SYSTEM Configuration Jumper

The SYSTEM configuration jumpers must be inserted to
select the type of cooling and heating system that has
been installed.

For a furnace and 2−stage air conditioner combination, se-
lect the GAS and 2COOL positions as shown in on the left-
hand side of figure 14. In this configuration, the maximum
discharge temperature the furnace is allowed to run is
160°F (temperature range illustrated in figure 15). At that
temperature, the zone control system removes a heat de-
mand from the furnace for a minimum of 5 minutes and un-
til the temperature comes back within normal operating
temperatures. While at or above 160°F, the control unit sig-
nals for continuous blower operation to those zones from
which a thermostat heat demand is received. When setting
up the furnace control board options, be sure to set the
BLOWER-OFF DELAY to no greater than 210 SECONDS.

For a heat pump with electric backup heat, select the HP
position as shown in on the right-hand side of figure 14. In
this configuration, the maximum discharge temperature
the electric heat or heat pump is allowed to run is 135°F. At
that temperature, the zone control system removes de-
mand from the heating unit for a minimum of 5 minutes and
until the temperature returns to the normal operating tem-
perature range. While at or above 135°F, the control unit
signals for continuous blower operation to those zones
from which a thermostat heat demand is received.

Select the number of equipment cooling stages by placing
the COOL stages jumper to the appropriate side (1COOL
or 2COOL). Similarly, set the number of Heat Pump stages
(1HP or 2HP). Jumper settings on the right-hand side of
figure 14 illustrate the proper settings for a 2-stage heat
pump and two-stage air conditioning system.

SYSTEM Configuration Jumper

(Typical configuration shown; yours may differ)

Gas furnace & 2−stage AC

2-stage heat pump w/1-stage

aux. electric heat & 2−stage AC

SYSTEM

E−HEAT

SYSTEM

E−HEAT

Configuration

Stages

Configuration

Stages

HP

GAS

df

hp

gas

df

2cool

1cool

1

2cool

1cool

1

2hp

1hp

2

2hp

1hp

2

3

3

DOESN’T MATTER

Dual fuel heating & 

1−stage AC & heat pump

SYSTEM

E−HEAT

 

Configuration

Stages

HP

GAS

df

gas

/df

2cool

1cool

1

2cool

1cool

1

2hp

1hp

2

2hp

1hp

2

3

3

Figure 14

NOTE − Variations to the jumper configuration settings
shown in figure 14 are described in figure 18.

When using a heat pump with electric backup heat, insert
an E−HEAT jumper to select the total number of available
electric heat stages. Upper right-hand view in figure 14
shows 1 heat-strip configuration.

The lower left diagram in figure 14 shows a dual−fuel con-
figuration (heat pump for heat and cool with gas backup
heat). The E−Heat stages jumper must be set to DF for dual
fuel operation.

Heating Staging Temperature Jumper

The Heating Staging Temperature jumper is used to set the
discharge air temperature at which the equipment will turn
second stage on. It is selectable between 85 and 130°F
with a built in differential of 20°F.

During operation, when the discharge air temperature falls
below the setpoint, second stage operation begins. If the
discharge air temperature reaches the setpoint plus 20°F,
second stage operation will cease and first stage operation
will resume until the temperature again falls below the set
point.

The recommended settings for heating staging and maxi-
mum discharge temperatures are as follows (illustrated in
figure 15):

S

Heat Pumps (system configuration jumper: HP; heat-
ing staging jumper: 90°F (range: 85 − 110°F). The max-
imum discharge air temperature at which the heat
pump/electric heat is allowed to run is fixed at 135°F.

S

Gas Furnaces (system configuration jumper: GAS;
heating staging jumper: 120°F (range: 100 − 130°F).
The maximum discharge air temperature at which the
furnace is allowed to run is fixed at 160°F.

Heating Maximum and Minimum Settings

Jumper Setting = 90°F

(Heat Pump Settings 85°F−110°F)

Jumper Setting = 120°F 

(Furnace Settings 100°F−130°F)

blower only

low fire

either speed

high fire

Settings can be from 85°F to

130°F with 20°F differential

135°F

110°F

160°F

140°F

120°F

90°F

total
differential =
20°F

total

differential =

20°F

INCREASING

TEMPERA

TURE

Figure 15

When the zone control system is applied to a heat pump
with electric heat, the electric heat will be staged on to
maintain the discharge air temperature set by the heating
stage jumper position.

Содержание HARMONY II

Страница 1: ...cs Codes 25 Troubleshooting Diagrams 27 PIAB Calculation Worksheet 30 RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE Shipping Packing List Items shipped with the Harmony IIIt Zone Control System inclu...

Страница 2: ...ke comfort settings for each zone A programmable thermostat should be used to provide a specialized heating and cooling sequence While the sys tem is in the zone mode a programmable thermostat con tro...

Страница 3: ...nical or electro mechanical thermostats will not work with the Harmony IIIt zone control system Recommended thermostats include S SignatureStatt Thermostat 1 heat 1 cool 81M26 IMPORTANT When using thi...

Страница 4: ...at Pump IMPORTANT LENNOX recommends ONLY Harmony II and Harmony IIIt Zone Control Systems for use with Variable Speed Blower Motor VSM technology 1 Lennox Blower Coil Unit with VSM Use ONLY blower coi...

Страница 5: ...appliances and sunny windows near concealed pipes and chimneys or in unconditioned spaces such as closets or exterior walls Dampers Motorized dampers in the supply duct system regulate air to the zon...

Страница 6: ...RTANT Be sure to cut jumper W914 if not cut the zone con trol board DS fuse will blow WARNING Electrical Shock Hazard Disconnect power from unit and wait at least five minutes to allow capacitors to d...

Страница 7: ...s remove any factory installed jumper between terminal R and W1 W2 or W3 D In all cases cut and tape wire 7 see figure 8 on the VSM harness that runs from the BDC3 board to the motor 9 Figure 8 4 5 1...

Страница 8: ...on Chart Model Equivalent Positions Harmony II 25 35 45 55 65 75 85 95 Harmony IIIt 0 10 30 40 50 70 80 90 When jumpers are set to 0 this corresponds to the mini mum air volume available according to...

Страница 9: ...is re duced during heating mode Determining Actual Air Delivered By Blower The actual CFM delivered to each zone will be determined by the zone control system settings blower motor control board setti...

Страница 10: ...AB 8 x CFM Max 2220 Min 720 x 1500 Min CFM 720 TOTAL 1920 CFM 4 Determine total air delivered during a continuous blower call Calculate these totals using the formu las and example Table 8 which uses...

Страница 11: ...hp 1hp 2 2hp 1hp 2 3 3 DOESN T MATTER Dual fuel heating 1 stage AC heat pump SYSTEM E HEAT Configuration Stages HP GAS df gas df 2cool 1cool 1 2cool 1cool 1 2hp 1hp 2 2hp 1hp 2 3 3 Figure 14 NOTE Vari...

Страница 12: ...g close to AC house wiring If this cannot be avoided limit close parallel of power and control wiring to a few feet Dampers and Damper Transformer Wiring Connect dampers to the zone control board as s...

Страница 13: ...NOTE If not already done remove the wire to K20 blower relay terminal 7 on BDC3 board and tape it off Also be sure the factory installed jumper between terminal R and W1 W2 and W3 has been removed He...

Страница 14: ...11 120 VAC 24 VAC C R IMPORTANT Connectivity is NOT COMPLETE until all electrical adjustments jumpers and wiring changes have been made See Electrical Adjustments for SureLight Board page 6 and for BD...

Страница 15: ...UNDED METAL OBJECT BEFORE TOUCHING THE CIRCUIT BOARD LENNOX Harmony IIIt V3 0 2004 System Configuration E Heat jumper settings page 11 piab jumper settings page 8 air reduction jumper settings page 9...

Страница 16: ...quipment DISCHARGE AIR SENSOR 88K38 included IMPORTANT Connect thermostat gauge wire to SureLight board C terminal HEAT PUMP VARIABLE SPEED FURNACE Figure 21 NOTE Do not wire Y wire s from the Harmony...

Страница 17: ...ing the blower may continue after the end of a demand until the heater is cooled sufficiently Cooling Operation When the Harmony IIIt zone control system receives a thermostat cooling call the followi...

Страница 18: ...p heat or in a dual mode system the heat demand is satisfied by the gas furnace Operation Troubleshooting Indicators Zone Control Board LEDs The zone control system operation is indicated by light emi...

Страница 19: ...ng proper operation Perform the gas and heat pump heating checks on pages 20 through 24 Table 9 Time Delays Delay Time Function Blower Off Delay gas heat only 3 1 2 min Gas Furnace only Dumps air into...

Страница 20: ...e damper functions properly repeat these steps for zones 2 4 Gas Heating Checkout Multiple Zone Prerequisites S All zone thermostats set to Heat OUTPUT STATUS LEDs DAMPER 2 3 4 OFF W1 on W RED on hEAT...

Страница 21: ...LEDs DAMPER 2 3 4 on DAMPER 1 Off W RED ON event Sequence 1 Y1 ON 2 Y2 IF EQUIPPED ON IF NO SIGNIFICANT WARMING AFTER 4 MIN 3 W1 ON IF NO SIGNIFICANT WARMING AFTER 4 MIN THEN W2 THEN W3 PRESSURE SWITC...

Страница 22: ...ing 3 1 2 minute purge Other zones damper LEDs are on during the 3 1 2 minute purge dampers closed After 3 1 2 minute delay all dampers LEDs go off dampers open Heat Pump Heating Checkout Central Cont...

Страница 23: ...individual zone damper functions properly repeat these steps for zones 2 4 Gas Heating Checkout Multiple Zone Dual Fuel Option and BPS Prerequisites S All zone thermostats set to Heat S Balance Point...

Страница 24: ...ill produce a faulty reading At 77 F the resistance of the sensor will be 10K ohm at lower probe temperatures ex pect higher resistance at warmer probe temperatures ex pect lower resistance After read...

Страница 25: ...or Some of the errors found in table will cause a fail safe or shutdown condition The system will shutdown after the er ror is present for about five seconds During a shutdown condition all dampers wi...

Страница 26: ...ill cycle from high to off in cooling The compressor will cycle from high to off in heating The furnace will operate normally in gas heat Replace discharge probe If error persists replace zone control...

Страница 27: ...spond to demand 0 volts AC open 24 volts AC closed Dampers should drive closed when 24 volts is jumpered to damper motor Is wiring correct in good condition Figure 23 Line Voltage to transformer 24VAC...

Страница 28: ...n relays may need to be used 24VAC supplied to each thermostat terminal R from zone control system Check each thermostat for output signal when calling Heating output W1 Cooling output Y1 Do dampers r...

Страница 29: ...charge air plenum as de scribed on Page 5 Is it wired cor rectly Does outdoor unit respond to demand Is it operating properly Test Defrost Does outdoor unit initiate and terminate defrost correctly W1...

Страница 30: ...AB 0 2 x 100 20 Zone 1 CFM Required Minimum Maximum Minimum ZONE 1 PIAB x 100 b b ZONE 1 PIAB x 100 b ZONE 1 PIAB x 100 Zone 2 CFM Required Minimum Maximum Minimum ZONE 2 PIAB x 100 b b ZONE 2 PIAB x...

Отзывы: