 GAS-FIRED STEAM BOILER

INSTALLATION 

INSTRUCTIONS

PRODUCT LITERATURE

Lennox  Industries Inc.

Dallas, Texas

RETAIN THESE INSTRUCTIONS 

FOR 

FUTURE REFERENCE

These instructions must be 

affixed on or adjacent to the 

boiler.

GAS-FIRED HOT WATER BOILERS

These Gas-Fired Water Boilers are low 

pressure, sectional cast iron boilers Design 

Certified by CSA (Canadian Standards 

Association) for use with Natural and 

Propane Gases.  They are constructed 

and hydrostatically tested for a maximum 

working pressure of 50 psi (pounds per 

square inch) in accordance with A.S.M.E. 

(American Society of Mechanical Engineers) 

Boiler and Pressure Vessel Code Section IV: 

Rules for Construction of Heating Boilers.

 

WARNING

 

Improper installation, adjustment, 

alteration, service, or maintenance can 

cause injury or property damage. Refer 

to this manual. For assistance or additional 

information  consult  a  qualified  installer, 

service agency, or the gas supplier.

Содержание GSB8-E

Страница 1: ...Canadian Standards Association for use with Natural and Propane Gases They are constructed and hydrostatically tested for a maximum working pressure of 50 psi pounds per square inch in accordance wit...

Страница 2: ...imensions Inches Intermittent Ignition w Vent Damper Flue Diameter A Width GSB8 075E 5 11 GSB8 112E 6 14 GSB8 150E 6 17 GSB8 187E 7 21 GSB8 225E 7 24 GSB8 262E 7 27 GSB8 299E 7 30 Add 5 to height for...

Страница 3: ...I Rating Sq Ft 1 GSB8 075E 3 Natural Gas 75 62 82 7 47 196 Propane 70 58 82 7 44 183 1 GSB8 112E 4 Natural Gas 112 91 82 0 68 283 Propane 105 85 80 4 64 267 1 GSB8 150E 5 Natural Gas 150 122 82 0 92 3...

Страница 4: ...whatsoever Introduction Boiler is designed for use in closed heating systems where all steam is returned as condensate and make up water is minimal Boiler is not designed for or intended for use in o...

Страница 5: ...any other gas appliance with improper methods or materials could result in death or serious injury due to fire or to asphyxiation from poisonous gases such as carbon monoxide which is odorless and in...

Страница 6: ...conditions of use Boiler location should not interfere with proper circulation of air Introduce outside air if normal infiltration does not provide necessary air Fresh Air for Combustion on page 11 6...

Страница 7: ...or place any obstruction in discharge line Terminate freely to atmosphere where any discharge will be clearly visible and at no risk of freezing Allow complete drainage of valve and discharge line Ins...

Страница 8: ...from the header one for each main 6 All boilers in gravity return systems must be equipped with a Hartford Loop as shown in Figure 5 7 When piping the vertical risers from the boiler to the header th...

Страница 9: ...9 Figure 4 Recommended Near Boiler Piping Using One Supply Tapping SYSTEM PIPING...

Страница 10: ...LATION SYSTEM PIPING Figure 6 Chilled Water Piping VALVES A B OPEN FOR HEATING CLOSE FOR COOLING VALVES C D CLOSE FOR HEATING OPEN FOR COOLING Figure 5 Recommended Near Boiler Piping Using Two Supply...

Страница 11: ...ter than 0 60 Room volume is greater than 21 cubic feet divided by ACH air changes per hour x Total Input Mbh C Refer to National Fuel Gas Code for opening requirements between connected indoor spaces...

Страница 12: ...uld not be longer than 3 4 the chimney height HT Figure 7 page 13 Vent Pipe Fasten sections of vent pipe with 3 sheet metal screws at each joint to make piping rigid Support horizontal portions of ven...

Страница 13: ...er gas burning appliance to their previous conditions of use 7 Any improper operation of the common venting system should be corrected so the installation conforms with the National Fuel Gas Code ANSI...

Страница 14: ...on and for vent damper troubleshooting guide refer to manual packaged with vent damper Horizontal Installation To Boiler Vent Damper To Chimney NO NO YES YES Flow Install vent damper with actuator to...

Страница 15: ...or dampen excessive vibrations and prevent strain on gas connection Gas valve will not support piping weight Use thread joint compound pipe dope suitable for natural and liquefied petroleum gas Insta...

Страница 16: ...ut off two wires are black One wire is located on secondary of 24 volt transformer second wire is located on pressure limit control F Boilers with PS 802 probe type low water cut off one wire is green...

Страница 17: ...ol knob slightly and turn clockwise to OFF Do not force For Your Safety Read Before Operating WARNING If you do not follow these instructions exactly a fire or explosion may result causing property da...

Страница 18: ...wn on left side of boiler Determine water level when boiler is off and cold when all water in the system is inside the boiler and return piping below water line and everything above water line is air...

Страница 19: ...inner cones in softer blue outer mantel with no yellow Remain still when observing main burner flames Check main burner orifices burner throat and flame ports for dust and lint obstruction if flame ap...

Страница 20: ...ower on and turn thermostat to call for heat C Gas valve opens for approximately 10 seconds time delay on probe type LWCO gas valve will close and red indicator illuminates on LWCO D When water is res...

Страница 21: ...ild up Run connection from boiler drain valve to safe discharge point outside Shut off gas burners open drain valve allow all of water in boiler to drain out Close drain valve Allow boiler to cool slo...

Страница 22: ...bead of 400 F RTV silicone to four mounting surface flanges of flue collector Mount flue collector on heat exchanger Tighten nuts and bolts 6 Seal front edge and four corners of flue collector to hea...

Страница 23: ...e joints Rollout switch blown Have your service technician check heat exchanger for blockage Chimney flue is blocked Spill switch contacts open requiring manual reset of spill switch Have your service...

Страница 24: ...s appliance must be replaced it must be replaced with type 105 C Thermoplastic wire or its equivalent Figure 13 Wiring Diagrams For Boilers With PS 802 Probe Type Low Water Cut Off Shown PS802 PS802 C...

Страница 25: ...ny of the original wire as supplied with this appliance must be replaced it must be replaced with type 105 C Thermoplastic wire or its equivalent Figure 17 Wiring Diagrams For Boilers With 67D 1 Float...

Страница 26: ...l Model WF 2U 24 water feeder maybe used with either of the low water cutoffs listed Water feeder maintains safe minimum water level Keeps boiler running by compensating for minor evaporative steam le...

Страница 27: ...27 REPAIR PARTS...

Страница 28: ...28 REPAIR PARTS...

Страница 29: ...29 REPAIR PARTS...

Страница 30: ...30 REPAIR PARTS Safety Relief Valve 14 11 NPT X 4 Nipple PF 033 02...

Страница 31: ...31 Date Service Performed Company Name Tech Initials Company Address Phone...

Страница 32: ...PRODUCT LITERATURE Lennox Industries Inc Dallas Texas...

Отзывы: