Page 6
SPECIFICATIONS – CB30M
Model Number
CB30M-21/26
CB30M-31
CB30M-41
CB30M-46
CB30M-51
CB30M-65
Net face area — ft.
2
(m
2
)
3.11 (0.29)
3.56 (0.33)
4.44 (0.41)
4.44 (0.41)
5.0 (0.46)
5.0 (0.46)
Tube outside diameter — in. (mm)
3/8 (9.5)
3/8 (9.5)
3/8 (9.5)
3/8 (9.5)
3/8 (9.5)
3/8 (9.5)
Evaporator
Number of rows
3
3
3
3
3
3
Evaporator
Coil
Fins per inch (fins per m)
12 (472)
12 (472)
12 (472)
12 (472)
12 (472)
12 (472)
Suct. (va-
por) line conn. – in. (mm) sweat
5/8 (16)
3/4 (19)
3/4 (19)
7/8 (22.2)
7/8 (22.2)
1-1/8 (28)
Liquid line conn. — in. (mm) sweat
3/8 (9.5)
3/8 (9.5)
3/8 (9.5)
3/8 (9.5)
3/8 (9.5)
3/8 (9.5)
Condensate drain connection (fpt) — in. (mm)
(2) 3/4 (19)
(2) 3/4 (19)
(2) 3/4 (19)
(2) 3/4 (19)
(2) 3/4 (19)
(2) 3/4 (19)
Nominal cooling capacity — tons (kW)
1-5 – 2
(5.3 – 7.0)
2.5 (8.8)
3 (10.6)
3.5 (6.3)
4 (14.1)
5 (17.6)
Refrigerant
HCFC-22
Blower wheel nominal diameter x width — in. (mm)
10 x 7
(254 x 178)
10 x 8
(254 x 203)
11 x 8
(279 x 203)
11 x 8
(279 x 203)
11.5 x 9
(292 x 229)
12 x 9
(305 x 229)
Blower motor output — hp (W)
1/5 (149)
1/3 (249)
1/3 (249)
1/3 (249)
1/3 (249)
1/2 (373)
Number and size of filters
in.
(1) 15 x 20 x 1
(1) 20 x 20 x 1
(1) 20 x 24 x 1
Number and size of filters
mm
(1) 381x508x25
(1) 508 x 508 x 25
(1) 508 x 610 x 25
Electrical characteristics (60hz)
208/230v–1ph
208/230v–1ph
**460v – 3 ph
208/230v–1ph
208/230v – 1 ph
**460v – 3 ph
***575v – 3 ph
Shipping weight — lbs. (kg) 1 package
136 (62)
157 (71)
177 (80)
181 (82)
206 (93)
206 (93)
Optional Accessories (Must Be Ordered Extra)
Side Return Unit Stand
Catalog number
45K31
45K32
Side Return Unit Stand
(Up-Flow Only)
Ship. wt. – lbs.
(kg)
5 (2)
6 (3)
Wall Hanging Bracket Kit – Shipping weight – lbs.
(kg)
45K30
– 3 (1) (Up-Flow Only)
Down-Flow Combustible Base – Ship. wt. – lbs. (kg)
34J72
– 8 (4)
34J73
– 8 (4)
ECB29-2 5
*Output – Btuh (kW)
9,500 (2.8)
10,000 (2.9)
- - - -
- - - -
- - - -
- - - -
ECB29-2.5
A.F.U.E.
100%
100%
- - - -
- - - -
- - - -
- - - -
ECB29-5,
ECB29 5CB
*Output – Btuh (kW)
18,000 (5.3)
18,500 (5.4)
18,500 (5.4)
19,000 (5.6)
19,000 (5.6)
- - - -
ECB29-5CB
A.F.U.E.
100%
100%
100%
100%
100%
- - - -
ECB29-8,
ECB29 8CB
*Output – Btuh (kW)
28,000 (8.2)
28,500 (8.4)
28,500 (8.4)
29,000 (8.5)
29,000 (8.5)
30,500 (8.9)
ECB29-8CB
A.F.U.E.
100%
100%
100%
100%
100%
100%
ECB29-10,
ECB29 10CB
*Output – Btuh (kW)
35,000 (10.3)
35,500 (10.4)
35,500 (10.4)
36,000 (10.5)
36,000 (10.5)
37,000 (10.8)
El
t i
ECB29-10CB
A.F.U.E.
100%
100%
100%
100%
100%
100%
Electric
Heat
C
i
ECB29-12 5CB
*Output – Btuh (kW)
- - - -
44,000 (12.9)
44,000 (12.9)
44,500 (13.0)
44,500 (13.0)
45,500 (13.3)
Capacity
(1 phase)
ECB29-12.5CB
A.F.U.E.
- - - -
100%
100%
100%
100%
100%
( p
)
ECB29-15CB
*Output – Btuh (kW)
- - - -
52,500 (15.4)
52,500 (15.4)
53,000 (15.5)
53,000 (15.5)
54,000 (15.8)
ECB29-15CB
A.F.U.E.
- - - -
100%
100%
100%
100%
100%
ECB29-20CB
*Output – Btuh (kW)
- - - -
- - - -
69,500 (20.4)
70,000 (20.5)
70,000 (20.5)
71,500 (20.9)
ECB29-20CB
A.F.U.E.
- - - -
- - - -
100%
100%
100%
100%
ECB29-25CB
*Output – Btuh (kW)
- - - -
- - - -
- - - -
- - - -
87,000 (25.5)
88,500 (25.9)
ECB29-25CB
A.F.U.E.
- - - -
- - - -
- - - -
- - - -
100%
100%
ECB29-30CB
*Output – Btuh (kW)
- - - -
- - - -
- - - -
- - - -
- - - -
105,500 (30.9)
ECB29-30CB
A.F.U.E.
- - - -
- - - -
- - - -
- - - -
- - - -
100%
Annual Fuel Utilization Efficiency based on U.S. DOE test procedures and according to FTC labeling regulations.
CB30M-21/26, -31, -46, -51, -65 furnished with disposable frame type filter, CB30M-41 furnished with cleanable polyurethane frame type filter.
*Includes additional blower motor heat capacity.
**Blower motor is 460v single phase.
***Blower motor is 460v single phase. 575v electric heaters are shipped with step–down transformer for use with 460v units (CB30M-51 & CB30M-65 models only).
Содержание CB29M-21