Status input D1 and GND
Contact
sensing
Insulation against mains
Operating
action
With the RCC10
With the RCC10.1
SELV DC 6-15V / 3-6 mA
4 kV, extra insulation
selectable (N.O. / N.C.)
(N.O.)
Perm. cable length with copper cable 1.5 mm
2
for connection to terminals B1, B2 and D1
80 m
Setpoint setting range
8...30 °C
Max. control deviation at 25 °C
max.
±
0.7 K
Switching differential in heating mode SDH
(selectable)
1 K or 4 K
Switching differential in cooling mode SDC
(selectable)
0.5 K or 2 K
Setpoint «Energy saving mode », heating
16 °C
Setpoint « Energy saving mode », cooling
28 °C
Setpoint «Standby »
8 °C
Operation
Climatic conditions
Temperature
Humidity
to IEC 721-3-3
class 3K5
0...+50 °C
<95 % r.h.
Transport
Climatic conditions
Temperature
Humidity
Mechanical conditions
to IEC 721-3-2
class 2K3
−
25...+70 °C
<95 % r.h.
class 2M2
Storage
Climatic conditions
Temperature
Humidity
to IEC 721-3-1
class 1K3
−
25...+70 °C
<95 % r.h.
conformity to
EMC directive
Low voltage directive
89/336/EEC
73/23/EEC and 93/68/EEC
N474
C-Tick
conformity to
EMC emission standard
AS/NSZ 4251.1:1994
Product standards
Automatic electrical controls for household and
similar use
EN 60 730 – 1 and
EN 60 730 – 2 - 9
Electromagnetic compatibility
Emissions
Immunity
EN 50 081-1
EN 50 082-1
Safety class
II to EN 60 730
Pollution class
normal
Degree of protection of housing
IP 30 to EN 60 529
Connection terminals
Use solid wires or prepared
stranded wires.
2 x 0.4-1.5 mm
2
or 1 x 2.5 mm
2
Weight 0.25
kg
Colour of housing front
white, NCS S 0502-G (RAL9003)
Operational data
Environmental
conditions
Norms and standards
General
7