Page 16
CBX40UHV
IMPORTANT
Before changing any clippable links or jumper settings,
make sure the motor has completely stopped. Any
changes will not take place while the motor is running.
Table 3. Air Handler Control Connections —
Communicating (CBX40UHV-XXX-230-6-ALL)
Label
Label
Function
Thermostat
R
24VAC
i+
RSbus data high connection
i-
RSbus data low connection
C
24VAC command (ground)
Outdoor Unit
R
24VAC
i+
RSbus data high connection
i-
RSbus data low connection
C
24VAC command (ground)
Link
i+
Not used.
i-
Thermostat Wire Length
Table 4. Run Length — Communicating
(CBX40UHV-XXX-230-6-02)
Wire Run Length
AWG #
Insulation/Core Types
Maximum length of wiring
for all connections on the
RSBus is limited to 1500
feet (457 meters).
18
Color-coded, temperature
rating 95
º
F (35
º
C) minimum,
solid core. (Class II Rated
Wiring)
Table 5. Run Length — Non-Communicating
(CBX40UHV-XXX-230-6-01 and -02)
Wire Run Length
AWG #
Insulation/Core Types
Less than 100' (30m)
18
Color-coded, temperature
rating 95
º
F (35
º
C) minimum,
solid core. (Class II Rated
Wiring)
More than 100' (30m)
16
Air Handler Control 9-Pin Connector
1.
Air Handler ONLY - 2-wire harness (Wired to points 7
and 8) from the factory provides 230 volt power to Air
Handler Control.
2.
Air Handler with ECB40 Electric Heat - 8-wire harness
(Wired as noted in table 6)
Table 6. Stages
Position &
Wire Color
Function / Description
1 red
Heat stage 1 relay coil
2 orange
Heat stage 2 relay coil
3 yellow
Relay coil return
4 black
Heat stage 3 relay coil
5 brown
Heat stage 4 relay coil
6 blue
Heat stage 5 relay coil
7 black
L1 230VAC supply from heater kit
8 red
L2 230 VAC supply from heater kit
9
Not Used