20
UNIT INSTALLED ON SHOCK ABSORBERS
Ceiling supports
(shock absorbers)
G POINT: Centre of gravity
TABLE 1:
WEIGHT DISTRIBUTION
AND CENTRE OF
GRAVITY COORDINATES
2.- INSTALLATION
Outdoor Sec.
Y
X
Outdoor Sec.
Y
X
MODELS 10-12-16-22
MODELS 24-28-30
Floor supports
(shock absorbers)
WEIGHT DISTRIBUTION (Kg)
CENTRE OF GRAVITY
COORDINATES (G) (mm.)
The bedplate is made up of three galvanized metal channels, capable of withstanding the weight of the units
whether hung from the ceiling or mounted on the floor.
If the unit is floor mounted, then the profiles should be isolated with shock absorbing material such as anti-vibration
or pads. If used, consult the weight distribution table below to make the correct selection. Keep in mind that fans
rotate at approximately 850 rpm.
If the unit is hung, M-10 threaded rods should be used along with shock absorbing ceiling supports.
UNIT HUNG WITH RODS
2.4.- UNIT LOCATION AND WEIGHT DISTRIBUTION
Fan
Comp.
Bat.
B
E
A
F
G
Fan
Bat.
C
D
Indoor Sec.
X
G
Y
G
Fan
Comp.
B
E
A
F
G
Fan
Bat.
C
D
Indoor Sec.
X
G
Y
G
Bat.
10
12
16
22
24
28
30
A
B
C
D
E
F
Total
35
65
10
20
40
35
205
35
65
15
20
40
35
210
70
60
15
30
80
30
285
Model
Point
80
70
20
40
75
45
330
90
100 15
65
85
55
410
95
110
20
65
85
55
430
95
110
25
70
80
55
435
X
G
585
590
565
615
630
600
710
685
760
815
715
825
705
825
Y
G