background image

Page 1

INSTALLATION INSTRUCTIONS FOR LP KIT USED ON
LGH/KG/KD/ZG 024-090 PACKAGED ROOFTOP UNITS

Litho U.S.A.

507586-01
8/2016
Supersedes 1/2016

©

2016

NATURAL TO LP (PROPANE)

GAS CHANGEOVER KIT

PACKAGED UNITS KITS
AND ACCESSORIES

WARNING

This conversion kit shall be installed by a quali­
fied service agency in accordance with the
manufacturer's instructions and all applicable
codes and requirements of the authority having
jurisdiction. If the information in these instruc­
tions is not followed exactly, a fire, an explosion
or production of carbon monoxide may result
causing property damage, personal injury or
loss of life. The qualified service agency is re­
sponsible for the proper installation of this kit.
The installation is not proper and complete un­
til the operation of the converted appliance is
checked as specified in the manufacturer's in­
structions supplied with the kit.

Shipping and Packing List

Package 1 of 1 contains:

 7- Orifices (3 in 21A01)

 1- Spring kit (2 in 14N21 & 21A02)

 1- Bag assembly containing:

3-Conversion plates (1 in 21A02)

1-Conversion sticker

1-Acrylic sheet

1-J/P19 harness (14N21 & 21A01 only)

Requirements

This conversion kit shall be installed by a qualified service

agency. A qualified service agency is any individual, firm,

corporation or company which either in person or through

a representative is engaged in and is responsible for the

connection, installation, repair or servicing of gas

utilization equipment or accessories, who is experienced

in such work, familiar with all precautions required, and

has complied with all the requirements of the authority

having jurisdiction.

Canadian installations only

 

- The conversion shall be

carried out in accordance with the requirements of the
Provincial authorities having jurisdiction and in
accordance with the requirements of the
CAN/CGA-B149.1 and .2 Installation Code.

Application

The LP/propane gas changeover kit is required for gas

conversion as shown in table 1. The 10

th

 character on the

unit nameplate determines the type of gas valve. For

example, ZGA060S4B

H

1G would contain a two-stage,

high heat gas valve.

Installation

WARNING

Improper installation, adjustment, alteration, ser­
vice or maintenance can cause property damage,
personal injury or loss of life. Installation and ser­
vice must be performed by a licensed professional
HVAC installer or equivalent, service agency, or the
gas supplier

1- Turn main manual shut-off valve off and turn off

electrical supply to unit. Set thermostat to “Off”
position.

2- Open access panels as shown in figure 1. On

LGH/KG/KD units, remove the mullion between the
heat and compressors sections.

TABLE 1

Unit

Cat. No.

Part No.

Htg. Stages

10

th

 Character

LGH036-072S, KG 024-090, KD 024-030H, ZG 036-072

14N20

614839-01

Single-Stage

S, M, T, W, Y, Z

LGH036-072S, KG 024-090, KD 036-060H, ZG 036-072

14N21

614839-02

Two-Stage Med. & High

H, U, Q, X

LGH036-072H, LGH036-074U, KG 036-074, KD 036-060H

21A01

614839-03

Two-Stage Standard

B

LGH048-074U, LGH060H

21A02

614839-04

Four-Stage High

D

Отзывы: