32
1
2
3
Power supply.
Electrical connection between outdoor units.
Indoor motor fan electrical connection.
Printed circuit
board
Electrical
box
Thermostat
connection
Thermostat
connection
Printed circuit
board
Thermostat
connection
Thermostat
connection
Electrical
box
PE L1 L2 L3 N
X1
3N ~ 400V - 50 Hz + PE
PE L1 L2
X1
L3
3 ~ 230V - 50 Hz + PE
MODELS
VOLTAGE
LIMIT
28E/56D
24E/48D
32E/64D
22E/44D
38E/76D
86D
86D
100D
100D
1
1
48D2
44D2
56D2
76D2
64D2
2
3
86D2
100D2
1
1
48D2
44D2
56D2
76D2
64D2
2
3
86D2
100D2
Electrical connection
between outdoor units.
Indoor motor
fan electrical
connection.
Indoor motor
fan electrical
connection.
UNIT
MODEL
POWER SUPPLY
230V THREE-PHASE UNITS
Power supply
WITHOUT
electrical heater.
Power supply
WITH electrical
heater.
Nr. OF CABLES x SECTION (mm )
2
COOLING
HEATING
UNIT
MODEL
POWER SUPPLY
400V THREE-PHASE UNITS
Power supply
WITHOUT
electrical heater.
Power supply
WITH electrical
heater.
Nr. OF CABLES x SECTION (mm )
2
COOLING
HEATING
Electrical connection
between outdoor units.
230 V-3Ph-50Hz
230 V-3Ph-50Hz
230 V-3Ph-50Hz
400 V-3Ph-50Hz
400 V-3Ph-50Hz
198-264 V -3Ph- 50Hz
180-242 V -3Ph- 50Hz
342-462 V -3Ph- 50Hz
198-264 V -3Ph- 50Hz
342-462 V -3Ph- 50Hz
230 V-3Ph-50Hz
230 V-3Ph-50Hz
400 V-3Ph-50Hz
400 V-3Ph-50Hz
198-264 V -3Ph- 50Hz
342-462 V -3Ph- 50Hz
180-242 V -3Ph- 50Hz
342-457 V -3Ph- 50Hz
4 x 1,5
4 x 1,5
4 x 1,5
4 x 1,5
4 x 1,5
4 x 95
4 x 2,5
4 x 16
10 x 1
4 x 2,5
4 x 2,5
4 x 16
14 x 1
4 x 95
4 x 2,5
4 x 2,5
8 x 6
16 x 1
4 x 2,5
8 x 6
20 x 1
4 x 70
4 x 70
4 x 70
4 x 95
4 x 95
4 x 25
4 x 25
4 x 35
4 x 50
4 x 50
4 x 1,5
4 x 1,5
4 x 1,5
4 x 1,5
4 x 1,5
5 x 35
4 x 2,5
4 x 6
10 x 1
4 x 2,5
4 x 2,5
4 x 6
14 x 1
5 x 50
4 x 2,5
4 x 2,5
8 x 4
16 x 1
4 x 2,5
8 x 4
20 x 1
5 x 25
5 x 25
5 x 35
5 x 35
5 x 50
5 x 10
5 x 10
5 x 16
5 x 25
5 x 25
4 x 120
4 x 150
5 x 50
5 x 70
VOLTAGE OPERATING LIMITS
- Connect the power supply cables to the terminals in the electric box through the grommet.
- The sections have been calculated for a length no longer than 50m and a voltage drop of 10V.
Do not start the unit if the drop is greater than this.
- The wiring and circuit breakers to be mounted in the installation must comply with the Regulations in force.
- Ground wires must be properly connected and have a greater length than the phase wires.
FOR UNITS MODELS:
44D2-48D2
56D2-64D2-76D2
86D2-100D2
INDOOR
SECTION
MASTER
OUTDOOR SECTION
SLAVE
OUTDOOR SECTION
INDOOR
SECTION
OUTDOOR
SECTION
2.- INSTALLATION
2.8.- ELECTRICAL CONNECTION
1
3
1
3
3
3
2