background image

Page 7

CBX25UH SERIES

IMPORTANT

A field-fabricated secondary drain pan, with a drain pipe
to the outside of the building, is required in all installa­
tions over a finished living space or in any area that may
be damaged by overflow from the main drain pan. In
some localities, local codes may require a secondary
drain pan for any horizontal installation.

The air handler is provided with ¾” NPT condensate drain
connections.

SLOPING THE DRAIN

Make sure the unit is sloped (similar to the slope shown in
figure 10) (horizontal or upflow) so that the drain pan will
empty completely without water standing in the pan.

THIS CORNER SHOULD BE 5/8” (+/- 1/8”) HIGHER
THAN DRAIN CORNER

DRAIN CORNER

THIS CORNER SHOULD BE 
5/8” (+/- 1/8”) HIGHER THAN
DRAIN CORNER

Figure 10. Sloping the Drain

INSTALL CONDENSATE DRAIN

1. Remove the appropriate drain knockouts. If

necessary, remove the indoor coil assembly from the
cabinet.

2. Connect primary drain line connection to the primary

drain pan connection. The primary drain connection is
flush with the bottom of the inside of the pan.
Secondary connection is raised above the bottom of
the inside of the pan.

NOTE — When making drain fitting connections to the
drain pan, hand tighten the fitting and use a thread sealant.
Over-tightening the fittings can split connections on the
drain pan.

3. If the auxiliary drain line is to be used, remove the plug

and route the drain line so that water draining from the
outlet will be easily noticed by the homeowner. The
auxiliary drain line does not require venting or a trap.
Refer to local codes.

4. After removal of drain pan plugs, check the drain port

to see if holes have been drilled. If not drilled, use a
19/32” bit to drill out the primary drain hole; use a 3/8”
drill bit for the secondary drain hole. Remove all drill
shavings.

5. Make sure drain ports and drain pan are free of all

debris.

6. Plug and check any unused drain pan openings for

tightness. Torque plugs to 30 in. lb. to prevent water
leaks or seepage from the drain pan.

7. Install a 2” trap in the primary drain lines as close to the

unit as practical (see figure 9). Make sure the top of the
trap is below the connection to the drain pan to allow
complete drainage of the pan.

NOTE — Horizontal runs must have an anti-siphon air vent
(standpipe) installed ahead of the horizontal run (See
figure 9). 
An extremely long horizontal run may require an
oversized drain line to eliminate air trapping.

NOTE — Do not operate air handler without a drain trap.
The condensate drain is on the negative pressure side of
the blower; therefore, air being pulled through the
condensate line will prevent positive drainage without a
proper trap.

8. Route the drain line to the outside or to an appropriate

drain. Drain lines must be installed so they do not block
service access to the front of the air handler. A 24”
clearance is required for filter, coil, or blower removal
and service access.

NOTE — Check local codes before connecting the drain
line to an existing drainage system.

Insulate the drain lines where sweating could cause water
damage.

TEST CONDENSATE DRAIN

Test the drain pan and drain line after installation:

1. Pour several quarts of water into drain pan, enough to

fill drain trap and line.

2. Check to make sure the drain pan is draining

completely, no leaks are found in drain line fittings, and
water is draining from the end of the primary drain line.

3. Correct any leaks found.

Duct System and Filters

DUCT SYSTEM

The air handler is provided with flanges for the connection
of the plenum and ducts. The air handler is equipped with
flanges that can form a filter rack for the installation of the
air filter, or the filter may be installed as part of the return air
duct system.

Supply and return duct system must be adequately sized
to meet the system's air requirements and static pressure
capabilities. The duct system should be insulated with a
minimum of 1” thick insulation with a vapor barrier in
conditioned areas or 2” minimum in unconditioned areas.

Table 1. Unit Air Filter Size Chart

Model

Filter Size

Actual Minimum
Filter Size

-018

12” x 20” x 1

11.50” x 19.50” x .75”

-024 and -030

15” x 20” x 1

14.50” x 19.50” x .75”

-036

18” x 20” x 1

17.50” x 19.50” x .75”

-042, -048 and -060

18” x 24” x 1

17.50” x 23.50” x .75”

Содержание CBX25UH Series

Страница 1: ...12 Table of Contents Shipping and Packing List 1 CBX25UH Series Units 1 Requirements 3 Installation Clearances 3 Installation 4 Condensate Drain 6 Duct System and Filters 7 Connecting Refrigerant Line...

Страница 2: ...4 451 17 432 16 1 2 419 20 3 4 527 16 406 5 1 2 140 40 1 2 1029 18 1 2 470 22 559 6 152 14 357 5 1 2 140 13 1 2 343 17 3 4 451 17 432 16 1 2 419 20 3 4 527 16 406 3 5 8 92 inches mm inches mm inches m...

Страница 3: ...tely assembled The unit is provided with flanges for the connection of the duct system Do not remove the cabinet knockouts until it has been determined which knockouts will need to be removed for the...

Страница 4: ...that is at least 14 from the floor This will allow proper air return HORIZONTAL DRAIN PAN IMPORTANT REMOVE PAN FOR BEST EFFICIENCY AND AIR FLOW UPFLOW DRAIN PAN UPFLOW DRAIN CON NECTIONS BOTH SIDES U...

Страница 5: ...Drain Pan Mounting Bracket 018 through 036 REMOVE BRACKETS SECURING BOTH DRAIN PANS TO UNIT Figure 5 Remove Horizontal and Main Drain Pan Mounting Brackets 042 through 060 3 Remove coil assembly bott...

Страница 6: ...OR J TRAP 3 4 OVERFLOW DRAIN AIR HANDLER DRAIN PAN WHEN A COIL IS LOCATED ABOVE A FINISHED SPACE A 3 4 19 1MM SECONDARY DRAIN LINE MUST BE S CONNECTED TO SECONDARY DRAIN PAN OR S CONNECTED TO THE OVE...

Страница 7: ...trap in the primary drain lines as close to the unit as practical see figure 9 Make sure the top of the trap is below the connection to the drain pan to allow complete drainage of the pan NOTE Horizon...

Страница 8: ...he suction and liquid lines from the fittings on the indoor coil to the fittings on the outdoor unit Run the lines in as direct a path as possible avoiding unnecessary turns and bends 2 Make sure that...

Страница 9: ...oltage S The power supply must be sized and protected according to the specifications supplied on the product S This air handler is factory configured for 240 volt single phase 60 cycles For 208 volt...

Страница 10: ...rating of the air handler If the outdoor unit is smaller than the maximum cooling capacity rating for the air handler the cooling blower speed may need to be changed Refer to blower performance chart...

Страница 11: ...d Med Blue High Black 510 670 905 495 650 865 475 630 820 420 595 770 325 505 705 24 Low Red Med Blue High Black 630 885 1130 625 875 1100 615 850 1070 610 820 1010 580 780 950 30 Low Red Med Blue Hig...

Страница 12: ...not call for heat Allow up to 5 minutes for all sequencers to cycle off Operation TIME DELAY RELAY Blower time delay operation 1 When cooling demand is initiated there is a 1 second motor on delay 2 A...

Страница 13: ...corrected Contact a qualified service technician Cabinet Insulation IMPORTANT DAMAGED INSULATION MUST BE REPAIRED OR REPLACED before the unit is put back into operation In sulation loses its insulati...

Страница 14: ...Duct Temperature ___________ THERMOSTAT Adjusted and Programmed Return External Static ______ ______ Total External Static ______ ______ 6 Supply Duct Temperature ___________ Temperature Drop _______...

Страница 15: ...Total External Static ______ ______ 6 6 Supply Duct Temperature ___________ Temperature Drop ___________ TEMPERATURE RISE Heating Mode Return Duct Temperature __________ Supply Duct Temperature ______...

Страница 16: ......

Отзывы: