Status input D1 and GND 
 Contact 

sensing 

 

Insulation against mains 

 Operating 

action 

 

With the RCC10 

 

With the RCC10.1 

 
SELV DC 6-15V / 3-6 mA 
4 kV, extra insulation 
 
selectable (N.O. / N.C.) 
(N.O.) 

Perm. cable length with copper cable 1.5 mm

for connection to terminals B1, B2 and D1 

 
80 m 

Setpoint setting range 

8...30 °C 

Max. control deviation at 25 °C 

max. 

±

0.7 K 

Switching differential in heating mode SDH  

(selectable) 

1 K or 4 K 

Switching differential in cooling mode SDC 

(selectable) 

0.5 K or 2 K 

Setpoint «Energy saving mode  », heating 

16 °C 

Setpoint « Energy saving mode  », cooling 

28 °C 

Setpoint «Standby  »  

8 °C 

Operation 

Climatic conditions 
Temperature 
Humidity 

 
to IEC 721-3-3 
class 3K5 
0...+50 °C 
<95 % r.h. 

Transport 

Climatic conditions 
Temperature 
Humidity 
Mechanical conditions 

to IEC 721-3-2 
class 2K3 

25...+70 °C 

<95 % r.h. 
class 2M2 

Storage 

Climatic conditions 
Temperature 
Humidity 

to IEC 721-3-1 
class 1K3 

25...+70 °C 

<95 % r.h. 

 conformity to 

EMC directive 
Low voltage directive 

 
89/336/EEC 
73/23/EEC and 93/68/EEC 

N474

 

C-Tick

 conformity to 

EMC emission standard 

 
AS/NSZ 4251.1:1994 

Product standards 

Automatic electrical controls for household and 
similar use 

 
EN 60 730 – 1 and 
EN 60 730 – 2 - 9 

Electromagnetic compatibility 

Emissions 
Immunity 

 
EN 50 081-1 
EN 50 082-1 

Safety class 

II to EN 60 730 

Pollution class 

normal 

Degree of protection of housing 

IP 30 to EN 60 529 

Connection terminals 

Use solid wires or prepared 
stranded wires. 
2 x  0.4-1.5 mm

2

 or 1 x 2.5 mm

2

 

Weight 0.25 

kg 

Colour of housing front 

white, NCS S 0502-G (RAL9003) 

Operational data 

Environmental 
conditions 

Norms and standards 

General 

7

Содержание LXRCC10

Страница 1: ...Providing indoor climate comfort Application guide LXRCC10 AGU 0509 E LXRCC10 Remote control...

Страница 2: ......

Страница 3: ...RCC10 1 normal and energy saving mode or OFF Operating mode changeover input for remote control Function for avoiding damage resulting from moisture RCC10 1 Selectable control parameters RCC10 Operat...

Страница 4: ...ing an external operating mode changeover switch provided plant conditions do not call for energy saving or frost protection mode only with the RCC10 or turning the controller s power supply off The h...

Страница 5: ...ility Arbitrary setpoint readjustments can thus be prevented Operating modes The following operating modes are available Heating or cooling mode with automatic changeover and with manually selected fa...

Страница 6: ...oom temperature falls below 8 C and if DIP switch no 3 is set to OFF frost protec tion mode will become active The operating action of the switch N C or N O can be selected Type summary Type reference...

Страница 7: ...l operation and standby 1 3 2 Operating action of switch for external operating mode changeover Changeover activated when contact of switch is closed N O 1 Changeover activated when contact of switch...

Страница 8: ...r makes a reset during which the fan LED flashes indicating that the reset has been correctly made This takes about 3 seconds Then the controller will be ready to operate Prior to fitting the changeov...

Страница 9: ...t Climatic conditions Temperature Humidity Mechanical conditions to IEC 721 3 2 class 2K3 25 70 C 95 r h class 2M2 Storage Climatic conditions Temperature Humidity to IEC 721 3 1 class 1K3 25 70 C 95...

Страница 10: ...n speed III AC 230 V Y11 Control output Valve AC 230 V N O contact for N C valves Y12 Control output Valve AC 230 V N C contact for N O valves Only with the RCC10 Connection diagrams L L B1 M B2 D1 GN...

Страница 11: ......

Страница 12: ...o quality the Specifications Ratings and Dimensions are subject to change without notice and without incurring liability Improper installation adjustment alteration service or maintenance can cause pr...

Отзывы: