II- PLACEMENT AND INSTALLATION

Make sure unit is installed in accordance with installation 

instructions and applicable codes.

III- START-UP
A- Heating Start-Up

 WARNING

Shock and burn hazard.

ML180UHE(X) units are equipped with a hot surface 

ignition system. Do not attempt to light manually.

Gas Valve Operation

GAS VALVE SHOWN IN ON POSITION

MANIFOLD

PRESSURE

OUTLET

PORT

INLET

PRESSURE

PORT

MANIFOLD

PRESSURE

ADJUSTMENT

SCREW

FIGURE 19 

1 -   

STOP! 

Read the safety information at the beginning 

of this section.

2 -   Set the thermostat to the lowest setting.
3 -   Turn off all electrical power to the unit.
4 -   This  furnace  is  equipped  with  an  ignition  device 

which automatically lights the burners. Do not try to 

light the burners by hand.

5 -   Remove the upper access panel.
6 -   Move  gas  valve  switch  to  OFF  position.  Do  not 

force. See figure 19.

7 -   Wait five minutes to clear out any gas. If you then 

smell gas, STOP! Immediately call your gas supplier 

from a neighbor’s phone. Follow the gas supplier’s 

instructions. If you do not smell gas go to next step.

8 - 

 Move gas valve switch to ON position. Do not force. 

See figure 19.

9 -   Replace the upper access panel.

10 - 

 Turn on all electrical power to to the unit.

11 - 

 Set the thermostat to desired setting.

NOTE - 

When unit is initially started, steps 1 through 

11 may need to be repeated to purge air from gas 

line.

12 -  If  the  appliance  will  not  operate,  follow  the 

instructions “Turning Off Gas to Unit” and call the 

gas supplier.

Turning Off Gas to Unit

1 - 

 Set the thermostat to the lowest setting.

2 -   Turn off all electrical power to the unit if service is to 

be performed.

3 -   Remove the upper access panel.
4 -   Move  gas  valve  switch  to  OFF  position.  Do  not 

force. See figure 19.

5 -   Replace the upper access panel.

B- Safety or Emergency Shutdown

Disconnect main power to unit. Close manual and main 

gas valves.

C- Extended Period Shutdown

Turn off thermostat or set to “UNOCCUPIED” mode. Close 

all gas valves (both internal and external to unit) to guar

-

antee  no  gas  leaks  into  combustion  chamber.  Turn  off 

power  to  unit. All  access  panels  and  covers  must  be  in 

place and secured.

IV-HEATING SYSTEM SERVICE CHECKS

A- C.S.A. Certification

All units are C.S.A. design certified without modifications. 

Refer to the ML180UHE(X) Installation Instruction.

B- Gas Piping

Gas supply piping should not allow more than 0.5”W.C. 

drop in pressure between gas meter and unit. Supply gas 

pipe must not be smaller than unit gas connection. Com

-

pounds used on gas piping threaded joints should be re

-

sistant to action of liquefied petroleum gases.

C- Testing Gas Piping

 CAUTION

If a flexible gas connector is required or allowed by 

the authority that has jurisdiction, black iron pipe 

shall be installed at the gas valve and extend outside 

the furnace cabinet.

 IMPORTANT

In case emergency shutdown is required, turn off the 

main shut-off valve and disconnect the main power 

to unit. These controls should be properly labeled 

by the installer.

 WARNING

Do not exceed 600 in-lbs (50 ft-lbs) torque when 

attaching the gas piping to the gas valve.

When pressure testing gas lines, the gas valve must be 

disconnected and isolated. Gas valves can be damaged if 

subjected to more than 0.5psig (14” W.C.). See figure 20. 

If the pressure is equal to or less than 0.5psig (14”W.C.), 

close the manual shut-off valve before pressure testing to 

isolate furnace from gas supply.

Содержание MERIT ML180UH045E36A

Страница 1: ...Propane operation ML180UHE X model units are equipped with a hot sur face ignition system The ML180UHE X unit meets the California Nitrogen Oxides NOx Standards and Califor nia Seasonal Efficiency re...

Страница 2: ...15 15 Shipping Data lbs 1 package 111 111 127 142 SPECIFICATIONS Gas Heating Performance Model No ML180UH090E60C ML180UH110E60C ML180UH135E60D Model No Low Nox ML180UH110XE60C 1 AFUE 80 80 80 Input B...

Страница 3: ...h Altitude Pressure Switch Kit Natural Gas to LPG Propane Kit LPG Propane to Natural Gas Kit Natural Gas High Altitude Orifice Kit 0 4500 ft 4501 7500 ft 7501 10 000 ft 0 7500 ft 7501 10 000 ft 0 7500...

Страница 4: ...35 0 70 1190 350 1000 235 855 205 790 190 540 140 0 80 1160 365 925 245 790 205 735 200 445 145 ML180UH070E36A PERFORMANCE Less Filter External Static Pressure in w g Air Volume Watts at Various Blowe...

Страница 5: ...0 2255 640 1940 420 1750 310 1580 230 1485 185 2290 655 1980 425 1775 310 1605 235 1495 195 0 10 2200 655 1910 440 1705 315 1535 240 1385 190 2250 675 1945 445 1730 320 1555 245 1400 190 0 20 2150 675...

Страница 6: ...er Box includes sensor ignitor and rollout switches Combustion Air Inducer Combustion Air Inducer Pressure Switch Heat Exchanger Upper Access Panel Blower Access Panel Primary Limit under combustion a...

Страница 7: ...e hot surface ignition control system consisting of an in tegrated control figure 3 with control terminal designations in tables 1 2 and 3 sensor and ignitor figure 6 The in tegrated control and ignit...

Страница 8: ...e Switch In 11 Rollout Switch In 12 Gas Valve Out TABLE 3 1 4 Quick Connect Terminals 120HUM Humidifier 120VAC LINE 120VAC XFMR Transformer 120VAC CIRC Indoor blower 120VAC EAC Indoor air quality acce...

Страница 9: ...Switch failed to close or opened during heat demand 10 Watchguard Pressure Switch opened 5 times during one heat demand 11 Pressure Switch stuck closed prior to activation of combustion air inducer 12...

Страница 10: ...out Switch Open 9 Pressure Switch failed to close or opened during heat demand 10 Watchguard Pressure Switch opened 5 times during one heat demand 11 Pressure Switch stuck closed prior to activation o...

Страница 11: ...air temperature once the heat demand is satisfied Note the supply air temperature at the instant the blower is de energized Adjust the fan off delay to achieve a supply air tempera ture between 90 11...

Страница 12: ...c er See figure 7 When excess heat is sensed in the heat exchanger the limit will open If the limit is open the in tegrated control energizes the supply air blower and clos es the gas valve The limit...

Страница 13: ...ire 5 Connect lead to Terminal FS on integrated control 6 Turn supply voltage on and close thermostat contacts to cycle system 7 When main burners are in operation for two minutes take reading TABLE 6...

Страница 14: ...s after the gas valve closes post purge A pressure switch mounted on the combustion air inducer orifice plate is used to prove inducer operation The com bustion air inducer orifice will be different f...

Страница 15: ...diameter probes in order not to damage plug Check voltage during 20 second ignitor warm up period Voltage should read 120 volts 10 If voltage reads below these values check for correct supply voltage...

Страница 16: ...ive to atmospheric pressure If the flue becomes obstructed during operation the switch senses a loss of negative pressure pressure becomes more equal with atmospheric pressure and opens the cir cuit t...

Страница 17: ...then reinstall the mounting screws See unit Installation Instructions for more detail IMPORTANT The combustion air pressure switch must be moved for horizontal discharge air left position vent pipe v...

Страница 18: ...roubleshooting Troubleshooting the motor is an easy process Follow steps below 1 Shut off power to unit 2 Remove input plugs P48 and P49 from motor See figure 14 for troubleshooting procedure If corre...

Страница 19: ...peed tap used for continuous fan 1 2 3 4 or 5 on input plug P49 If 24 volts is not present problem may be up stream of plug P49 Proceed to test 4 Multi Meter set to VAC 12 0 12 0 24 Multi Meter set to...

Страница 20: ...ximately the same resistance within an ohm 3 Check to see if the blower wheel spins freely Motor Test FIGURE 17 TABLE 9 Scale Measurement range in words ohms 2 M two megohm two million ohms 0 2 000 00...

Страница 21: ...ervice is to be performed 3 Remove the upper access panel 4 Move gas valve switch to OFF position Do not force See figure 19 5 Replace the upper access panel B Safety or Emergency Shutdown Disconnect...

Страница 22: ...fitting Connect to a test gauge to measure supply pressure 2 Start unit and allow 5 minutes for unit to reach steady state 3 After allowing unit to stabilize for 5 minutes record supply pressure and...

Страница 23: ...0 135 Nat 3 5 3 5 2 9 3 5 4 5 13 0 LP Propane 10 0 10 0 9 6 10 0 11 0 13 0 TABLE 13 Pressure Switch and Gas Conversion Kits at all Altitudes Model Input Size High Altitude Pressure Switch Kit High Al...

Страница 24: ...es a poor or partial ground Compare the readings to the table below If the readings exceed the maximum shown in table 14 make repairs before operating the furnace 2 In addition measure the AC voltage...

Страница 25: ...ate TEMPERATURE RISE Supply Duct Temperature ________ Return Duct Temperature _ _____ Temperature Rise ________ SUPPLY AIR Temperatures RETURN AIR FIGURE 23 C External Static Pressure 1 Tap locations...

Страница 26: ...t exchanger and clean if necessary 6 Check the cleanliness of blower assembly and clean the housing blower wheel and blower motor if necessary The blower motors are prelubricated for extended bearing...

Страница 27: ...alve rollout switches primary limit switch and make up box then disconnect them 4 Remove the screws that secure the combustion air inducer pressure switch assembly to the collector box Carefully remov...

Страница 28: ...NOx units only Replace NOx inserts 15 Reinstall collector box and combustion air assembly Reinstall all screws to the collector box and combustion air inducer Failure to replace all screws may cause l...

Страница 29: ...rol energizes B6 combustion air inducer S18 combustion air pressure switch closes Once S18 closes a 15 second pre purge follows 6 A92 integrated control energizes R33 ignitor A 20 second warm up perio...

Страница 30: ...OFF COMBUSTION AIR INDUCER ON INDOOR BLOWER ON HEATING SPEED LED FLASHES CODE 11 PRESSURE SWITCH CLOSED GAS VALVE OFF COMBUSTION AIR INDUCER OFF INDOOR BLOWER OFF WITH DELAY Sequence holds until press...

Страница 31: ...NCE FOUR TIMES FLAME SIGNAL 1 5 MICROAMPS OR GREATER YES YES YES ROLLOUT SWITCH CLOSED LED FLASHES CODE 8 ROLLOT SWITCH OPEN GAS VALVE POWER OFF COMBUSTION AIR INDUCER POWER ON INDOOR BLOWER ON SEQUEN...

Страница 32: ...SLOW FLASH RATE REMAINS UNCHANGED THROUGHOUT COOLING CYCLE THERMOSTAT CALLS FOR COOLING COMPRESSOR CONTACTOR AND SYSTEM FAN ENERGIZED WITH 2 SECOND DELAY COOLING SPEED EAC TERM ENERGIZED COMPRESSOR O...

Страница 33: ...D EAC TERM REMAINS ON THERMOSTAT OPENS MANUAL FAN SELECTION MADE AT THERMOSTAT CONTROL G ENERGIZES SYSTEM FAN AT FAN SPEED EAC TERM ENERGIZED NO YES YES NO SYSTEM FAN SWITCHES TO HEAT SPEAD AFTER 30 S...