background image

Page 22

IMPORTANT

If a high­efficiency filter is being installed as part of
this system to ensure better indoor air quality, the fil­
ter must be properly sized. High­efficiency filters
have a higher static pressure drop than standard­ef­
ficiency glass/foam filters. If the pressure drop is too
great, system capacity and performance may be re­
duced. The pressure drop may also cause the limit to
trip more frequently during the winter and the indoor
coil to freeze in the summer, resulting in an increase
in the number of service calls.

Before using any filter with this system, check the
specifications provided by the filter manufacturer
against the data given in the appropriate Lennox
Product Specifications bulletin. Additional informa­
tion is provided in Service and Application Note
ACC­00­2 (August 2000).

5- Check the condition and cleanliness of burners and

heat exchanger and clean if necessary.

6- Check the cleanliness of blower assembly and clean

the housing, blower wheel and blower motor if neces­
sary

The blower motors are prelubricated for extended

bearing life. No further lubrication is needed.

7- Inspect the combustion air inducer and clean if neces­

sary.

8- Evaluate the heat exchanger integrity by inspecting the

heat exchanger per the AHRI heat exchanger inspec­
tion procedure.  This procedure can be viewed at
www.ahrinet.org

9- Ensure sufficient combustion air is available to the fur­

nace.  Fresh air grilles and louvers (on the unit and in the
room where the furnace is installed) must be properly
sized, open and unobstructed to provide combustion
air

.

10 Inspect the furnace venting system to make sure it is in

place, structurally sound, and without holes, corrosion,
or blockage. Vent system must be free and clear of ob­
structions and must slope upward away from the fur­
nace

.

 Vent system should be installed per the National

Fuel Gas Code

11 Inspect the furnace return air duct connection to ensure

the duct is sealed to the furnace. Check for air leaks on
supply and return ducts and seal where necessary

.

12 Check the condition of the furnace cabinet insulation

and repair if necessary.

13 Perform a complete combustion analysis during the fur­

nace inspection to ensure proper combustion and oper­
ation.  Consult Service Literature for proper combustion
values.

14 Verify operation of CO detectors and replace batteries

as required.

Perform a general system test. Turn on the furnace to
check operating functions such as the start-up and shut-off
operation.
 1 - Check the operation of the ignition system, inspect

and clean flame sensor. Check microamps before and
after. Check controls and safety devices (gas valve,
flame sensor, temperature limits). Consult Service
Manual for proper operating range. Thermal Limits
should be checked by restricting airflow and not dis­
connecting the indoor blower. For additional details,
please see Service and Application Note H­04­9.

 2 - Verify that system total static pressure and airflow set­

tings are within specific operating parameters.

 3 - Clock gas meter to ensure that the unit is operating at

the specified firing rate. Check the supply pressure
and the manifold pressure. On two-stage gas furnaces
check the manifold pressure on high fire and low fire. If
manifold pressure adjustment is necessary, consult
the Service Literature for unit specific information on
adjusting gas pressure. Not all gas valves are ad­
justable

Verify correct temperature rise.

Cleaning the Heat Exchanger and Burners

NOTE - Use papers or protective covering in front of the fur­
nace during cleaning.

1 - Turn off both electrical and gas power supplies to fur­

nace.

2 - Remove flue pipe, top cap, flue chase and internal flue

pipe assembly from the unit.

3 - Label the wires from gas valve, rollout switches, prima­

ry limit switch and make-up box then disconnect them.

4 - Remove the screws that secure the combustion air in­

ducer/pressure switch assembly to the collector box.
Carefully remove the combustion air inducer to avoid
damaging blower gasket. If gasket is damaged, it must
be replaced to prevent leakage.

5 - Remove the collector box located behind the combus­

tion air inducer. Be careful with the collector box gas­
ket. If the gasket is damaged, it must be replaced to
prevent leakage.

6 - Disconnect gas supply piping. Remove the four screws

securing the burner manifold assembly to the vestibule
panel and remove the assembly from the unit.

7 - Remove screws from both sides, top and bottom of

vestibule panel.

8 - Remove heat exchanger. It may be necessary to

spread cabinet side to allow more room. If so, remove
five screws from the left side or right side of cabinet.
See figure 25.

 9- Back wash using steam. Begin from the burner opening

on each clam. Steam must not exceed 275°F.

10- To clean burners, run a vacuum cleaner with a soft brush

attachment over the face of burners. Visually inspect in­
side the burners and crossovers for any blockage
caused by foreign matter. Remove any blockage. Figure
24 shows burner detail.

Содержание EL180DF045E36A

Страница 1: ...ute code WARNING Improper installation adjustment alteration service or maintenance can cause property damage person al injury or loss of life Installation and service must be performed by a licensed professional HVAC in staller or equivalent service agency or the gas sup plier TABLE OF CONTENTS Specifications Page 2 Blower Data Page 3 Parts Identification Page 5 I Unit Components Page 6 II Instal...

Страница 2: ...mounting are not furnished and must be field provided 1 Annual Fuel Utilization Efficiency based on DOE test procedures and according to FTC labeling regulations Isolated combustion system rating for non weatherized furnaces OPTIONAL ACCESSORIES MUST BE ORDERED EXTRA A Width Models B Width Models C Width Models CABINET ACCESSORIES Downflow Combustible Flooring Base 11M59 11M60 11M61 FILTERS 1 Down...

Страница 3: ...5 170 1225 135 1185 125 1110 105 0 10 1430 290 1275 175 1190 145 1155 135 1005 95 0 20 1400 295 1230 190 1125 160 1110 150 900 100 0 30 1360 310 1205 205 1085 160 1055 155 845 115 0 40 1310 325 1155 210 1050 175 1000 165 790 115 0 50 1280 335 1110 220 985 185 950 180 705 130 0 60 1250 350 1060 235 935 195 865 185 645 135 0 70 1220 355 1000 245 865 205 815 195 590 140 0 80 1165 365 935 250 795 210 ...

Страница 4: ... 2095 405 1875 295 1700 225 1635 180 0 10 2385 630 2100 415 1830 310 1610 240 1505 190 0 20 2325 650 2010 440 1760 330 1570 255 1375 195 0 30 2280 675 1940 460 1705 340 1500 260 1320 210 0 40 2235 690 1895 475 1635 365 1440 285 1265 225 0 50 2165 710 1845 490 1595 380 1380 300 1200 235 0 60 2125 735 1800 510 1545 390 1320 310 1170 250 0 70 2090 740 1755 530 1510 405 1285 325 1100 260 0 80 2035 760...

Страница 5: ...ustion air inducer Gas Valve Burner Box includes sensor ignitor and rollout switches Combustion Air Inducer Heat Exchanger Flue Chase Blower Assembly Secondary Limit Access Panel Control Box includes integrated control transformer inter lock switch and circuit breaker ...

Страница 6: ...rface ignition control system consisting of an in tegrated control figure 3 with control terminal designa tions in tables 1 2 and 3 flame sensor and ignitor figure 6 The integrated control and ignitor work in combination to ensure furnace ignition and ignitor durability The inte grated control controls all major furnace operations The integrated control also features a RED LED for trouble shooting...

Страница 7: ...re Switch In 11 Rollout Switch In 12 Gas Valve Out TABLE 3 1 4 QUICK CONNECT TERMINALS 120HUM Humidifier 120VAC LINE 120VAC XFMR Transformer 120VAC CIRC Indoor blower 120VAC EAC Indoor air quality accessory 120VAC NEUTRALS Common 120VAC HUM24 Humidifier 24VAC 3 16 QUICK CONNECT TERMINALS COOL Cooling tap 24VAC HEAT Heating tap 24VAC FAN Continuous blower 24 VAC PARK no power Park terminal for spee...

Страница 8: ... etc To clear error codes depress and hold button longer than 5 seconds TABLE 5 03 Integrated Control RED LED Flash Code2 Diagnostic Codes Status of Furnace Off No power to control or board fault detected Heartbeat1 Normal Operation Idle Continuous Fan Cool Continuous Rapid Flash Call For Heat Burner Operation 1 Reverse Line Voltage Polarity 2 Improper Earth Ground 3 Burner failed to light or lost...

Страница 9: ...ith a fac tory fan off setting of 90 seconds For customized comfort monitor the supply air temperature once the heat demand is satisfied Note the supply air temperature at the instant the blower is de energized Adjust the fan off delay to achieve a supply air temperature between 90 110 at the instant the blower is de ener gized Longer delay times allow for lower air temperature shorter delay times...

Страница 10: ...xchanger the limit will open If the limit is open the integrated control energizes the supply air blower and closes the gas valve The limit auto matically resets when unit temperature returns to normal The switch must reset within three minutes or SureLight control will go into Watchguard for one hour The switch is factory set and cannot be adjusted The switch may have a different setpoint for eac...

Страница 11: ...hermostat contacts to cycle system 7 When main burners are in operation for two minutes take reading TABLE 6 Flame Signal in Microamps Normal Low Drop Out 1 5 0 5 1 4 0 4 FIGURE 7 Measuring Flame Signal upflow furnace shown Flame Sensor Flame Sensor Wire Integrated Control Remove Sensor Wire from Integrated Control and Connect Alligator Clip to Flame Sensor Lead Flame Sensor Terminal Remove Sensor...

Страница 12: ...the only test needed If the reading on the meter is not correct 0 or infinity then a second test is needed Test 2 Check ignitor for correct resistance Seperate the 2 pin jack plug near the manifold and check resistance of ignitor at the plug Reading should be between 39 and 70 ohms If the reading is correct then the problem is with the wiring between the jack plug and the control If reading is not...

Страница 13: ...ressure Switch S18 EL180DFE series units are equipped with a combustion air pressure switch located on the combustion air inducer ori fice bracket The switch is connected to the combustion air inducer housing by means of a flexible silicone hose It mon itors negative air pressure in the combustion air inducer housing The switch is a single pole single throw proving switch elec trically connected t...

Страница 14: ...and motor is not operating properly replace motor The motor is not field re pairable If replacing the indoor blower motor or blower wheel is nec essary placement is critical The blower wheel must be cen tered in the blower housing as shown in figure 10 When re placing the indoor blower motor the set screw must be aligned and tightened with the motor shaft as shown in figure 11 13 Secondary Limit C...

Страница 15: ...us fan 1 2 3 4 or 5 on input plug P49 If 24 volts is not present problem may be up stream of plug P49 Proceed to test 4 Multi Meter set to VAC 12 0 12 0 24 Multi Meter set to VAC Check for 24 volts across terminals 24 COM and FAN ter minals on the integrated control If voltage is present prob lem is with the harness If voltage is not present problem may be may be with the integrated control Check ...

Страница 16: ...l read approxim ately the same resistance within an ohm 3 Check to see if the blower wheel spins freely FIGURE 16 Motor Test TABLE 9 Scale Measurement range in words ohms 2 M two megohm two million ohms 0 2 000 000 200 K two hundred kilo ohm two hundred thousand ohms 0 200 000 20 K twenty kilo ohm twenty thousand ohms 0 20 000 2 K two kilo ohm two thousand ohms 0 2 000 200 two hundred ohms 0 200 M...

Страница 17: ...s to be performed 3 Remove the heating compartment access panel 4 Move gas valve switch to OFF position Do not force See figure 18 5 Replace the heating compartment access panel B Safety or Emergency Shutdown Disconnect main power to unit Close manual and main gas valves C Extended Period Shutdown Turn off thermostat or set to UNOCCUPIED mode Close all gas valves both internal and external to unit...

Страница 18: ...to a test gauge to measure supply pressure 2 Start unit and allow 5 minutes for unit to reach steady state 3 After allowing unit to stabilize for 5 minutes record supply pressure and compare to value given in table 12 Manifold Pressure Measurement 1 Remove the threaded plug from the outlet side of the gas valve and install a field provided barbed fitting Connect to a test gauge to measure manifold...

Страница 19: ... 10 0 11 0 13 0 TABLE 13 Pressure Switch and Gas Conversion Kits at all Altitudes Model Input Size High Altitude Pressure Switch Kit High Altitude Natural Gas Burner Orifice Kit Natural Gas to LP Propane Burner Orifice Kit LP Propane to Natural Gas Burner Orifice Kit 0 4500 ft 4501 7500 ft 7501 10 000 ft 7501 10 000 ft 0 7500 ft 7501 10 000 ft 0 7500 ft 045 No Change No Change 80W51 73W37 11K49 11...

Страница 20: ...nergized 0 75 5 Indoor Blower Energized Less than 2 10 CHECK VOLTAGE BETWEEN LINE NEUTRAL AND LOW VOLTAGE C TERMINAL FIGURE 20 CHECK VOLTAGE BETWEEN LINE HOT AND LINE NEUTRAL FIGURE 21 V TYPICAL OPERATING CHARACTERISTICS A Blower Operation and Adjustment NOTE The following is a generalized procedure and does not apply to all thermostat controls 1 Blower operation is dependent on thermostat control...

Страница 21: ... trol See figure NO TAG The heating tap is connected to the HEAT terminal and the cooling tap is connected to the COOL terminal The continuous blower tap is connected to the FAN terminal Unused taps must be secured on dummy terminals labeled PARK To change out existing speed tap turn off power and switch out speed tap with tap connected to PARK See blower speed tap table on unit diagram for motor ...

Страница 22: ...l system test Turn on the furnace to check operating functions such as the start up and shut off operation 1 Check the operation of the ignition system inspect and clean flame sensor Check microamps before and after Check controls and safety devices gas valve flame sensor temperature limits Consult Service Manual for proper operating range Thermal Limits should be checked by restricting airflow an...

Страница 23: ...er Failure to replace all screws may cause leaks Inspect gaskets for any damage and replace if necessary 14 Reinstall burner box manifold assembly and burner box cover 15 Reconnect all wires 16 Reconnect top cap and vent pipe to combustion air in ducer outlet 17 Reconnect gas supply piping 18 Turn on power and gas supply to unit 19 Set thermostat and check for proper operation 20 Check all piping ...

Страница 24: ...s are found to be closed Call for heat can continue 5 A92 integrated control energizes B6 combustion air inducer S18 combustion air pressure switch closes Once S18 closes a 15 second pre purge follows 6 A92 integrated control energizes R33 ignitor A 20 second warm up period begins 7 GV1 gas valve opens for a 4 second trial for ignition 8 Flame is sensed gas valve remains open for the heat call 9 A...

Страница 25: ...LVE ENERGIZED GAS VALVE OFF COMBUSTION AIR INDUCER ON INDOOR BLOWER ON HEATING SPEED LED FLASHES CODE 11 PRESSURE SWITCH CLOSED GAS VALVE OFF COMBUSTION AIR INDUCER OFF INDOOR BLOWER OFF WITH DELAY Sequence holds until pressure switch opens or thermostat resets control NO NO YES YES IS VOLTAGE ABOVE 70 VOLTS LED FLASHES CODE 13 LOW LINE VOLTAGE CONTROL WILL NOT RESPOND TO A CALL FOR HEATING UNTIL ...

Страница 26: ...TIMES FLAME SIGNAL 1 5 MICROAMPS OR GREATER YES YES YES ROLLOUT SWITCH CLOSED LED FLASHES CODE 8 ROLLOT SWITCH OPEN GAS VALVE POWER OFF COMBUSTION AIR INDUCER POWER ON INDOOR BLOWER ON SEQUENCE HOLDS UNTIL ROLLOUT SWITCH IS RESET AND MAIN POWER IS INTERRUPTED OR THERMOSTAT IS CYCLED OFF ON FOR 1 SEC MINIMUM YES THERMOSTAT DEMAND SATISFIED LED SLOW FLASH COMB AIR INDUCER CONTINUES 5 SECOND POST PUR...

Страница 27: ...LOSED LED SLOW FLASH RATE REMAINS UNCHANGED THROUGHOUT COOLING CYCLE THERMOSTAT CALLS FOR COOLING COMPRESSOR CONTACTOR AND SYSTEM FAN ENERGIZED WITH 2 SECOND DELAY COOLING SPEED EAC TERM ENERGIZED COMPRESSOR OFF THERMOSTAT OPENS SYSTEM FAN AND EAC TERM OFF WITH 45 SECOND DELAY NO NO LED FLASHES CODE 8 ROLLOUT SWITCH OPEN GAS VALVE OFF COMBUSTION AIR INDUCER ON INDOOR BLOWER ON SEQUENCE HOLDS UNTIL...

Страница 28: ...M FAN SWITCHED TO COOL SPEED EAC TERM REMAINS ON THERMOSTAT OPENS MANUAL FAN SELECTION MADE AT THERMOSTAT CONTROL G ENERGIZES SYSTEM FAN AT FAN SPEED EAC TERM ENERGIZED NO YES YES NO SYSTEM FAN SWITCHES TO HEAT SPEAD AFTER 30 SECOND DELAY EAC AND HUM TERMINAL REMAIN ON SYSTEM FAN CONTINUES FAN SPEED WITHOUT INTERRUPTION EAC TERMINAL REMAIN ON HUM TERMINAL IS ENERGIZED WITH COMBUSTION AIR BLOWER HU...

Отзывы: