Requirements

IMPORTANT

Read all of the information in this manual before using
this thermostat.

All wiring must conform to local and national building
and electrical codes and ordinances.

This is a 24VAC Class II voltage thermostat. Do not
install on voltages higher than 30VAC.

Be sure that power routed to the thermostat has been pow­
ered off before beginning installation.

This thermostat should be used only as described in this
manual.

Do not install the thermostat on outside walls (where there is
unconditioned space on opposite side of wall) or in locations
where direct sunlight may be present.

Install thermostat about 5 feet up from the floor.

CAUTION

Do not short (jumper) across terminals on the gas
valve or at the system control to test installation.
This will damage the thermostat and void the war­
ranty.

Installation

NOTE - If this thermostat is replacing an existing thermo­
stat, carefully label the existing thermostat wires so that
they can be identified later.

1. If a previously‐installed thermostat exists, remove it;

if none exists, identify the location for installation (lo­
cate, or install wiring as necessary). To facilitate instal­
lation, enlarge the hole  where the thermostat wires
protrude through the wall to about 1-1/2” wide by 3/4”
high.

2. Pull about 3 inches of the thermostat wiring through

the wall opening. Strip 1/4” of the insulation from the
ends of the thermostat wires to be used.

3. Use a screwdriver to remove the thermostat subbase

from the body. Carefully pry the subbase away from
the body along the bottom edge of the base near the
two mounting snaps; then lift the subbase upward.

4. Use the subbase as a template to mark the desired

mounting hole locations on the wall.

5. Drill two 3/16” holes at the marked locations on the

wall. Insert the provided plastic wall anchors provided
into the holes. Press the anchors into the holes until
anchors are flush with the wall.

6. Align the subbase over the plastic anchors and secure

it to the wall using the provided screws.

7. Use a small slotted screwdriver to secure all wires to

the subbase terminal block. Make thermostat connec­
tions as follows:

D

L3011C - See table 1 and figure 1.

D

L3021H - See table 2 and figure 2.

8.

Thermostat L3021H Only

D

For most applications, E will be jumpered to W1. If
separate wires are not provided for both E and
W1, jumper the E terminal to the W1 terminal on
the thermostat subbase.

D

For dual-fuel applications (heat pump with gas fur­
nace), OR for auxiliary heat lockout applications,
the optional outdoor sensor (part number X2658)
MUST be installed.

D

Connect the outdoor temperature sensor wires to
the T terminals on the subbase terminal strip. (The
sensor connections are not polarity-sensitive.)

9. After wiring is complete, thoroughly seal the hole in the

wall with a suitable material to prevent unconditioned
air in the wall space from entering the thermostat.

10. Set the thermostat DIP switches as required for the

application. See table 3 for DIP switch settings.

11. Carefully attach the thermostat to the subbase by first

engaging the hinges at the top of the unit, then pivoting
the thermostat downward until the thermostat snaps
into place.
The thermostat is now ready for operation. Turn on
power to the thermostat and refer to the appropriate
thermostat operation manual: 504,865M for L3011C
or 504,931M for L3021H.

12. Remove the clear protective film from the face of the

thermostat display.

Note: After this film is removed, some dark streaks or
lines may temporarily appear on the display. These
are normal and should disappear within a few minutes.

Removing Thermostat

The thermostat hinges on tabs on the top of the subbase.
After installation is complete, no tool is needed to remove
the thermostat from the subbase. Pivot the bottom of the­
thermostat outward (releasing the snaps), then lift up to re­
move.

Table 1. L3011C Terminal Designations

Terminal

Description

R

24VAC

G

Fan control

Y1

First stage cooling

W1

First stage heating

L

Service Indicator

C

24VAC common

Содержание ComfortSense L3021H

Страница 1: ...use have a large easy to read display and provide excellent temperature control Both thermo stat models also includes a programmable filter change re minder and a system check indicator which will notify the user of the need for equipment service Thermostat model L3011C is suitable for non heat pump single stage heat single stage cool applications that are matched with a gas or electric furnace Th...

Страница 2: ...re flush with the wall 6 Align the subbase over the plastic anchors and secure it to the wall using the provided screws 7 Use a small slotted screwdriver to secure all wires to the subbase terminal block Make thermostat connec tions as follows D L3011C See table 1 and figure 1 D L3021H See table 2 and figure 2 8 Thermostat L3021H Only D For most applications E will be jumpered to W1 If separate wi...

Страница 3: ...as been stored or is being used at ambient temperatures that are above 93 F The heating function will be enabled after the thermostat is exposed to ambient temperatures below 93 F for about 30 minutes DIP Switch Settings DIP Switch Settings L3011C and L3021H thermostats include five DIP switches located on the back side of the thermostat body These switches may be used to re calibrate the thermost...

Страница 4: ...G fan operation during the heating mode will be controlled by the furnace rather than by the thermostat The thermostat fan icon is not displayed during heating mode op eration even though the fan may be energized This setting is used in applications which include a gas furnace If the fan operation DIP switch is set on E the thermostat controls fan operation during the heating mode This setting is ...

Страница 5: ... diagrams for the thermostats are shown in figure 3 for the L3011C and figure 4 Page 6 for the L3021H COIL BLOWER WITH V DRIVE COIL BLOWER FURNACE WITH V DRIVE FURNACE L3011C L3011C L3011C L3011C Figure 3 Typical Wiring Diagrams for Condenser and L3011C Thermostat ...

Страница 6: ...6080 02 5 2017 HEAT PUMP DUAL FUEL FURNACE WITH V DRIVE COIL BLOWER COIL BLOWER WITH V DRIVE FURNACE L3021H L3021H L3021H L3021H Figure 4 Typical Wiring Diagrams for Heat Pump or Dual Fuel with L3021H Thermostat ...

Отзывы: