Lennox G40DF Series Скачать руководство пользователя страница 13

Page 13

 6 − Single appliance venting configurations with zero lat-

eral lengths (tables 5 and 6), are assumed to have no
elbows in the vent system. For all other vent configura-
tions, the vent system is assumed to have two 90° el-
bows. For each additional 90° elbow or equivalent (for
example two 45° elbows equal one 90° elbow) beyond
two, the maximum capacity listed in the venting table
should be reduced by 10 percent (0.90 x maximum
listed capacity).

 7 − The common venting tables (7, 8, 9, and 10) were gen-

erated using a maximum horizontal vent connector
length of 1−1/2 feet (.46 m) for each inch (25 mm) of
connector diameter as follows:

      TABLE 4

Connector Diameter

inches (mm)

Maximum Horizontal

Connector Length −− feet (m)

3 (76)

4−1/2 (1.37)

4 (102)

6 (1.83)

5 (127)

7−1/2 (2.29)

6 (152)

9 (2.74)

7 (178)

10−1/2 (3.20)

 8 − If the common vertical vent is offset, the maximum

common vent capacity listed in the common venting
tables should be reduced by 20%, the equivalent of two
90° elbows (0.80 x maximum common vent capacity).
The horizontal length of the offset shall not exceed
1-1/2 feet (.46 m) for each inch (25 mm) of common
vent diameter.

 9 − The vent pipe should be as short as possible with the

least number of elbows and angles required to com-
plete the job. Route the vent connector to the vent us-
ing the shortest possible route.

10 − A vent connector shall be supported without any dips

or sags and shall slope a minimum of 1/4 inch (6.4 mm)
per linear foot (305 mm) of connector, back toward the
appliance.

11 − Vent connectors shall be firmly attached to the furnace

flue collars by screws or other approved means, ex-
cept vent connectors of listed type B vent material
which shall be assembled according to the manufac-

turer’s instructions. Joints between sections of single
wall connector piping shall be fastened by screws or
other approved means.

12 − When the vent connector used for Category I ap-

pliances must be located in or pass through a crawl-
space or other areas which may be cold, that portion of
the vent connector shall be constructed of listed
double-wall type B vent material or material having
equivalent insulation qualities.

13 − All venting pipe passing through floors, walls, and ceil-

ings must be installed with the listed clearance to com-
bustible materials and be fire stopped according to lo-
cal codes. In absence of local codes, refer to NFGC
(Z223.1).

14 − No portion of the venting system can extend into, or pass

through any circulation air duct or plenum.

15 − Vent connectors serving Category I appliances shall

not be connected to any portion of mechanical draft
systems operating under positive pressure such as
Category III or IV venting systems.

16 − If vent connectors are combined prior to entering the

common vent, the maximum common vent capacity
listed in the common venting tables must be reduced by
10 percent, the equivalent of one 90° elbow (0.90 x
maximum common vent capacity).

17 − The common vent diameter must always be at least as

large as the largest vent connector diameter.

18 − In no case, shall the vent connector be sized more than

two consecutive table size diameters over the size of
the draft hood outlet or flue collar outlet.

19 − Do not install a manual damper, barometric draft regu-

lator or flue restrictor between the furnace and the
chimney.

20 − When connecting this appliance to an existing dedi-

cated or common venting system, you must inspect the
venting system’s general condition and look for signs
of corrosion. The existing vent pipe size must conform
to these instructions and the provided venting tables
for the USA, and the appropriate venting tables in the
standards of CSA B149 Natural Gas and Propane
Installation Codes for Canada. If the existing venting
system does not meet these requirements, it must be
resized.

Содержание G40DF Series

Страница 1: ...Blower Performance 26 Service 28 Planned Service 30 Repair Parts List 30 Ignition Control Board Diagnostic Codes 31 Troubleshooting 32 G40DF X Start Up Performance Check List 35 WHAT TO DO IF YOU SMEL...

Страница 2: ...7 8 124 Right 2 1 4 57 Left 40 1016 3 3 4 95 5 8 16 AIR FLOW 5 8 16 3 4 19 19 1 2 495 5 8 16 B 5 8 16 5 8 16 Supply Air Supply Air Model No A B C D in mm in mm in mm in mm G40DF X 24A 045 G40DF X 36A...

Страница 3: ...Flue Collector Box Gasket Combustion Air Inducer Gasket Manifold Burner Gas Valve Flame Rollout Switches Flame Sensor Primary Limit Igniter Heat Exchanger Igniter Bracket Combustion Air Pressure Swit...

Страница 4: ...d other applicable local codes Adequate clearance must be made around the air open ings into the vestibule area In order to ensure proper unit operation combustion and ventilation air supply must be p...

Страница 5: ...rating plate D One hundred percent 100 outdoor air must be pro vided for combustion air requirements during construc tion Temporary ducting may supply outdoor air to the furnace Do not connect duct d...

Страница 6: ...B149 installation codes CAUTION Do not install the furnace in a corrosive or contami nated atmosphere Meet all combustion and ventila tion air requirements as well as all local codes All gas fired ap...

Страница 7: ...communicate di rectly or by ducts with the outdoors or spaces crawl or at tic that freely communicate with the outdoors or indirectly through vertical ducts Each opening shall have a minimum free are...

Страница 8: ...pply flue and air intake connections and sufficient installation and servicing clearances See table 1 for correct floor opening size 2 Flange warm air plenum and lower the plenum into the opening 3 Se...

Страница 9: ...re 8 5 Make certain that an adequate seal is made SECURE FROM INSIDE CABINET HEMMED EDGE FIBERGLASS SEALING STRIP Field Provided CABINET SIDE PANEL PLENUM Side View FIGURE 8 Setting Equipment WARNING...

Страница 10: ...m filter sizes A filter must be in place any time the unit is operating TABLE 3 Furnace Cabinet Size Return Air Filter Size inches 14 1 2 14 X 25 X 1 1 17 1 2 16 X 25 X 1 1 21 20 X 25 X 1 1 24 1 2 24...

Страница 11: ...or dedicated gas vent Unlined masonry chimneys are prohibited See figures 11 and 12 for com mon venting A chimney with one or more sides exposed to the outside of the structure is considered to be an...

Страница 12: ...ney passageway must be checked periodically to ensure that it is clear and free of obstructions Do not install a manual damper barometric draft regulator or flue restrictor between the furnace and the...

Страница 13: ...fastened by screws or other approved means 12 When the vent connector used for Category I ap pliances must be located in or pass through a crawl space or other areas which may be cold that portion of...

Страница 14: ...22 339 5 22 65 30 130 39 219 49 330 10 29 59 40 121 51 206 64 315 15 35 53 48 112 61 195 76 301 20 0 0 97 0 202 0 349 0 540 2 10 75 14 149 18 250 20 377 5 21 71 29 143 38 242 47 367 10 28 64 38 133 50...

Страница 15: ...225 115 337 5 51 63 75 128 102 216 144 326 10 NR NR 95 116 128 201 182 308 15 NR NR NR NR 158 186 220 290 20 0 35 96 54 200 78 346 114 537 2 37 74 56 148 78 248 113 375 5 50 68 73 140 100 239 141 363...

Страница 16: ...1 21 50 33 89 47 142 64 220 2 22 53 35 96 49 153 66 235 3 24 55 36 102 51 163 68 248 20 1 21 54 33 99 46 157 62 246 2 22 57 34 105 48 167 64 259 3 23 60 35 110 50 176 66 271 30 1 20 62 31 113 45 181...

Страница 17: ...rat ing and the other appliances which are not operating re main connected to the common venting system If the venting system has been installed improperly you must correct the system as indicated in...

Страница 18: ...ng must be resistant to the actions of liquified petro leum gases NOTE Install a 1 8 inch NPT plugged tap in the field piping upstream of the gas supply connection to the unit The tap must be accessib...

Страница 19: ...sting pressure of gas lines gas valve must be disconnected and isolated See figure 15 Gas valves can be damaged if subjected to pressures greater than 1 2 psig 3 48 kPa 14 inches w c MANUAL MAIN SHUT...

Страница 20: ...correctly and is properly grounded One line voltage EAC terminal is provided on the fur nace control board Any electronic air cleaner rated up to one amp can be connected to this terminal with the ne...

Страница 21: ...TERMINAL DESIGNATIONS HUM LINE XFMR EAC COOL HEAT PARK FLAME NEUTRALS Humidifier 120VAC Input 120VAC Transformer 120VAC Electronic Air Cleaner 120VAC Blower Cooling Speed 120VAC Blower Heating Speed 1...

Страница 22: ...Page 22 G40DF X Typical Schematic Wiring Diagram FIGURE 21...

Страница 23: ...ersonal injury or death Gas Valve Operation Figures 22 23 and 24 1 STOP Read the safety information at the beginning of this section 2 Set the thermostat to the lowest setting 3 Turn off all electrica...

Страница 24: ...uence then restarts at step 1 Gas Pressure Adjustment Gas Flow Approximate 1 Operate unit at least 15 minutes before checking gas flow Determine the time in seconds for one revolu tions of gas through...

Страница 25: ...an Control There is no cooling mode fan on delay however there is a cooling fan off delay of 45 seconds This delay is not adjust able The heating mode fan on time of 45 seconds is not adjust able The...

Страница 26: ...m Watts cfm Watts 0 00 1475 616 1345 554 1150 495 990 415 0 05 1450 606 1320 543 1140 481 985 407 0 10 1425 595 1300 532 1125 466 975 398 0 15 1395 585 1275 521 1115 452 970 390 0 20 1375 574 1255 510...

Страница 27: ...g Air Volume Watts at Different Blower Speeds High Medium High Medium Low Low cfm Watts cfm Watts cfm Watts cfm Watts 00 2475 1276 2280 987 1995 845 1690 698 10 2390 1248 2235 955 1990 829 1675 690 2...

Страница 28: ...ective covering in front of the fur nace during cleaning Cleaning the heat exchanger requires a steel spring snake a reversible drill and a vacuum cleaner The steel spring snake may be constructed usi...

Страница 29: ...place all screws may cause leaks 16 To clean the burner run a vacuum cleaner with a soft brush attachment over the face of burners Inspect in side the burners and crossovers for any blockage Clean the...

Страница 30: ...nace until the items can be repaired or replaced Instruct the homeowners to pay attention to their furnace Situations can arise between annual furnace in spections that may result in unsafe operation...

Страница 31: ...Pressure switch closed prior to activation of combustion air inducer ALTERNATING SLOW FLASH ALTERNATING SLOW FLASH Watchguard burners failed to ignite or lost flame 5 times during single heating dema...

Страница 32: ...VE OFF COMBUSTION AIR INDUCER ON INDOOR BLOWER ON HEATING SPEED LED 1 SLOW FLASH LED 2 OFF GAS VALVE OFF COMBUSTION AIR INDUCER OFF INDOOR BLOWER OFF WITH DELAY LED 1 OFF LED 2 SLOW FLASH Sequence hol...

Страница 33: ...LE HEAT DEMAND WATCHGUARD MODE GAS VALVE OFF COMBUSTION AIR INDUCER OFF INDOOR BLOWER OFF WITH DELAY LEDs SIGNAL WATCHGUARD FAILURE CODE IS 60 MINUTE RESET PERIOD COMPLETE YES 4 SECONDS YES HAS CONTRO...

Страница 34: ...TCH CLOSED LED SLOW FLASH RATE REMAINS UNCHANGED THROUGHOUT COOLING CYCLE THERMOSTAT CALLS FOR COOLING COMPRESSOR CONTACTOR AND SYSTEM FAN ENERGIZED WITH 2 SECOND DELAY COOLING SPEED EAC TERM ENERGIZE...

Страница 35: ...WITH COMB AIR INDUCER SYSTEM FAN REMAINS ON HEATING SPEED SYSTEM FAN REMAINS ON HEATING SPEED HUM TERM DE ENERGIZES WITH COMB AIR INDUCER G40DF X Start Up Performance Check List Filter Clean Secure El...

Отзывы: