G-Burners
Periodically examine burner flames for proper
appearance during the heating season. Before each
heating season examine the burners for any deposits or
blockage which may have occurred.
Clean burners as follows:
1- Turn off both electrical power and gas supply to unit.
2- Remove blower access panel.
3- Remove top burner box panel and screws securing
burners to burner support and lift the individual
burners or the entire burner assembly from the
orifices. See figure 26. Clean as necessary.
4- Locate the ignitor under the right burners. Check
ignitor spark gap with appropriately sized twist drills
or feeler gauges. See figure 27.
5- Replace burners and screws securing burner. See
figure 26.
6- Replace access panel.
BURNER BOX ASSEMBLY
FIGURE 26
GAS VALVE
GAS MANIFOLD
FLAME
SENSOR
BURNER
ASSEMBLY
IGNITOR
FIGURE 27
IGNITOR
SPARK GAP
SHOULD BE 1/8”
(3mm)
WARNING
Danger of explosion. Can cause injury or
death. Do not overtighten main burner
mounting screws. Snug tighten only.
7- Restore electrical power and gas supply. Follow
lighting instructions attached to unit and use
inspection port in access panel to check flame.
H-Combustion Air Inducer
A combustion air proving switch checks combustion air
inducer operation before allowing power to the gas
controller. Gas controller will not operate if inducer is
obstructed.
Under normal operating conditions, the combustion air
inducer wheel should be checked and cleaned prior to the
heating season. However, it should be examined
periodically during the heating season to establish an
ideal cleaning schedule. With power supply
disconnected, the condition of the inducer wheel can be
determined by looking through the vent opening.
Clean combustion air inducer as follows:
1- Shut off power supply and gas to unit.
2- Disconnect pressure switch air tubing from
combustion air inducer port.
3- Remove the mullion on the right side of the heat
section.
4- Remove and retain screws securing combustion
air inducer to flue box. Remove vent connector.
See figure 28.
5- Clean inducer wheel blades with a small brush and
wipe off any dust from housing. Clean accumulated
dust from front of flue box cover.
6- Replace the mullion on the right side of the heat
section.