Page 2
SPECIFICATIONS
Model No.
HP29-018
HP29-024
HP29-030
HP29-036−1ph
HP29-036−3ph
Net face area
Outer coil
11.41 (1.06)
11.41 (1.06)
15.21 (1.43)
15.21 (1.41)
15.21 (1.41)
Outdoor
Net face area
sq. ft. (m
2
)
Inner coil
- - - -
- - - -
5.44 (.51)
14.50 (1.35)
5.44 (.51)
Outdoor
Coil
Tube diam.−in. (mm) no. of rows
5/16 (7.9) 1
5/16 (7.9) 1
5/16 (7.9) 1
5/16 (7.9) 2
5/16 (7.9)−1.37
Coil
Fins per inch (m)
22 (866)
22 (866)
18 (709)
18 (709)
22 (866)
Diameter−in. (mm) no. of blades
18 (457) 3
18 (457) 3
18 (457) 4
18 (457) 4
18 (457) − 4
Outdoor
Motor hp (W)
1/6 (124)
1/6 (124)
1/6 (124)
1/6 (124)
1/6 (124)
Outdoor
Coil
F
Cfm (L/s)
2400 (1135)
2400 (1135)
2550 (1203)
2530 (1193)
2500 (1180)
Coil
Fan
Rpm
1105
1105
1115
1110
1100
Watts
180
180
190
195
200
*Refrigerant charge furnished (HCFC-22)
4 lbs. 2 oz. (1.86 kg) 4 lbs. 1oz. (1.83 kg)
5 lbs.12 oz. (2.6 kg)
7 lbs.2 oz. (3.22kg) 6 lbs 0 0z. (2.72kg)
Liquid line in. (mm) o.d. conn. (sweat)
**3/8 to 5/16 (8)
**3/8 to 5/16 (8)
**3/8 to 5/16 (8)
3/8 (9.5)
3/8 (9.5)
Vapor line in. (mm) o.d. conn. (sweat)
5/8 (15.9)
5/8 (15.9)
3/4 (19.1)
3/4 (19.1)
3/4 (19.1)
Shipping weight lbs. (kg) 1 package
152 (69)
152 (69)
161 (73)
173 (78.5)
193 (88)
*Refrigerant charge sufficient for 15 ft. (4.5 m) length of refrigerant lines.
**5/16 to 3/8 reducer coupling supplied with unit.
SPECIFICATIONS
Model No.
HP29-042−1ph
HP29-042−3ph
HP29-048
HP29-060
Net face area sq ft (m
2
)
Outer coil
15.21 (1.41)
15.21 (1.41)
15.21 (1.41)
21.11 (1.96)
Outdoor
Net face area - sq. ft. (m
2
)
Inner coil
14.50 (1.35)
5.44 (.51)
14.50 (1.35)
20.31 (1.9)
Outdoor
Coil
Tube diameter in. (mm) & no. of rows
5/16 (7.9) − 2
5/16 (7.9) − 1.37
5/16 (7.9) 2
5/16 (7.9) 2
Fins per inch (m)
18 (709)
22 (866)
18 (709)
18 (709)
Diameter in. (mm) & no. of blades
18 (457) − 4
18 (457) − 4
18 (457) 4
18 (457) 4
Outdoor
Motor hp (W)
1/3 (249)
1/6 (124)
1/3 (249)
1/3 (249)
Outdoor
Coil
F
Cfm (L/s)
2975 (1403)
2500 (1180)
3020 (1425)
4330 (2043)
Coil
Fan
Rpm
1130
1100
1125
1075
Watts
310
200
330
420
*Refrigerant charge furnished (HCFC-22)
8 lbs. 5 0z. (3.76 kg) 7 lbs. 10 0z. (3.45 kg) 7 lbs. 12 oz. (3.51 kg) 11 lbs. 13 oz. (5.34kg)
Liquid line in. (mm) o.d. connection (sweat)
3/8 (9.5)
3/8 (9.5)
3/8 (9.5)
3/8 (9.5)
Vapor line in. (mm) o.d. connection (sweat)
7/8 (22.2)
7/8 22.2)
7/8 (22.2)
1-1/8 (28.6)
Shipping weight lbs. (kg) 1 package
182 (83)
199 (90.3)
190 (86.2)
254 (115.2)
*Refrigerant charge sufficient for 15 ft. (4.5 m) length of refrigerant lines.
ELECTRICAL DATA
Model No.
HP29−211−
1
HP29−211−
2
HP29−261−
1
HP29-261−
2
HP29-311
HP29-411
HP29-413
Line voltage data 60 hz
208/230v
1ph
208/230v
1ph
208/230v
1ph
208/230v
1ph
208/230v
1ph
208/230v
1ph
208/23v
3ph
460v
3ph
Rated load amps
8.6
7.9
9.8
10.1
13.7
16.2
10.3
4.3
Compressor
Power factor
.97
.97
.96
.96
.92
.90
.83
.83
Locked rotor amps
49.0
49.0
56.0
60.0
75.0
96.0
75.0
40.0
Outdoor Coil
Full load amps
1.1
1.1
1.1
1.1
1.1
1.1
1.1
0.55
Outdoor Coil
Fan Motor
Locked rotor amps
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.0
Rec. maximum fuse or circuit breaker size (amps)
20
15
20
20
30
35
20
10
*Minimum circuit ampacity
11.9
11.0
13.5
13.8
18.4
21.4
14.0
6.5
*Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
NOTE Extremes of operating range are plus 10% and minus 5% of line voltage.
ELECTRICAL DATA
Model No.
HP29-461
HP29-463
HP29-511
HP29-513
HP29-651
HP29-653
Line voltage data 60 hz
208/230v
1ph
208/230v
3ph
460v
3ph
208/230v
1ph
208/230v
3ph
460v
3ph
575v
3ph
208/230v
1ph
208/230v
3ph
460v
3ph
575v
3ph
Rated load amps
17.5
12.8
6.4
23.4
14.0
7.1
5.8
26.9
17.3
9.0
7.1
Compressor
Power factor
.98
.93
.93
.98
.88
.88
.88
.98
.86
.86
.86
Locked rotor amps
92.0
87.0
44.0
110.0
91.0
46.0
37.0
123.0
128.0
64.0
51.0
Outdoor Coil
Full load amps
1.1
1.1
0.55
1.9
1.9
0.90
0.90
1.9
1.9
0.90
0.90
Outdoor Coil
Fan Motor
Locked rotor amps
1.9
1.9
1.0
4.1
4.1
2.1
2.1
4.1
4.1
2.1
2.1
Rec. max. fuse or circuit breaker size (amps)
40
25
15
50
30
15
10
60
40
20
15
*Minimum circuit ampacity
23.0
17.1
8.6
31.2
19.4
9.8
8.2
35.5
23.5
12.2
9.8
*Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
NOTE Extremes of operating range are plus 10% and minus 5% of line voltage.
Содержание HP29 Series
Страница 20: ...Page 20 HP29 SINGLE PHASE WITH RECIPROCATING COMPRESSOR 1 2 3 5 6 4 7 8 9 10 11 12 15 14 16 17 18 19 20 1 19 19...
Страница 21: ...Page 21 HP29 SINGLE PHASE WITH RECIPROCATING COMPRESSOR 1 2 3 5 6 4 7 8 9 10 11 12 15 14 16 17 18 20 1 19 19...
Страница 23: ...Page 23 HP29 SINGLE PHASE WITH SCROLL COMPRESSOR 1 2 3 6 4 7 8 9 10 11 12 15 14 16 17 18 19 20 1 19 19 4...
Страница 24: ...Page 24 HP29 SINGLE PHASE WITH SCROLL COMPRESSOR 1 2 3 6 4 7 8 9 10 11 12 15 14 16 17 18 20 1 19 19 4...