SPECIFICATIONS
Gas
Heating
Performance
Model No.
EL280UH045E36A
EL280UH070E36A
Model No. - Low NOx
- - -
EL280UH070XE36A
1
AFUE
80%
80%
High
Fire
Input - Btuh
44,000
66,000
Output - Btuh
35,000
53,000
Temperature rise range - °F
30 - 60
30 - 60
Gas Manifold Pressure (in. w.g.)
Nat. Gas / LPG/Propane
3.5 / 10.0
3.5 / 10.0
Low
Fire
Input - Btuh
29,000
43,000
Output - Btuh
23,000
35,000
Temperature rise range - °F
20 - 50
20 - 50
Gas Manifold Pressure (in. w.g.)
Nat. Gas / LPG/Propane
1.7 / 4.5
1.7 / 4.5
High static - in. w.g.
Heating
0.5
0.5
Cooling
0.5
0.5
Connections
in.
Flue connection − in. round
4
4
Gas pipe size IPS
1/2
1/2
Indoor
Blower
Wheel nominal diameter x width - in.
10 x 8
10 x 8
Motor output - hp
1/2
1/2
Tons of add-on cooling
1.5 - 3.5
2 - 3.5
Air Volume Range - cfm
250 - 1500
350 - 1375
Electrical Data
Voltage
120 volts - 60 hertz - 1 phase
Blower motor full load amps
6.1
6.1
Maximum overcurrent protection
15
15
Shipping Data
lbs. - 1 package
111
121
NOTE - Filters and provisions for mounting are not furnished and must be field provided.
1
Annual Fuel Utilization Efficiency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized furnaces.
SPECIFICATIONS
Gas
Heating
Performance
Model No.
EL280UH090E36B
EL280UH090E48B
Model No. - Low NOx
- - -
EL280UH090XE48B
1
AFUE
80%
80%
High
Fire
Input - Btuh
88,000
88,000
Output - Btuh
70,000
69,000
Temperature rise range - °F
35 - 65
30 - 60
Gas Manifold Pressure (in. w.g.)
Nat. Gas / LPG/Propane
3.5 / 10.0
3.5 / 10.0
Low
Fire
Input - Btuh
57,000
57,000
Output - Btuh
46,000
46,000
Temperature rise range - °F
25 - 55
20 - 50
Gas Manifold Pressure (in. w.g.)
Nat. Gas / LPG/Propane
1.7 / 4.5
1.7 / 4.5
High static - in. w.g.
Heating
0.5
0.5
Cooling
0.5
0.5
Connections
in.
Flue connection − in. round
4
4
Gas pipe size IPS
1/2
1/2
Indoor
Blower
Wheel nominal diameter x width - in.
10 x 9
10 x 10
Motor output - hp
1/2
3/4
Tons of add-on cooling
2 - 3.5
3 - 4
Air Volume Range - cfm
350 - 1600
765 - 1800
Electrical Data
Voltage
120 volts - 60 hertz - 1 phase
Blower motor full load amps
6.1
8.2
Maximum overcurrent protection
15
15
Shipping Data
lbs. - 1 package
136
140
NOTE - Filters and provisions for mounting are not furnished and must be field provided.
1
Annual Fuel Utilization Efficiency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized furnaces.