Application Guide • 

FLATAIR-AGU-MSL60-1505-E

10 - INSTALLATION

10.2 - REFRIGERANT CONNECTIONS

To locate the outdoor and the indoor units, refer to the following information:

A,B,C: Units positions
L: Total length
1: Gas line
2: Liquid line

POSITION A:

 

A syphon suction must be installed on the vertical line of the gas line 1, and syphons must be installed every 8 meters upward. The 
minimum speed suction must not be below 6 m/s.

POSITION B:

 

Tip the lines toward the outdoor unit. Make special attention to the line length longer than 10m and avoid collapse on pipe lines 
installation.
w

DISPOSICIÓN C:

Install a syphon at the base of the vertical line, no more syphons are necessary.

OUTDOOR UNIT

INDOOR UNIT

OUTDOOR UNIT

OUTDOOR UNIT

INDOOR UNIT

INDOOR UNIT

REFRIGERANT LINES

SIZE

Total length
0 to 30m

Liquid

Gas

Maximum vertical line length (m)

Maximum number of bends

For other positions and lines lengths between 30 and 50m or longer, consult the commercial-technical de-
partment, pipe dimensions, syphon suction, isolations, refrigerant load, line lengths.

Split units are supplied with nitrogen gas.

The installer should remove this gas and charge the units with the charge of refrigerant 

R410A , shown in the table 2.7.2 plus the charge by additional meter shown in the table 2.7.3.

TABLE 2.7.1.: REFRIGERANT LINES

Содержание FLATAIR FIC-H Series

Страница 1: ...lennoxemeia com FMC H FIC H FSC H FLATAIR APPLICATION GUIDE Horizontal packaged air conditioners 10 28 kW FLATAIR AGU MSL60 1505 E...

Страница 2: ......

Страница 3: ...provided by us remain the property of Lennox and must not be utilised except in operation of this product reproduced issued to or made available to third parties without the prior written agreement of...

Страница 4: ...nium fings designed to get a high heat transfer Their dimensions and design of the refrigenrant circuit have been specially worked to obtain the maximum performance of the exchanger increasing the pow...

Страница 5: ...oller constantly monitors more machine parameters than ever to improve rooftop operation and maximize efficiency and reliability 1 3 OPTIONS Flatair units can be equipped with the following options Ma...

Страница 6: ...uide FLATAIR AGU MSL60 1505 E 2 DENOMINATION EXAMPLE Approximate Cooling capacity in kW Revision number Compact unit Outdoor unit Indoor unit 1 Circuit Cooling only Heat pump Cooling only heat pump R4...

Страница 7: ...250 1250 1300 1450 1500 1500 mm 430 430 500 620 775 775 3 8 3 8 1 2 5 8 5 8 5 8 3 4 3 4 7 8 7 8 1 1 8 1 1 8 Application Guide FLATAIR AGU MSL60 1505 E 3 MAIN TECHNICAL FEATURES Cooling capacity coolin...

Страница 8: ...410 FIH 20 4850 4500 3090 FIH 25 5750 5470 3455 FIH 30 5500 5060 3695 FSH 10 3500 2970 2350 FSH 12 3400 2890 2400 FSH 15 4500 4250 3740 FSH 20 5650 5150 4095 FSH 25 6000 5600 4760 FSH 30 5850 5400 500...

Страница 9: ...Dry bulb temperature WB Wet bulb temperature OPERATION LIMITS FOR HEAT PUMP UNITS Maximum temperatures Minimum temperatures Cooling mode Indoor temperature 32 C DB 23 C WB 21 C DB 15 C WB Outdoor temp...

Страница 10: ...25 240 3455 10 12 15 20 25 30 0 3500 3400 4500 5650 6000 5850 10 3410 3325 4460 5550 5920 5755 20 3300 3160 4410 5450 5840 5665 30 3190 3075 4360 5350 5760 5575 40 3080 2980 4310 5250 5680 5485 50 297...

Страница 11: ...81 dB Lw dB A Hz 125 250 500 1000 2000 4000 8000 10 71 67 67 67 4 64 9 64 1 58 3 72 12 71 67 67 67 4 64 9 64 1 58 3 72 15 74 69 72 71 3 69 1 66 0 59 7 76 20 77 71 75 75 8 73 4 70 7 65 7 80 25 79 73 7...

Страница 12: ...06 8 56 4 71 5 82 27 10 95 3 19 8 62 10 60 3 36 8 47 10 18 3 57 8 29 9 71 3 84 8 07 9 18 4 19 7 80 8 59 4 70 7 48 30 10 99 3 19 10 40 10 64 3 36 10 23 10 24 3 57 10 01 9 77 3 84 9 75 9 32 4 21 9 32 8...

Страница 13: ...70 4 90 7 49 12 04 5 35 7 25 11 28 6 02 6 96 10 78 6 59 6 77 27 13 74 4 31 9 85 13 28 4 57 9 66 12 72 4 90 9 43 12 07 5 36 9 13 11 31 6 02 8 77 10 81 6 59 8 52 30 13 77 4 31 11 76 13 31 4 57 11 56 12...

Страница 14: ...10 13 14 99 6 05 9 86 14 15 6 54 9 52 13 22 7 25 9 13 27 16 97 5 17 13 66 16 44 5 40 13 40 15 82 5 69 13 09 15 10 6 06 12 70 14 28 6 55 12 25 13 36 7 25 11 71 30 17 17 5 18 16 27 16 67 5 41 15 96 16 0...

Страница 15: ...3 7 72 13 13 19 30 8 28 12 76 18 25 9 04 12 32 17 32 9 90 11 91 27 21 80 6 97 17 55 21 14 7 31 17 20 20 35 7 74 16 77 19 45 8 30 16 27 18 42 9 07 15 66 17 52 9 92 15 11 30 22 05 7 00 20 78 21 41 7 35...

Страница 16: ...15 69 24 24 9 53 15 31 23 05 10 28 14 85 21 71 11 36 14 30 20 52 12 62 13 78 27 26 19 8 55 20 43 25 34 8 99 20 01 24 34 9 55 19 50 23 18 10 32 18 88 21 85 11 41 18 13 20 68 12 70 17 44 30 26 48 8 58...

Страница 17: ...11 33 17 41 26 86 12 36 16 83 25 00 13 91 16 12 24 60 14 32 15 96 27 31 02 10 03 23 25 29 88 10 60 22 77 28 50 11 34 22 17 26 89 12 37 21 41 25 05 13 92 20 48 24 66 14 33 20 27 30 31 06 10 04 27 90 29...

Страница 18: ...ACITIES CORRECTION COEFICIENTS CALCULATION OF COOLING CAPACITY DEPENDING ON AIR FLOW INDOOR OUTDOOR AIRFLOW RATES INDOOR OUTDOOR AIRFLOW RATES CALCULATION OF HEATING POWER DEPENDING ON AIR FLOW Sizes...

Страница 19: ...10 12 15 20 25 30 5 1 4 9 6 1 7 0 9 4 11 3 13 0 29 1 11 1 13 4 15 8 19 3 25 7 26 7 87 6 31 5 37 1 46 2 71 0 78 0 82 6 131 1 46 1 54 6 68 0 105 3 115 7 122 7 Application Guide FLATAIR AGU MSL60 1505 E...

Страница 20: ...18 FIX 10 12 FSC FSH 10 12 Application Guide FLATAIR AGU MSL60 1505 E 9 DIMENSIONS 9 1 UNIT DIMENSION...

Страница 21: ...19 FIX 15 FSC FSH 15 Application Guide FLATAIR AGU MSL60 1505 E 9 DIMENSIONS 9 1 UNIT DIMENSION...

Страница 22: ...20 FIC FIH 20 FSC FSH 20 Application Guide FLATAIR AGU MSL60 1505 E 9 DIMENSIONS 9 1 UNIT DIMENSION...

Страница 23: ...21 FIC FIH 25 30 FSC FSH 25 30 Application Guide FLATAIR AGU MSL60 1505 E 9 DIMENSIONS 9 1 UNIT DIMENSION...

Страница 24: ...22 FMC FMH 10 12 FMC FMH 15 Application Guide FLATAIR AGU MSL60 1505 E 9 DIMENSIONS 9 1 UNIT DIMENSION...

Страница 25: ...23 FMC FMH 20 FMC FMH 25 30 Application Guide FLATAIR AGU MSL60 1505 E 9 DIMENSIONS 9 1 UNIT DIMENSION...

Страница 26: ...an Outdoor fan Outdoor fan Outdoor fan O utdoor coil O utdoor coil O u t d o o r c o i l O u t d o o r c o i l O utdoor coil O utdoor coil I n d o o r c o i l I n d o o r c o i l I n d o o r c o i l I...

Страница 27: ...hed there are no leaks if the pressure remains the same for at least 24 hours and the final pressure is not less than 10 below the initial pressure 5 Ensure that the gas line is insulated 6 Evacuation...

Страница 28: ...the line length longer than 10m and avoid collapse on pipe lines installation w DISPOSICI N C Install a syphon at the base of the vertical line no more syphons are necessary OUTDOOR UNIT INDOOR UNIT...

Страница 29: ...GERANT CHARGE TABLE 2 7 3 EXTRA REFRIGERANT CHARGE R410A BY METER Liquid Gas g m 10 INSTALLATION 10 3 ELECTRICAL CONNECTIONS Before making any electrical connections ensure that all circuit breakers a...

Страница 30: ...E OUTDOOR UNIT 2 x Shielded twisted pairs AWG 20 100 m maximum 1x Shielded twisted pair AWG20 2 x 1 5 mm 200m maximum CONTROL PANEL NOTES For securing and connecting the Control Panel consult the cont...

Страница 31: ...SENSOR These sensors may be used in conjunction with remote controller allowing the controller to be mounted in a room away from the conditioned space REMOTE DUCT SENSOR The sensor will be located in...

Страница 32: ...LGIUM AND LUXEMBOURG FRANCE GERMANY ITALY NETHERLANDS POLAND PORTUGAL SALES OFFICES OTHER COUNTRIES Due to Lennox s ongoing commitment to quality the specifications ratings and dimensions are subject...

Отзывы: