railed motor plate Following figure 12 fan section can be entered through bottom removable panel if direct driven fan or front removable panel if bel...

Страница 10: ...Motor wiring burned Replace the relais board Replace fan motor Air performance decreasing Air filter dirty Air duct blocked Clean or replace filter Check air plant are dampers open Condensate water s...

Страница 11: ...Fig 1 Fig 3 Fig 5 Fig 2 Fig 4 Fig 6 MINIAIR IOM 0310 E 9...

Страница 12: ...Fig 5 Fig 7 Fig 8 Fig 9 MINIAIR IOM 0310 E 10...

Страница 13: ...Fig 10a Fig 11 Fig 12 Fig 10b Fig 13 MINIAIR IOM 0310 E 11...

Страница 14: ......

Страница 15: ...BELGIUM AND LUXEMBOURG FRANCE GERMANY ITALY NETHERLANDS POLAND PORTUGAL SALES OFFICES OTHER COUNTRIES Due to Lennox s ongoing commitment to quality the specifications ratings and dimensions are subjec...

Отзывы: