STEP 2 −− REFRIGERANT PIPING −− Flush-
ing Existing Line Set & Indoor Coil 

F

lush the existing line set per the following instruc-

tions. For more information, refer to the Installation
and Service Procedures manual available on Dave-
Net. 

CAUTION − 

DO NOT attempt to flush and re−use ex-

isting line sets or indoor coil when the system con-
tains

 

contaminants (i.e., compressor burn out).

NOTE − When installing refrigerant lines longer than 50
feet, refer to the Refrigerant Piping Design and Fabrication
Guidelines manual available on DaveNet (Corp. 9351−L9),
or contact the Technical Support Department Product Ap-
plication group for assistance.

NOTE − For new or replacement line set installation, refer
to Service and Application Note − Corp. 9112−L4 (C−91−4).

TABLE 1

REFRIGERANT LINE SET  INCHES (MM)

Model

Field Connec-

tions

Recommended Line Set

Liquid
Line

Suction
Line

Liquid
Line

Suction
Line

L15 Line Set

−018

3/8"
(10
mm)

3/4" (19
mm)

3/8"
(10
mm)

3/4" (19
mm)

L15−41  15 ft. −
50 ft. (4.6 m − 15
m)

−024

−030

−036

−042

3/8"
(10
mm)

7/8" (22
mm)

3/8"
(10
mm)

7/8" (22
mm)

L15−65  15 ft. −
50 ft. (4.6 m − 15
m)

−048

−060

3/8"
(10
mm)

1−1/8"
(29
mm)

3/8"
(10
mm)

1−1/8"
(29
mm)

Field Fabricated

NOTE  Some applications may required a field provided 7/8" to
1−1/8" adapter

IMPORTANT !

If this unit is being matched with an approved line
set or indoor unit coil that was previously charged
with mineral oil, or if it is being matched with a coil
which was manufactured before January of 1999,
the coil and line set must be flushed prior to installa-
tion. Take care to empty all existing traps. Polyol es-
ter (POE) oils are used in Lennox units charged with
HFC−410A refrigerant. Residual mineral oil can act
as an insulator, preventing proper heat transfer. It
can also clog the expansion device and reduce sys-
tem performance and capacity.
Failure to properly flush the system per this instruc-
tion and the detailed Installation and Service Proce-
dures manual will void the warranty.

WARNING

When using a high pressure gas such as
nitrogen to pressurize a refrigeration or air
conditioning system, use a regulator that
can control the pressure down to 1 or 2
psig (6.9 to 13.8 kPa).

WARNING

Refrigerant can be harmful if it is inhaled. Refrigerant
must be used and recovered responsibly.
Failure to follow this warning may result in personal injury
or death.

WARNING

Fire, Explosion and Personal Safety Haz-
ard. Failure to follow this warning could re-
sult in damage, personal injury or death.
Never use oxygen to pressurize or purge
refrigeration lines. Oxygen, when exposed
to a spark or open flame, can cause fire
and/or an explosion, that could result in
property damage, personal injury or death.

WARNING

Polyol ester (POE) oils used with HFC−410A
refrigerant absorb moisture very quickly. It is very
important that the refrigerant system be kept closed
as much as possible. DO NOT remove line set caps
or service valve stub caps until you are ready to make
connections.

IMPORTANT !

Some scroll compressors have an internal vacuum
protector that will unload scrolls when suction pres-
sure goes below 20 psig. A hissing sound will be
heard when the compressor is running unloaded.
Protector will reset when low pressure in system is
raised above 40 psig. DO NOT REPLACE COM-
PRESSOR.

Содержание Elite XP13-018-230

Страница 1: ...Units HEAT PUMP UNITS 506728 01 7 2012 Supersedes 3 2012 WARNING Improper installation adjustment alteration service or maintenance can cause property damage personal inju ry or loss of life Installat...

Страница 2: ...XP13 018 AND 024 BASE SECTION SMALL 8 3 4 222 5 1 2 140 9 1 2 241 8 1 4 210 13 1 2 343 13 7 8 352 K J UNIT SUPPORT FEET XP13 030 TO 060 BASE WITH ELONGATED LEGS MEDIUM 7 3 4 197 3 1 4 83 27 1 8 689 3...

Страница 3: ...E SET VIBRATION Install unit away from windows FIGURE 2 Install unit level or if on a slope maintain slope tolerance of 2 degrees or 2 inches per 5 feet 50 mm per 1 5 m away from building structure SL...

Страница 4: ...all existing traps Polyol es ter POE oils are used in Lennox units charged with HFC 410A refrigerant Residual mineral oil can act as an insulator preventing proper heat transfer It can also clog the...

Страница 5: ...ve and the two Teflon rings H Use a field provided fitting to temporarily reconnect the liquid line to the indoor unit s liquid line orifice housing LOW HIGH EXISTING INDOOR UNIT GAUGE MANIFOLD CYLIND...

Страница 6: ...d debur the ends The pipe must remain round Do not crimp end of the line Remove service cap and core from both the suction vapor and liquid line service ports 1 2 LIQUID LINE SERVICE VALVE SERVICE POR...

Страница 7: ...ths WHEN BRAZING LINE SET TO SERVICE VALVES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WRAP SERVICE VALVES To help protect service valve seals during brazing wrap water saturated...

Страница 8: ...UT DISTRIBUTOR ASSEMBLY C Install one of the provided Teflon rings around the stubbed end of the check expansion valve and lightly lubricate the connector threads and expose surface of the Teflon ring...

Страница 9: ...ect the cylinder of HFC 410A refrigerant to the center port of the manifold gauge set Open the valve on the HFC 410A cylinder vapor only B Open the high pressure side of the manifold to allow HFC 410A...

Страница 10: ...nd closing the manifold gauge valves F When the absolute pressure requirement above has been met disconnect the manifold hose from the vacuum pump and connect it to a cylinder of HFC 410A positioned t...

Страница 11: ...r damage as a result of slugging CAUTION ELECTROSTATIC DISCHARGE ESD Precautions and Procedures Electrostatic discharge can affect electronic components Take care during unit installation and service...

Страница 12: ...GH VOLTAGE CIRCUITS A B C D 3 FIGURE 12 Typical 24VAC Control Wiring Diagrams Field Installed THERMOSTAT INDOOR UNIT R C W1 Y1 O G R C W1 W2 W3 G R C W1 Y1 O COMMON 1ST STAGE AUXILIARY HEAT INDOOR BLO...

Страница 13: ...defrost mode The compressor will be cycled off for 30 seconds going in and out of the defrost mode when the compressor delay jumper is installed NOTE The 30 second compressor feature is ignored when j...

Страница 14: ...Air Temperature Ambient Temperature Return Air Temperature System Refrigerant Charge Refer to manufacturer s information on unit or installation instructions for required subcooling and approach temp...

Страница 15: ...he inside air Have your dealer show you the location of the drain line and how to check for obstructions This would also apply to an auxiliary drain if installed Thermostat Operation See the ComfortSe...

Отзывы: