SureLight Troubleshooting: Continuous Fan Sequence of Operation
LED: SLOW FLASH RATE REMAINS
UNCHANGED THROUGHOUT SEQUENCE.
MANUAL FAN SELECTION MADE AT THERMOSTAT.
CONTROL (G) ENERGIZES SYSTEM FAN AT ACB
LOW SPEED. ACC. TERM. IS ENERGIZED.
THERMOSTAT CALLS FOR HEAT (W).
THERMOSTAT CALLS FOR COOLING.
THERMOSTAT OPENS.
SYSTEM FAN SWITCHED TO COOLING SPEED.
ACC. TERM. REMAINS ON.
THERMOSTAT OPENS.
SYSTEM FAN OFF. ACC. TERM. OFF.
(AFTER OFF DELAY COMPLETED).
MANUAL FAN SELECTION MADE AT THERMOSTAT.
CONTROL (G) ENERGIZES SYSTEM FAN AT LOW
SPEED. ACC. TERM. ENERGIZED.
NO
YES
YES
NO
HTG ACC. TERM. ENERGIZES
WITH COMB. AIR BLOWER.
BOARD NO. 63K8901
SYSTEM FAN DE-ENERGIZED. SYSTEM FAN ENERGIZES
ON ACB. HEAT SPEED, AFTER NORMAL IGNITION DELAY.
BOARD NO. 24L8501
SYSTEM FAN ENERGIZES ON ACB HEAT
SPEED AFTER NORMAL IGNITION DELAY