
Page 16
505023M 04/06
BPS BPS
PS PS
Harmony III
t
Zone Control System Option 3 − Lennox Heat Pump &
Lennox Variable-Speed Gas Furnace (Dual Fuel)
IMPORTANT!
Connectivity is NOT COMPLETE until all electrical adjustments (jumpers and wiring changes) have been made.
See Electrical Adjustments for SureLight
®
Board (page 6) and for BDC3 Board (page 7).
BALANCE POINT
SENSOR 56A83
DAMPERS(Spring
open, power close)
85
90
100
110
120
130
0%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
NotUsed
OFF
0%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
Zone4
PIAB
Zone1
PIAB
Zone2
PIAB
Zone3
PIAB
SYSTEM
Configuration
E−HEAT
Stages
Heating
Staging Temp
50
55
60
Cooling
Staging Temp
0%
20%
40%
0%
25%
50%
75%
OFF
0%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
OFF
0%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
Cont. Air
Reduction
Heating Air ‘
Reduction
DF
1
2
3
HP
2COOL
2HP
GAS
1COOL
1HP
TDO
Fault
Recall
OFF
Vacation
Mode
Selector
ON
OFF
E−Heat
Selector
ON
1/2 AMP
DS FUSE
S
P
ARE DS FUSE
3 AMP
P
ANEL FUSE
S
P
ARE P
ANEL FUSE
Thermostat 4
Thermostat 3
W C Y G R
W C Y G R
Balance
Point
Sensor
Pressure Switch
Diag4
Diag3
Diag2
Diag1
E−Heat
Vacation
damper 4
damper 3
Damper 2
Damper 1
Mode
Mode
Fan
Cooling
ElectHeating
Heating
Status
PRESSURE SWITCH
21J18 (R−22)
51M08 (R−410A)
ESD CAUTION
TOUCH A GROUNDED METAL
OBJECT BEFORE TOUCHING
THE CIRCUIT BOARD
LENNOX
Harmony III
t
V3.0 2004
System Configuration & E−Heat
PIAB jumper
Air reduction jumper
Heat/cool staging jumper
1 2 3
120
VAC
24
VAC
C R
Vacation OFF for individual zone
control.
Vacation ON for all zones to be
conditioned at the same time.
Emergency Heat OFF to allow
Heat Pump to provide heat.
Emergency Heat ON to force
auxiliary (backup) heat to provide
all heating (disallows heat pump
from providing any heat).
Damper1
NC
NO
C
das
Damper2
NC
NO
C
Damper3
NC
NO
C
Damper4
NC
NO
C
Thermostat 2
Thermostat 1
W C Y G R
W C Y G R
W C Y G R
W C Y G R
Y1
Y2
O
RC
W1−Def
R
C
Y1
Y2
O
W1
R
G
W1
W2
C
DS
RH
G
W1
W2
W3
DS
Equipment
Equipment
DISCHARGE AIR SENSOR
88K38 (included)
IMPORTANT
Connect
thermostat-gauge
wire to SureLight
®
board C" terminal
HEAT PUMP
VARIABLE
SPEED
FURNACE
Figure 21
NOTE
− Do not wire Y" wire(s) from the
Harmony III
t
zone control board to the
furnace terminal strip. Doing so causes
the motor to search" for proper CFM.
System Operation
This section describes the operation of the zone control
system.
Zone Thermostats
Only electronic thermostats with a C" terminal may be
used with the zone control system. The zone control sys-
tem distinguishes between heat pump and heat/cool ap-
plications via the SYSTEM jumper placement on the zone
control board.
1. Cool / Heat / Auto−Changeover ModesZone thermo-
stats send a heating or cooling signal to the zone con-
trol board. Thermostat servicing zone 1 is the central
control thermostat. Zones 2, 3 and 4 each have their
own thermostat. Thermostats may be standard or au-
tochangeover type.
Heat and cool demands present at the same time from
different zones (opposing demands) are satisfied on a
first come first served basis. If a heating demand and a
cooling demand reach the zone control board at the
same time, the heating demand is satisfied first. If op-
posing demands persist, the system will work to satis-
fy the current demand for a maximum of 20 minutes,
then switch over and try to satisfy the opposing de-
mand for a maximum of 20 minutes. When either de-
mand is satisfied, the system works to satisfy the other
demand.
NOTE − Allowing opposing demands to persist may
consume excess energy. If this condition continues,
check the installation (i.e. zone arrangement, supply
registers, return registers, zone loads etc.) and make
adjustments as necessary. Table 9 shows the time de-
lays that may be expected when opposing demands
are received from the zone thermostats.
The zone control system acknowledges a new or op-
posing demand as soon as it is received by illuminating
that zone’s thermostat input lights. If the first demand
is not satisfied by the time the delays elapse, the sys-
tem switches over and begins satisfying the opposing
demand. During the switchover, a delay may be im-
posed before the system begins satisfying the new de-
mand.