Page 16
ELECTRICAL DATA
3 TON
KHA036S
1
Voltage - 60hz
208/230V - 1 Ph
208/230V - 3 Ph
460V - 3 Ph
575V - 3 Ph
Compressor 1
Rated Load Amps
16.7
10.4
5.8
3.8
Locked Rotor Amps
79
73
38
36.5
Outdoor Fan
Motors (1)
Full Load Amps (total)
1.7
1.7
1.1
0.7
Power
Exhaust
(1) 0.75 HP
Full Load Amps (total)
5
5
2.2
1.5
Service Outlet 115V GFI
15 Amps
15 Amps
15 Amps
15 Amps
Indoor
Blower
Motor
Horsepower
.5
1.5
.5
1.5
2
.5 1.5
2
.5 1.5
2
Full Load Amps
3.9
11
3.9
6.6
7.5
2
3
3.4
2
2.4 2.7
2
Maximum
Overcurrent
Protection
Unit Only
40
50
25
30
30
15 15 15 15 15 15
with (1) 0.75 HP
Power Exhaust
45
50
30
35
35
15 15 15 15 15 15
3
Minimum
Circuit
Ampacity
Unit Only
27
34
19
22
23
11
12 12
8
8
9
with (1) 0.75 HP
Power Exhaust
32
39
24
27
28
13
14 14
9
10 10
ELECTRIC HEAT DATA
Electric Heat Voltage
208
240
208
240
208
240
208
240
208
240
480 480 480
600 600 600
2
Maximum
Overcurrent
Protection
Unit +
Electric Heat
7.5 kW
70 70 70 80
40
45
45
45 45 50 25 25 25
20 20 20
15 kW
100 110 110
125
60
70
70
70 70 70 35 35 35 30 30 30
3
Minimum
Circuit
Ampacity
Unit +
Electric Heat
7.5 kW
61 66
68 73 39
42
41
44 42
45
22
23
24
17 17 18
15 kW
95 105
102 112
58
64
61
67
62
68 33 34 35
26 26
27
2
Maximum
Overcurrent
Protection
Unit +
Electric Heat
and (1) 0.75 HP
Power Exhaust
7.5 kW
70 80 80 80 45
50
50
50 50 50 25 25 30
20 20 20
15 kW
100 110 110
125 70
70
70
80 70 80
40 40 40
30 30 30
3
Minimum
Circuit
Ampacity
Unit +
Electric Heat
and (1) 0.75 HP
Power Exhaust
7.5 kW
66
71 73 78
44
47
46
49
47 50
24
25
26
18
19 19
15 kW
100 110
107 117 63
69
66
72 67 73 36 37 37 27 28 28
ELECTRICAL ACCESSORIES
Disconnect
Kit
Standard Access -
0-7.5 kW 20W15
20W15
20W15
20W15
20W15
20W15
20W15
15 kW
20W16
20W16
20W15
20W15
20W15
20W15
20W15
Hinged Access -
0-7.5 kW
20W21
20W21
20W21
20W21
20W21
20W21
20W21
15 kW
20W22
20W22
20W21
20W21
20W21
20W21
20W21
Fuse Block
Unit Only
17W95 17W97 18W00
18W01
18W01
18W06
18W06
Unit + Power Exhaust
17W96 17W97 18W01
18W02
18W02
18W06
18W06
1
Extremes of operating range are plus and minus 10% of line voltage.
2
HACR type breaker or fuse.
3
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
Содержание KHA SERIES
Страница 41: ...Page 41 KHA036 048 060 Y Voltage 1 2 5 9 3 11 6 7 8 4 4 5 5 8 9 9 10...
Страница 42: ...Page 42 KHA036 048 060 G J Voltage 1 2 5 9 3 11 6 7 8 4 4 5 5 7 9 9 10 11...
Страница 46: ...Page 46 T1EH 7 5 10 15 22 5 kW P VOLTAGE 1 3 4 5 6 7 2 4 4 4 7 7 7...
Страница 47: ...Page 47 T1EHA 7 5 15 22 5kW Y VOLTAGE KHA SERIES UNITS 1 3 4 5 6 7 2 4 7...
Страница 48: ...Page 48 T1EHA 7 5 15 22 5kW G J VOLTAGE KHA SERIES UNITS 1 3 4 5 6 7 2 4 7...