Page 5
5/2 DAY PROGRAMMABLE THERMOSTAT
OC R
Y1 W1 Y2 W2
G
L C
T
T
Figure 1. Terminal Strip (11Y05)
DIP Switch Settings
DIP Switch Settings
This thermostat includes six DIP switches which are located
on the back side of the thermostat body. These switches
may be used to re-calibrate the thermostat (Cal 1, Cal 2 and
Cal±) and to select the internal or remote indoor
temperature sensor.
Thermostat includes a DIP switch used to indicate whether
electric or gas heat will be used. Also, SSR (Smooth
Setback Recovery) can be enabled or disabled. When
enabled, this feature provides additional comfort when
changing from one program period to the next. If SSR is
disabled, the HVAC equipment will respond to a program
change at the time the change is set to occur.
However, if SSR is enabled, the HVAC equipment will
respond to a program change before the change is set to
occur. Refer to table 3 for DIP switch function descriptions.
Thermostat Calibration
Cal 1, Cal 2, Cal±
DIP switches
may be used to offset or
recalibrate the room temperature display. Table 2 provides
DIP switch settings and corresponding temperature offset
values.
Table 2. DIP Switch Temperature Offset
Cal 1
Cal 2
Cal +/- Temperature Offset
Off
Off
Off
+0°F (no offset)
On
Off
Off
+1°F
Off
On
Off
+2°F
On
On
Off
+3°F
Off
Off
On
-0°F (no offset)
On
Off
On
-1°F
Off
On
On
-2°F
On
On
On
-3°F