Page 57
3 - W
NON-DIRECT VENT ROOF TERMINATION KIT
(15F75 or 44J41)
UNCONDITIONED
ATTIC SPACE
3” (76mm) OR
2” (51mm) PVC
PROVIDE SUPPORT
FOR EXHAUST LINES
12” (305mm)
ABOVE AVE.
SNOW
ACCUMULATION
FIGURE 43
NOTE - Do
tical discharge through an existing unused chimney or stack is required, insert piping
inside
trated. In any exterior portion of chimney, the exhaust vent must be insulated.
STRAIGHT-CUT OR
ANGLE-CUT IN DIRECTION
OF ROOF SLOPE
SHOULDER OF FITTINGS
PROVIDE SUPPORT
OF PIPE ON TOP PLATE
EXTERIOR
PORTION OF
CHIMNEY
INSULATE
TO FORM
SEAL
SHEET
METAL TOP
PLATE
NON-DIRECT VENT APPLICATION
USING EXISTING CHIMNEY
Minimum 12” (305MM)
above chimney top
plate or average snow
accumulation
FIGURE 44
Condensate Piping
This unit is designed for either right- or left-side exit of
condensate piping. Refer to FIGURE 45 and FIGURE 46
condensate trap locations.
NOTE -
If necessary the condensate trap may be installed
up to 5’ away from the furnace. Use PVC pipe to connect
trap to furnace condensate outlet. Piping from furnace
must slope down a minimum of 1/4” per ft. toward trap.
CONDENSATE TRAP AND PLUG LOCATIONS
Trap
(same
on right
side)
Plug
(same on left side)
1-1/2 in.
FIGURE 45
CONDENSATE TRAP LOCATION
(shown with right side exit of condensation)
5’ max.
to drain
1” min.
2” max.
Trap can be installed a maximum
of 5ft. from furnace (*PVC only)
Field Provided Vent
1” min. 2” max. above
condensate drain.
*Piping from furnace must slope down a
minimum 1/4” per ft. toward trap
FIGURE 46
1 -
Determine which side condensate piping will exit
the unit, location of trap, field-provided fittings and
length of PVC pipe required to reach available drain.
2 -
For furnaces with a 1/2” drain connection use a 3/8
allen wrench and remove plug (FIGURE 45) from
the cold end header box at the appropriate location
on the side of the unit. Install field-provided 1/2 NPT
male fitting into cold end header box. For furnaces
with a 3/4” drain connection use a large flat head
screw driver or a 1/2” drive socket extension and
remove plug. Install provided 3/4 NPT street elbow
fitting into cold end header box. Use Teflon tape or
appropriate pipe dope.