Page 15

Figure 17

Condensate Disposal – Upflow

TH

R

U

.

59.69/56.64

1/2” NPT PLUG

(SUPPLIED)

1/2” NPT x 3/4” PVC ADAPTER

(SUPPLIED)

3/4” PVC

TEE MUST REMAIN

OPEN

Condensate Disposal Installation

The condensate drain should be routed directly to a locally
acceptable disposal area. The condensate drain line
should not be run directly to the outdoors especially in
colder climates where temperatures may cause the
condensate to freeze in the drain line.

In horizontal installations where clearance beneath the
unit is limited, an alternate method for condensate dis-
posal trap installation may be used (see 

Horizontal

Installation – Tight Clearance Below Unit 

on page 17).

Upflow Installation

Install the condensate drain line to the unit as follows. The
condensate can be drained from either the right or left
side of the furnace. Install the 1/2" NPT x 3/4" PVC
adapter (supplied) in the drain on the side that the draining
will occur. Install the plastic pipe plug opposite of the
drain. Using 3/4" PVC pipe, make a connection from the
adapter just installed to extend just outside the unit. Install
a 3/4" PVC tee as shown in Figure 17. From the tee,
install the drain to the disposal area. The top of the tee
must be left open for proper condensate drainage.

Horizontal Installation – Right to Left Airflow

Furnace must be mounted such that the side through
which the condensate will drain is elevated a minimum of
9" above a surface such as a floor.

Install unit at a slight pitch forward (see Figure 18).

1. Relocate the 1/2" NPT plug installed on the flue pan to

one side of the internal trap assembly (as shown in
Figure 19).

2. Connect the 1/2" NPT plug (supplied) to the opposite

side of the internal trap assembly from the plug
installed in Step 1.

3. Insert trap assembly (supplied) into flue pan (see

Figure 20).

Figure 18

Tilt Unit Forward

Figure 20

Install Trap Assembly

1/2 NPT x 1/2 PVC

Adapter and Trap Assembly

(supplied)

"

"

Flue Pan

Figure 19

Insert Plugs

1/2 NPT Plug
(supplied in kit)

"

1/2 NPT Plug
(supplied on unit)

"

1/4" Max

Содержание CG90TB

Страница 1: ... or requirements take precedence over the general instructions in this manual IMPORTANT Do not store combustible materials including gasoline and other flammable vapors and liquids near the furnace vent pipe or warm air ducts The homeowner should be cau tioned that the furnace area must not be used as a broom closet or for any other storage purposes Such uses may result in actions that could cause...

Страница 2: ... Supply and Piping beginning on page 18 of these instructions 7 Always install furnace to operate within the furnace s intended temperature rise range with a duct system which has an external static pressure within the allow able range as specified in Temperature Rise on page 24 of these instructions See furnace rating plate 8 When a furnace is installed so that the supply ducts carry air circulat...

Страница 3: ...ormance care must be taken in choosing the location for this furnace The atmosphere in which the furnace operates must be free of contaminants such as chlorides and sulfates The furnace must be installed so that electrical compo nents are protected from water Unit must be level for proper condensate drainage Horizontal Installations Figure 1 All models are suitable for closet or utility room insta...

Страница 4: ...he horizontal position are approved for attic installations If the furnace is to be installed in an attic or other insulated space it must be kept free and clear of insulating materials To avoid property damage caused by condensate drain blockage install a field fabricated auxiliary drain pan with a separate drain line to the outside under the entire furnace and drain system Install according to l...

Страница 5: ...sed there must be no exposure to the substances listed in Item 5 3 All provisions for indoor combustion air must meet the requirements for combustion air indicated in the National Fuel Gas Code ANSI Z223 1 NFPA 54 latest edition and or any applicable local codes In Canada see CSA B149 1 Natural Gas and Propane Installation Codes latest edition 4 The following types of installation may require outd...

Страница 6: ...n through an unconditioned space 1 2 Armaflex or equivalent must be used over the pipe In extreme cold climates 3 4 Armaflex is recommended Materials All pipe fittings primer and solvent cement must conform with American National Standard Institute and theAmerican Society for Testing and Materials ANSI ASTM standards The solvent shall be free flowing and contain no lumps undissolved particles or a...

Страница 7: ...r hazard or cause property damage or where condensate vapor could cause damage or could be detrimental to the operation of regulators relief valves or other equipment See Figures 5 and 6 on pages 8 and 9 for additional information on where the horizontal vent terminal can and cannot terminate For horizontal venting in situations where clearance to floor joists is limited see Horizontal Venting Low...

Страница 8: ... r a e l C D e h t e v o b a d e t a c o l t i f f o s d e t a l i t n e v o t e c n a r a e l c l a c i t r e V e h t m o r f m c 1 6 t e e f 2 f o e c n a t s i d l a t n o z i r o h a n i h t i w l a n i m r e t l a n i m r e t e h t f o e n i l r e t n e c E t i f f o s d e t a l i t n e v n u o t e c n a r a e l C F r e n r o c e d i s t u o o t e c n a r a e l C G r e n r o c e d i s n i o t...

Страница 9: ...l C D e h t e v o b a d e t a c o l t i f f o s d e t a l i t n e v o t e c n a r a e l c l a c i t r e V e h t m o r f m c 1 6 t e e f 2 f o e c n a t s i d l a t n o z i r o h a n i h t i w l a n i m r e t l a n i m r e t e h t f o e n i l r e t n e c E t i f f o s d e t a l i t n e v n u o t e c n a r a e l C F r e n r o c e d i s t u o o t e c n a r a e l C G r e n r o c e d i s n i o t e c n ...

Страница 10: ...te as shown in Figure 7 The vent pipe on horizontal runs must slope upward away from the furnace at a minimum pitch of 1 4 per foot of run to prevent accumulation of condensate Do not cement air intake into the connector on burner box Use high temperature RTV silicone sealant so intake pipe can be removed if service is required In horizontal venting applications the vent and air intake pipe must b...

Страница 11: ...astic bag containing these Installation Instructions and the User s Information Manual This restrictor plate is to be used only in non direct vent applications Place the restrictor plate into the inlet collar insert 3 section of PVC pipe field supplied then attach a 90 elbow field sup plied to the PVC pipe in all non direct vent installations see Figures 9 and 10 Two inlet air restrictor plates ar...

Страница 12: ...h temperature RTV silicone sealant so intake pipe can be removed if service is required In horizontal venting applications the vent and air intake pipe must be installed on the same side of the house within the parameters shown in Figure 11 Horizontal Direct Vent Horizontal Venting Figure 11 3 Long Piece of 2 Diameter Pipe supplied 18 6 Drain Tee supplied Height to provide 12 clearance to average ...

Страница 13: ...ination of the flue pipe and is designed to keep objects out of the flue pipe For horizontal venting refer to Figure 13 For vertical venting refer to Figure 14 The vent pipe on horizontal runs must slope upward away from the furnace at a minimum pitch of 1 4 per foot of run to prevent accumulation of condensate Prime the trap system by slowly pouring 1 cup of water down the vent pipe On initial st...

Страница 14: ... 1 Seal any unused openings in the common venting system 2 Visually inspect the venting system for proper size and horizontal pitch as required in the National Fuel Gas Code ANSI Z223 1 NFPA 54 latest edition or the CSA B149 1 Natural Gas and Propane Installation Codes and these instructions Determine that there is no blockage or restriction leakage corrosion or other deficiencies which could caus...

Страница 15: ...t the draining will occur Install the plastic pipe plug opposite of the drain Using 3 4 PVC pipe make a connection from the adapter just installed to extend just outside the unit Install a 3 4 PVC tee as shown in Figure 17 From the tee install the drain to the disposal area The top of the tee must be left open for proper condensate drainage Horizontal Installation Right to Left Airflow Furnace mus...

Страница 16: ...PT plug installed on flue pan to one side of the internal trap assembly as shown in Figure 23 2 Connect the 1 2 NPT plug supplied to the opposite side of the internal trap assembly from the plug installed in Step 1 3 Insert trap assembly supplied into flue pan see Figure 24 4 Connect a length of 3 4 PVC pipe 3 minimum to the trap assembly see Figure 25 4 Connect a length of 3 4 PVC pipe 3 minimum ...

Страница 17: ...ting condensate drain installation Pressure Switch Connection Upflow Installation The unit is shipped from the manufacturer with a black hose connected to the pressure switch The other end of Figure 25 Completing Condensate Drain Installation 3 4 Tee 3 8 Vinyl Hose supplied Be sure to avoid double trapping the vinyl hose Hose must be installed as shown the hose must be connected to the flue pan se...

Страница 18: ... return air excessive condensation will occur within the furnace CAUTION Horizontal Installation The unit is shipped from the manufacturer with a black hose connected to the pressure switch The other end of the hose must be connected to the external drain trap Route hose through gas line access hole in cabinet Then connect to 1 4 barbed fitting on drain trap assembly For right to left airflow inst...

Страница 19: ...ter leak detection has been completed Failure to follow the safety warnings exactly could result in serious injury death or prop erty damage Never test for gas leaks with an open flame Use a commercially available soap solution made specifically for the detection of leaks to check all connections A fire or explosion may result causing property damage personal injury or loss of life WARNING FIRE OR...

Страница 20: ...s wired for a higher speed the increased amp draw could cause the board control to fail and void the warranty Humidifier Terminals are provided on the blower control board for connection to a 120 volt humidifier The HUM terminal is energized whenever the thermostat calls for heat Refer to furnace wiring diagram for specific connection information Electronic Air Cleaner Terminals are provided on th...

Страница 21: ...vice which automatically lights the burners Do not try to light the burners by hand Before operating smell all around the appliance area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor What to do if you smell gas Do not try to light any appliances Extinguish any open flame Do not touch any electric switch do not use any phone in your bui...

Страница 22: ...lectable heat blower off delay expires The control return to standby mode once the heat blower off delay expires Fan On During a fan on call the thermostat energizes the R G circuit of the control board immediately causing the fan to energize the COOL speed The fan remains energized as long as the thermostat calls for fan on operation If a call for cooling is energized during a fan on call the fan...

Страница 23: ...the blower control board 4 The remaining speed taps must be connected to dummy terminals marked PARK on the blower control board Checking and Adjusting Gas Input The minimum permissible gas supply pressure for the purpose of input adjustment is 5 W C for natural gas and 11 W C for propane gas This furnace requires conversion for use with propane see Accessories section on page 26 for correct kit T...

Страница 24: ...y proper operation after servicing WARNING ELECTRICAL SHOCK FIRE OR EXPLOSION HAZARD and Table 4 Typical manifold set point for installations at altitudes from 0 to 4500 feet above sea level is 10 0 W C Temperature Rise Check the temperature rise and if necessary adjust blower speed to maintain temperature rise within the range shown on the unit rating plate High Altitude In both the United States...

Страница 25: ... control continuously monitors its own operation and the operation of the system If a failure occurs the LED will indicate the failure code The flash codes are presented in Table 5 Fault Code History Button The control stores the last five fault codes in memory A pushbutton switch is located on the control see Figure 35 on page 27 When the pushbutton switch is pressed and released the control flas...

Страница 26: ...mbly Blower wheel Blower motor Blower motor mount Blower motor capacitor Burner Group Gas manifold Main burner orifices Main burners Accessories ALPKT572 Natural Gas to Propane Conversion Kit G1D91BT and CG90TB ALPKT574 Natural Gas to Propane Conversion Kit G1D93BT AFILTHA7 Single Side Filter Frame Kit AFILT524 Side Return Filter Kit AFILT529 Bottom Return Filter Kit ANGKT557 Propane to Natural Ga...

Страница 27: ... 47860A005 Page 27 Figure 35 Connection Diagram P N 45198 006 ...

Страница 28: ... 47860A005 Page 28 Figure 36 Schematic Diagram P N 45198 006 ...

Отзывы: