Page 10
505023M 04/06
3.
Determine heating PIAB and total heating air CFM
delivered during a heating call
Calculate these to-
tals using the formulas and example in Table 7. The ex-
ample uses the following assumptions:
D
Zone 1 Jumper
30%
D
Zone 2 Jumper
50%
D
Zone 3 Jumper
40%
D
Zone 4 Jumper
OFF
D
Zones calling for heat
1 & 3
D
Heat reduction jumper
20
D
Maximum CFM
2220
D
Minimum CFM
720
Table 7
Determine Total Heating CFM Delivered
Formulas:
Total PIAB =
(Sum of Calling Zones
Jumper Positions)
+
(# of Zones Calling − 1)
3
Heating PIAB =
Total PIAB x (1 − Heating air reduction setting)
Total Heating CFM =
Heating PIAB x (CFM Max − Min)
+
(Min CFM)
1st− Find Total PIAB:
[Jumpers 30% +0% +40% +0%]
.30 +.00 +.40 +.00
. . . . . .
+ [2 zones −1]/3
+. 33
. . . . . . . . . . . . . . . . . . . .
TOTAL
1.03
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Blower cannot support 103%; uses 100%
=
1
. . .
2nd− Find Heating PIAB:
b
[Total PIAB]
1
. . . . . . . . . . . . . . . . . . . . . . .
x [1−Heating air reduction setting]
x 1−.2
. . . . .
TOTAL
=
.8
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
3rd− Find Heating Total CFM:
b
[Heating PIAB]
.8
. . . . . . . . . . . . . . . . . . . . .
x [CFM (Max) 2220 − (Min) 720]
x 1500
. . . . . . .
+ [Min CFM]
+ 720
. . . . . . . . . . . . . . . . . . . . . . .
TOTAL
=
1920
CFM
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.
Determine total air delivered during a continuous
blower call
Calculate these totals using the formu-
las and example (Table 8) which uses the same as-
sumptions as table 7, except with zones 1, 2 and 3 call-
ing for cooling, and with 25% air reduction:
Table 8
Determine Total Continuous CFM Delivered
Formulas:
Total PIAB =
(Sum of Calling Zones
Jumper Positions)
+
(# of Zones Calling − 1)
3
Continuous Air PIAB =
Total PIAB x (1 − Cont. air reduction setting)
Total Continuous CFM =
Cont. Air PIAB x (CFM Max −
Min)
+ (Min CFM)
1st− Find Total PIAB:
[Jumpers 30% +50% +40% +0%]
.30 +.50 +.40 +.00
. . . . .
+ [3 zones −1]/3
+. 66
. . . . . . . . . . . . . . . . . . . .
TOTAL
1.86
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Blower cannot support 186%; uses 100%
=
1
. . .
2nd− Find Continuous Air PIAB:
b
[Total PIAB]
1
. . . . . . . . . . . . . . . . . . . . . . .
x [1−Continuous air reduction setting]
1−.25
. .
TOTAL
=
.75
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
3nd− Find Total Continuous CFM:
b
[Continuous Air PIAB]
.75
. . . . . . . . . . . . . .
x [CFM (Max) 2220 − (Min) 720]
x 1500
. . . . . . .
+ [Min CFM]
+ 720
. . . . . . . . . . . . . . . . . . . . . . .
TOTAL
= 1845 CFM
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
IMPORTANT
If any changes are made to the blower speed selec-
tions on the SureLight
®
or BDC3 boards, the zone
control PIAB calculations must be performed again
to ensure proper airflow.