background image

Page 14

14ACX SERIES

(VALVE STEM SHOWN CLOSED)
INSERT HEX WRENCH HERE

SERVICE PORT CORE

SERVICE PORT CAP

ANGLE-TYPE SERVICE VALVE

(FRONT-SEATED CLOSED)

STEM CAP

(VALVE STEM SHOWN OPEN)
INSERT HEX WRENCH HERE

ANGLE-TYPE SERVICE VALVE

(BACK-SEATED OPENED)

1 - Remove stem cap with an appropriately sized wrench.

2 - Use a service wrench with a hex-head extension (3/16” for liquid

line valve sizes and 5/16” for suction line valve sizes) to back the
stem out counterclockwise as far as it will go.

When service valve is 

CLOSED

, the service port is

open to the line set and indoor unit.

When service valve is 

OPEN

, the service port is

open to line set, indoor and outdoor unit.

NOTE

 - A label with specific torque requirements may be affixed to the

stem cap. If the label is present, use the specified torque.

OPERATING ANGLE-TYPE SERVICE VALVE:

FIGURE 16

1

2

3

4

5

6

7

8

9

10

11

12

1/12 TURN

A service port cap protects the service port core from contamination
and serves as the primary leak seal.

1 - Remove service port cap with an appropriately sized wrench.

2 - Connect gauge set to service port.

3 - When testing is completed, replace service port cap and tighten as

follows:

With torque wrench: Finger tighten and
torque cap per table 3.

Without torque wrench: Finger tighten and
use an appropriately sized wrench to turn
an additional 1/6 turn clockwise.

1

2

3

4

5

6

7

8

9

10

11

12

1/6 TURN

Reinstall Stem Cap:

Stem cap protects the valve stem from damage and serves as the
primary seal. Replace the stem cap and tighten as follows:

With Torque Wrench: Finger tighten
and then torque cap per table 3.

Without Torque Wrench: Finger
tighten and use an appropriately
sized wrench to turn an addition­
al 1/12 turn clockwise.

TO ACCESS SERVICE PORT:

FIGURE 17

Checking and Adding System Charge

The 14ACX unit is factory-charged with enough HFC-410A
refrigerant to accommodate a 15-foot length of refrigerant
piping. Charge should be checked and adjusted using the
tables provided on the charging procedure sticker located
on the unit access panel. Detailed information is provided
in the 14ACX Installation and Service Procedures manual
(Corp0638-L10), which is available on DaveNet.

Homeowner Information

CAUTION

Before attempting to perform any service or mainte­
nance, turn the electrical power to unit OFF at dis­
connect switch.

In order to ensure peak performance, your system must be
properly maintained. Clogged filters and blocked airflow
prevent your unit from operating at its most efficient level.

Homeowner Maintenance

The following maintenance may be performed by the
homeowner.

Contact a licensed professional HVAC technician to
schedule a yearly inspection and maintenance
appointment for your equipment.

Check the indoor unit filter each month and replace the
filter, if necessary.
Have your Lennox dealer show you where your indoor
unit filter is located. It will be either at the indoor unit
(installed internal or external to the cabinet) or behind a
return air grille in the wall or ceiling. Check the filter
monthly and clean or replace it as needed.
Disposable filters should be replaced with a filter of the
same type and size.

Check the indoor unit drain line for obstructions monthly
during the cooling season. 
The indoor evaporator coil is equipped with a drain pan
to collect condensate formed as your system removes
humidity from the inside air. Have your dealer show you
the location of the drain line and how to check for
obstructions. (This would also apply to an auxiliary drain,
if installed.)

Check the area around the outdoor unit monthly and
remove any obstructions that may restrict airflow to the
outdoor unit. This would include grass clippings, leaves,
or papers that may have settled around the unit.

Trim shrubbery away from the unit and periodically check
for debris which collects around the unit.

During the winter months, keep the snow level below the
louvered panels.

NOTE

 

-

 The filter and all access panels must be in place

any time the unit is in operation. If you are unsure about the
filter required for your system, call your Lennox dealer for
assistance.

Содержание Merit 14ACX-018-230

Страница 1: ...tdoor air conditioner is designed for use with HFC 410A refrigerant only This unit must be installed with an approved indoor air handler or coil See the Lennox 14ACX Product Specifications bulletin EH...

Страница 2: ...ing or stowing the panels consider any weather conditions especially wind that may cause panels to be blown around and damaged NOTICE Roof Damage This system contains both refrigerantand oil Some rubb...

Страница 3: ...e rises above 40 psig DO NOT REPLACE COMPRESSOR LIQUID LINE FILTER DRIER INSTALLATION The provided filter drier must be field installed in the liquid line between the outdoor unit s liquid line servic...

Страница 4: ...THE LIQUID LINE TO THE SUCTION LINE FLOOR JOIST OR ROOF RAFTER REFRIGERANT LINE SET INSTALLING HORIZONTAL RUNS NOTE Similar installation practices should be used if line set is to be installed on ext...

Страница 5: ...ndoor unit s liquid line orifice housing LOW HIGH EXISTING INDOOR UNIT GAUGE MANIFOLD CYLINDER CONTAINING CLEAN HCFC 22 TO BE USED FOR FLUSHING Positioned to deliver liquid refrigerant LIQUID LINE SER...

Страница 6: ...d debur the ends The pipe must remain round Do not crimp end of the line Remove service cap and core from both the suction and liquid line service ports 1 2 ANGLE TYPE SERVICE VALVE SERVICE PORT CORE...

Страница 7: ...WHEN BRAZING LINE SET TO SERVICE VALVES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WRAP SERVICE VALVES To help protect service valve seals during brazing wrap water saturated clo...

Страница 8: ...TION EQUALIZER LINE INSTALLATION A Remove and discard either the flare seal cap or flare nut with copper flare seal bonnet from the equalizer line port on the suc tion line as illustrated in the figur...

Страница 9: ...door unit E After a few minutes open one of the service valve ports and verify that the refrigerant added to the system earlier is measurable with a leak detector F After leak testing disconnect gauge...

Страница 10: ...utting off the vacuum pump and closing the manifold gauge valves F When the absolute pressure requirement above has been met disconnect the manifold hose from the vacuum pump and connect it to a cylin...

Страница 11: ...re only with this product CAUTION Failure to use properly sized wiring and circuit breaker may result in property damage Size wiring and circuit breaker s per Product Specifications bulletin EHB and u...

Страница 12: ...t and secure with provided wire tie B Make 24VAC thermostat wire connections Locate the two wires from the contactor and make connection using field provided wire nuts Yellow to Y1 Black to C common R...

Страница 13: ...ped with a service port which has a factory installed valve stem Figures 15 and 16 provide information on how to access and operate both angle and ball type service valves Torque Requirements When ser...

Страница 14: ...he tables provided on the charging procedure sticker located on the unit access panel Detailed information is provided in the 14ACX Installation and Service Procedures manual Corp0638 L10 which is ava...

Страница 15: ...as necessary 6 Inspect contactor contacts for pitting or burn marks Replace as necessary 7 Check outdoor fan motor for worn bearings bushings Replace as necessary 8 Inspect and clean outdoor coils if...

Страница 16: ...re Supply Air Temperature Ambient Temperature Return Air Temperature System Refrigerant Charge Refer to manufacturer s information on unit or installation instructions for required subcooling and appr...

Отзывы: