SureLight
®
Control Troubleshooting: Cooling Sequence of Operation
SYSTEM FAN AND EAC TERM. OFF
WITH 2 OR 45-SECOND DELAY.
SURELIGHT
®
CONTROL
COOLING SEQUENCE OF OPERATION
NORMAL COOLING MODE
ABNORMAL COOLING MODE
IGNITION CONTROL MAIN POWER ON.
CONTROL SELF DIAGNOSTIC CHECK.
IS CONTROL OPERATING NORMALLY?
YES
POWER ON
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF WITH NORMAL DELAY.
SIGNAL CIRCUIT BOARD FAILURE AT LED.
INTERRUPT MAIN POWER TO RESET CONTROL.
YES
IS POLARITY REVERSED?
ROLLOUT SWITCH MONITORED CONTINUOUSLY.
IS ROLLOUT SWITCH CLOSED?
CHECK TO ENSURE GAS VALVE IS DE−ENERGIZED.
IS GAS VALVE OFF?
LED: SLOW FLASH RATE REMAINS UNCHANGED
THROUGHOUT COOLING CYCLE.
THERMOSTAT CALLS FOR COOLING.
COMPRESSOR CONTACTOR IS ENERGIZED.
INDOOR BLOWER ON COOL SPEED AND EAC
TERMINAL IS ENERGIZED AFTER 2-SECOND DELAY.
COMPRESSOR OFF.
THERMOSTAT OPENS.
NO
YES
NO
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF WITH NORMAL DELAY.
SIGNAL CIRCUIT BOARD FAILURE AT LED.
SEQUENCE HOLDS UNTIL ROLLOUT SWITCH CLOSES.
NO
IS THERE
PROPER GROUND?
IS VOLTAGE
ABOVE 75 VOLTS?
NO
YES
NO
LED#1 AND LED#2
ALTERNATING FAST
FLASH. SIGNAL
HOLDS UNTIL UNIT IS
PROPERLY GROUND.
LED#1 AND LED#2 ALTERNATING FAST
FLASH. SIGNAL HOLDS UNTIL VOLTAGE
RISES ABOVE 75 VOLTS.
LED#1 FAST FLASH LED#2 SLOW FLASH