background image

Page 4

STEP 2 – REFRIGERANT PIPING – 
Flushing Existing Line Set & Indoor Coil 

F

lush the existing line set per industry standards. For

more information, refer to the XP20 Installation and
Service Procedures manual available on DaveNet.

CAUTION - 

DO NOT attempt to flush and re-use ex­

isting line sets or indoor coil when the system con­
tains

 

contaminants (i.e., compressor burn out).

WARNING

Refrigerant can be harmful if it is inhaled. Refrigerant
must be used and recovered responsibly.
Failure to follow this warning may result in personal
injury or death.

WARNING

Polyol ester (POE) oils used with HFC-410A refrigerant
absorb moisture very quickly. It is very important that
the refrigerant system be kept closed as much as
possible. DO NOT remove line set caps or service valve
stub caps until you are ready to make connections.

IMPORTANT !

If this unit is being matched with an approved line set or
indoor unit coil that was previously charged with mineral
oil, or if it is being matched with a coil which was manu­
factured before January of 1999, the coil and line set
must be flushed prior to installation. Take care to empty
all existing traps. Polyol ester (POE) oils are used in Len­
nox units charged with HFC-410A refrigerant. Residual
mineral oil can act as an insulator, preventing proper
heat transfer. It can also clog the expansion device and
reduce system performance and capacity.

Failure to properly flush the system per the XP20 Instal­
lation and Service Procedures will void the warranty.

WARNING

When using a high-pressure gas such as
nitrogen to pressurize a refrigeration or
air conditioning system, use a regulator
that can control the pressure down to 1 or
2 psig (6.9 to 13.8 kPa).

WARNING

Fire, Explosion and Personal Safety Haz­
ard. Failure to follow this warning could
result in damage, personal injury or
death.
Never use oxygen to pressurize or purge
refrigeration lines. Oxygen, when ex­
posed to a spark or open flame, can cause
fire and/or an explosion, that could result
in property damage, personal injury or
death.

IMPORTANT !

Some scroll compressors have an internal vacuum
protector that will unload scrolls when suction pres­
sure goes below 20 psig. A hissing sound will be heard
when the compressor is running unloaded. Protector
will reset when low pressure in system is raised above
40 psig. DO NOT REPLACE COMPRESSOR.

IMPORTANT !

If unit is equipped with a crankcase heater, and outdoor
ambient temperature is below 60°F, unit should be ener­
gized 24 hours before start­up to prevent compressor
damage as a result of slugging.

The XP20 is a variable capacity heat pump system utilizing
variable speed compressor technology. With the variable
speed compressor and variable pumping capacity, addi­
tional consideration must be given to refrigerant piping siz­
ing and application. The guidelines below are to be used
exclusively for the XP20 systems.

HEAT PUMP SYSTEM (HFC­410A)

S

Total equivalent length equals 180 feet (piping and all
fittings included).

NOTE —

 Length is general guide. Lengths may be more or

less, depending on remaining system design factors.

S

Maximum linear (actual) length = 150 feet.

S

Maximum linear liquid lift = 60 feet.

NOTE —

 Maximum lifts are dependent on total length,

number of elbows, etc

.

 that contribute to total pressure

drop.

S

Maximum length vapor riser equals 60 feet.

S

Up to 50 Linear Feet

: Use rated line sizes listed in

table 1.

S

Between 51 and 150 Linear Feet

: Crankcase heater

and non­bleed port TXV factory installed. No addition­
al components required. Vertical vapor riser must be
sized to the vapor riser listed in the table 2 on systems
with line sets longer than 51 feet. Use tables 2 and 3
to determine the correct liquid and vapor line sizes.

S

Over 150 Linear Feet

: not recommended.

S

Additional oil is not required for systems with line
lengths up to 150 feet.

SUCTION TRAPS

For systems with the outdoor unit 5 ­ 60 feet above the in­
door unit, one trap must be installed at the bottom of the
suction riser

.

Содержание Elite XP20-024-230

Страница 1: ...formation consult the Installa tion and Service Procedures manual available as Corp 1408 L10 on DaveNet or through the Technical Support department at 800 453 6669 WARNING Improper installation adjust...

Страница 2: ...ructure observe the following While installing or servicing this unit carefully stow all removed panels so that the panels will not cause injury to personnel objects or nearby structures Also take car...

Страница 3: ...NCHES PER 5 FEET 50 MM PER 1 5 M AWAY FROM BUILDING STRUCTURE MOUNTING SLAB BUILDING STRUCTURE GROUND LEVEL FIGURE 3 LEG DETAIL BASE 2 50 8MM SCH 40 FEMALE THREADED ADAPTER ELEVATED SLAB MOUNTING USIN...

Страница 4: ...n lines Oxygen when ex posed to a spark or open flame can cause fire and or an explosion that could result in property damage personal injury or death IMPORTANT Some scroll compressors have an interna...

Страница 5: ...Sizes for Horizontal Runs Required Vapor Riser Size 024 180 150 60 60 7 8 5 8 036 180 150 60 60 7 8 3 4 048 180 150 60 60 7 8 7 8 060 180 150 60 60 7 8 7 8 Table 3 Liquid Line Diameter Selection Table...

Страница 6: ...id line orifice housing LOW HIGH EXISTING INDOOR UNIT GAUGE MANIFOLD CYLINDER CONTAINING CLEAN HCFC 22 TO BE USED FOR FLUSHING Positioned to deliver liquid refrigerant LIQUID LINE SERVICE VALVE INLET...

Страница 7: ...ur the ends The pipe must remain round Do not crimp end of the line Remove service cap and core from both the suction and liquid line service ports 1 2 LIQUID LINE SERVICE VALVE SERVICE PORT CORE SERV...

Страница 8: ...water saturated cloths WHEN BRAZING LINE SET TO SERVICE VALVES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WRAP SERVICE VALVES To help protect service valve seals during brazing w...

Страница 9: ...S NUT DISTRIBUTOR ASSEMBLY C Install one of the provided Teflon rings around the stubbed end of the expansion valve and lightly lubricate the connector threads and expose surface of the Teflon ring wi...

Страница 10: ...e cylinder of HFC 410A refrigerant to the center port of the manifold gauge set Open the valve on the HFC 410A cylinder vapor only B Open the high pressure side of the manifold to allow HFC 410A into...

Страница 11: ...um pump and closing the manifold gauge valves F When the absolute pressure requirement above has been met disconnect the manifold hose from the vacuum pump and connect it to a cylinder of HFC 410A pos...

Страница 12: ...ge as a result of slugging CAUTION ELECTROSTATIC DISCHARGE ESD Precautions and Procedures Electrostatic discharge can affect electronic components Take care during unit installation and service to pro...

Страница 13: ...s PUSH BUTTON 7 SEGMENT DISPLAY PUMP DOWN WHEN UNIT IS IN PUMP DOWN MODE Pd WILL BE DISPLAYED ON 7 SEGMENT TO ACTIVATE PUMP DOWN MODE THE CONTROL MUST BE IN THE IDLE STATE AND THE PUMP DOWN JUMPER PLA...

Страница 14: ...oise see below Use a wire nut to bundle the four unused wires at each end of the cable Each bundle should also include an additional wire that should be connected on each end to the C terminal as show...

Страница 15: ...cles Charging The XP20 unit is factory charged with enough HFC 410A refrigerant to accommodate a 15 foot length of refrigerant piping Charge should be checked and adjusted using the tables provided on...

Страница 16: ...ealer show you the location of the drain line and how to check for ob structions This would also apply to an auxiliary drain if installed S Check the area around the outdoor unit monthly and re move a...

Страница 17: ...st debris obstructions leaks or cracks Pour water in pans to confirm proper drain age from the pan through to the outlet of the pipe Clean or replace as necessary E Inspect and clean evaporator indoor...

Страница 18: ...G MODE Vapor Pressure Liquid Pressure Supply Air Temperature Ambient Temperature Return Air Temperature HEATING MODE Vapor Pressure Liquid Pressure Supply Air Temperature Ambient Temperature Return Ai...

Отзывы: