Page 3

MERIT

®

 CBX25UHV SERIES

Requirements

WARNING

Excessive Weight Hazard - Use two or more people
when moving and installing the unit. Failure to do so can
result in back or other type of injury.

IMPORTANT

Merit

®

 CBX25UHV units include a factory-installed

check/expansion valve which provides optimal refriger­
ant control and system performance with outdoor units
of varying capacities. These units must be installed as
part of a matched system as outlined in the CBX25UHV
Product Specification bulletin.

CAUTION

As with any mechanical equipment, contact with sharp
sheet metal edges can result in personal injury. Take
care while handling this equipment and wear gloves and
protective clothing

.

These instructions are intended as a general guide and do
not supersede local or national codes in any way. Consult
authorities having jurisdiction before installation.

Compliance with all local, state, or national codes
pertaining to this type of equipment should be determined
prior to installation. Read this instruction manual, as well
as the instructions supplied in separate equipment, before
starting the installation.

In addition to conforming to manufacturer's installation
instructions and local municipal building codes, installation
of Lennox air handler units (with or without optional electric
heat), MUST conform with National Fire Protection
Association (NFPA) standards: “Standard for Installation
of Air Conditioning and Ventilation Systems” (NFPA No.
90A) and “Standard for Installation of Residence Type
Warm Air Heating and Air Conditioning Systems” (NFPA
No. 90B).

All models are designed for indoor installation only. The
installation of the air handler, field wiring, duct system, etc.
must conform to the requirements of the National Electrical
Code, ANSI/NFPA No. 70 (latest edition) in the United
States, and any state laws, and local ordinances (including
plumbing or wastewater codes). Local authorities having
jurisdiction should be consulted before installation is
made. Such applicable regulations or requirements take
precedence over the general instructions in this manual.

Install the conditioned air plenum, ducts and air filters
(provided) in accordance with NFPA 90B Standard for the
Installation of Warm Air Heating and Air-Conditioning
Systems (latest edition).

The air handler is shipped from the factory completely
assembled. This unit is provided with flanges for
connecting the supply plenum.

Do not remove the cabinet knockouts until it has been
determined which knockouts will need to be removed for
the installation.
Select the air discharge position which best suits the site
conditions. Consider required clearances, space, routing
requirements for refrigerant line, condensate disposal,
filters, duct system, wiring, and accessibility for service.
Refer to the rating plate on the air handler for specific
information.

WARNING

Danger of explosion. Keep flammable ma­
terials and vapors, such as gasoline, away
from air handler. Place air handler so that
heating elements are at least 18 inches (46
cm) above the floor for a garage installa­
tion. Failure to follow these instructions
can result in death, explosion, or fire.

IMPORTANT

Excessive condensation may occur if the unit is installed
in a warm, humid place. When the unit is installed in an
unconditioned space, apply sealant around electrical
wires, refrigerant piping and condensate lines at the
point where they enter the cabinet.
Apply sealant on the inside of the cabinet at the point
where the electrical wires exit through the conduit open­
ing. Sealing the cabinet in this way prevents warm,
moist, unconditioned air from entering the cabinet.
Warm, moist air in the cabinet forms condensate on the
cooler control box and electrical controls.

IMPORTANT

This unit is approved for installation clearance to com­
bustible material as stated on the unit rating plate. Ac­
cessibility and service clearances must take precedence
over combustible material clearances.
The air handler must be installed so that free access is
allowed to the coil/filter compartment and blower/control
compartment.

Installation Clearances

NON-DUCTED RETURN CLOSET INSTALLATION

The air handler can be installed in a closet with a false
bottom to form a return air plenum. It may also be installed
with a return air plenum under the air handler.
Louvers or return air grilles are field‐supplied. Local codes
may limit application of systems without a ducted return to
single-story buildings.
When a Merit

®

 CBX25UHV unit is installed in a closet with

a louvered return opening, the minimum open area for the
louvers will be:

320 square inches for -018 and -024 models;

360 square inches for -030 and -036 models;

450 square inches for -042 thru -060 models.

Содержание CBX25UHV-018

Страница 1: ...507616 02 7 2018 Shipping and Packing List Package 1 of 1 contains the following 1 Assembled air handler unit factory equipped for up flow or horizontal air discharge application includes up flow and horizontal drain pans and pre installed air filter Check equipment for shipping damage If found immediately report damage to the last carrier Check the unit rating plate to confirm that delivered unit...

Страница 2: ...s Up flow inches mm NOTE Unit is shipped configured for horizontal left hand air discharge Unit may be converted to horizontal right hand air discharge by repositioning horizontal drain pan Dimensions remain the same in all configurations ...

Страница 3: ...ning Systems latest edition The air handler is shipped from the factory completely assembled This unit is provided with flanges for connecting the supply plenum Do not remove the cabinet knockouts until it has been determined which knockouts will need to be removed for the installation Select the air discharge position which best suits the site conditions Consider required clearances space routing...

Страница 4: ... in the desired location and properly slope the unit see page 8 Connect the return and supply air plenums as required using sheet metal screws 4 In applications that do not include a return air plenum install units on a stand that is raised at least 14 above the floor This ensures proper air return HORIZONTAL DRAIN PAN IMPORTANT REMOVE PAN FOR BEST EFFICIENCY AND AIR FLOW UP FLOW DRAIN PAN UP FLOW...

Страница 5: ...ge the following field modifications are required 1 Remove and set aside blower and coil access panels 2 Remove brackets securing pans to unit See figure 4 Figure 4 Remove Main Drain Pan Mounting Brackets 3 Remove coil assembly bottom drain pan and horizontal drain pan as one unit from the air handler Figure 5 Remove Coil Assembly Bottom Drain Pan and Horizontal Drain Pan As A Unit 4 Remove the bl...

Страница 6: ...that Hold the Coil and Horizontal Drain Pan in Place Repositioning Black Box on Motor Module 018 024 and 030 Units When the horizontal drain pan is moved to the right side of the air handler the black box on the back of the supply fan motor will prevent the insertion of the blower assembly back into the cabinet The black box must be repositioned to overcome this issue Tools and Material Required 1...

Страница 7: ...r than the original position Figure 12 Black Box Repositioned on Motor Module 11 Slide the blower assembly into the cabinet to confirm clearance between the horizontal drain pan and the black box Remove the blower assembly and relocate the black box if necessary to achieve clearance Make note of the new position Apply two new strips of double sided tape to the black box and affix it to the module ...

Страница 8: ...ater standing in the pan THIS CORNER SHOULD BE 5 8 1 8 HIGHER THAN DRAIN CORNER DRAIN CORNER THIS CORNER SHOULD BE 5 8 1 8 HIGHER THAN DRAIN CORNER Figure 14 Sloping the Unit for Proper Drainage INSTALL CONDENSATE DRAIN The air handler is equipped with NPT condensate drain connections IMPORTANT On some pans the primary and secondary drain holes have knockouts Confirm primary and secondary drains a...

Страница 9: ...PE IN HALF AND USE IT TO ROUTE THE MAIN DRAIN Figure 16 Typical Main and Overflow Drain 2 Install properly sized field provided connection fittings and connect primary drain line to the main drain pan connection NOTE When installing drain line connection fittings to the drain pan hand tighten the fitting and use a thread sealant Over tightening the fittings can split connections on the drain pan 3...

Страница 10: ...rs have a higher static pressure drop than standard efficiency glass foam filters If the pressure drop is too great system capacity and performance may be reduced The pressure drop may also cause the limit to trip more frequently during the winter and the indoor coil to freeze in the summer result ing in an increase in the number of service calls Before using any filter with this system check the ...

Страница 11: ...ntroduction of moisture into a system NOTE When installing refrigerant lines longer than 50 feet see the Lennox Refrigerant Piping Design and Fabrication Guidelines CORP 9351 L9 or contact Lennox Technical Support Product Applications for assistance To obtain the correct information from Lennox be sure to communicate the following information Model and capacity 1 Route the suction and liquid lines...

Страница 12: ...TO ALLOW FILTER ACCESSIBILITY NOTE CBX25UHV SERIES UNITS USE NITROGEN OR DRY AIR AS A HOLDING CHARGE IF THERE IS NO PRESSURE WHEN THE RUBBER PLUGS ARE REMOVED CHECK THE COIL FOR LEAKS BEFORE INSTALLING REFER TO INSTRUCTIONS PROVIDED WITH OUTDOOR UNIT FOR LEAK TESTING EVACUATING AND CHARGING PROCEDURES FLOW REGULATED NITROGEN AT 1 TO 2 PSIG THROUGH THE REFRIGERATION GAUGE SET INTO THE VALVE STEM PO...

Страница 13: ... through specified low voltage opening Run line voltage wiring only through specified high voltage opening Do not combine voltage in one opening WARNING Electric Shock Hazard Can cause injury or death Foil faced insulation has conductive characteristics sim ilar to metal Be sure there are no electrical connections within a of the insulation If the foil faced insulation comes in contact with electr...

Страница 14: ...ical unit wiring as well as wiring of optional field installed electric heat is given in figure 21 Refer to the instructions provided with the electric heat section for proper installation See figure 22 for typical low voltage field wiring connections WARNING USE COPPER CONDUCTORS ONLY 1 Disconnect all power supplies 2 Remove the air handler access panel 3 Route the field supply wires to the air h...

Страница 15: ...O 104796 01 12 BLK 12 BLK 1 2 3 4 5 1 2 3 4 5 6 8 9 10 11 12 13 14 15 7 1 2 3 4 5 6 8 9 10 11 12 13 14 15 7 16 Y2 DS O W1 W2 Y1 G 14 RED L2 18 BLUE L2 18 WHITE L2 18 BLACK L2 R CIRCUIT BOARD MOTOR TR BR GRD 18 YEL 18 ORG 18 PRPLE 18 BLUE WHITE 18 GRN 18 RED 18 WHITE 18 BLK 18 RED 18 YEL 18 BLUE 18 RED 18 RED 18 YEL 14 YEL 14 YEL 14 BLK 18 WHITE 18 WHITE 18 WHITE 18 WHITE 18 WHITE 18 WHITE 18 WHITE...

Страница 16: ...Page 16 WARNING USE COPPER CONDUCTORS ONLY Figure 22 Low Voltage Connections Variable Speed Motor ...

Страница 17: ...er speed needed to meet application CFM requirements JUMPER SETTINGS IMPORTANT Before changing jumper setting make sure the motor has completely stopped Any jumper setting change will not take place while the motor is running Table 2 lists the recommended factory blower speed tap selections for Merit CBX25UHV series units These settings are for nominal tonnage match ups with the Merit CBX25UHV Whe...

Страница 18: ...ormance tables With the thermostat set for Continuous Fan and without a call for heating or cooling the Merit CBX25UHV provides 50 of the COOL CFM selected NOTE For two stage heat pumps air handler will operate at 70 of the COOL selection until supplemental electric heat is demanded At that time the air handler will operate at the selected HEAT speed This arrangement provides warmer supply air dur...

Страница 19: ... cfm 880 1115 1345 1435 615 770 930 1090 880 1110 1340 1435 NORM 800 1010 1215 1425 555 695 845 990 795 1005 1215 1420 715 905 1095 1275 505 625 755 885 715 905 1090 1280 NOTES The effect of static pressure filter and electric heater resistance is included in the air volumes listed First stage cooling air volume is 70 of COOL second stage speed setting Continuous blower speed is approximately 50 o...

Страница 20: ...COOL second stage speed setting Continuous blower speed is approximately 50 of COOL speed setting Lennox Harmony III Zoning System applications minimum blower speed is 450 cfm Table 10 Merit CBX25UHV Thermostat and Single Stage Outdoor Unit Operating Sequence Operating Sequence System Demand System Response System Condition Step Thermostat Demand Relative Humidity Com pressor Air Handler CFM COOL ...

Страница 21: ...ndent of a Y1 thermostat demand Normal Operation 1 On On On On Acceptable 24 VAC High 100 Dehumidification mode begins when hu midity is greater than set point Dehumidification Call 2 On On On On Demand 0 VAC High 60 65 70 Dehumidification Call ONLY 1 On On On On Demand 0 VAC High 60 65 70 Thermostat will try to maintain room hu midity setpoint by allowing the room space to maintain a cooler room ...

Страница 22: ... indoor units should come on immediately Check the airflow from a register to confirm that the system is moving cooled air Set the thermostat 5ºF higher than the indoor temperature The indoor blower and outdoor unit should cycle off Air handler should cycle off 45 seconds after the outdoor unit shuts off CHECK ELECTRIC HEATER IF USED Set thermostat to call for auxiliary heat approximately 5 F abov...

Страница 23: ...must be taped with a similar foil faced tape 1 CUT INSULATION IN X PATTERN 2 APPLY GLUE 3 PRESS GLUED TABS AGAINST CABINET GLUE Make sure there is full coverage of glue on the metal or insulation so there are no areas where air pockets may form which can lead to sweating Figure 24 Repairing Insulation Use of Air Handler During Construction Lennox does not recommend the use of its air handler unit ...

Страница 24: ...n Duct Temperature ___________ THERMOSTAT Adjusted and Programmed Return External Static ______ ______ Total External Static ______ ______ 6 Supply Duct Temperature ___________ Temperature Drop ___________ TEMPERATURE RISE Heating Mode Return Duct Temperature __________ Supply Duct Temperature __________ Temperature Rise __________ Operation Explained to Owner 9 Explained Operation of System to Ho...

Страница 25: ...___ Total External Static ______ ______ 6 6 Supply Duct Temperature ___________ Temperature Drop ___________ TEMPERATURE RISE Heating Mode Return Duct Temperature __________ Supply Duct Temperature __________ Temperature Rise __________ Operation Explained to Owner 9 Electric Heat Amps 7 Explained Operation of System to Homeowner Technician s Name _______________________Date Start Up Performance C...

Отзывы: