Page 35 - Application Guide 04-2003 / Rooftop BALTIC Series - Page 35
!
If temperature entering gas burner section is below -5°C, the life expectancy of the gas burner can be
significantly affected due to corrosive condensation.
Table 4.26
Gas Power
Heating
Power abs.
Number
SIZE
Input
capacity
Electrical
of stages
kW
kW
kW
020
Standard heat
High heat
025
Standard heat
High heat
030
Standard heat
High heat
035
Standard heat
High heat
040
Standard heat
High heat
045
Standard heat
High heat
050
Standard heat
High heat
20
18,6
0,2
2
33
30,7
0,2
2
20
18,6
0,2
2
33
30,7
0,2
2
20
18,6
0,2
2
46
42,8
0,2
2
20
18,6
0,2
2
46
42,8
0,2
2
33
30,7
0,2
2
60
55,8
0,2
2
33
30,7
0,2
2
60
55,8
0,2
2
33
30,7
0,2
2
60
55,8
0,2
2
PERFORMANCES
ELECTRIC HEATER
BCK
= Cooling only rooftop
BHK
= Heat pump rooftop
Available
Number
Temperature
SIZE
capacity
of
rise at
kW
Stages
nominal air flow
020
025
030
Table 4.25
12
2 stages
stage 1
#
5,2°C
stage 2
#
10,4°C
24
2 stages
stage 1
#
10,4°C
stage 2
#
20,9°C
36
0 - 100%
50%
#
15,7°C
100%
#
31,3°C
12
2 stages
stage 1
#
4,2°C
stage 2
#
8,4°C
24
2 stages
stage 1
#
8,4°C
stage 2
#
16,7°C
36
0 - 100%
50%
#
12,5°C
100%
#
25,1°C
24
2 stages
stage 1
#
7°C
stage 2
#
13,9°C
36
2 stages
stage 1
#
10,4°C
stage 2
#
20,9°C
48
0 - 100%
50%
#
13,9°C
100%
#
27,9°C
Available
Number
Temperature
SIZE
capacity
of
rise at
kW
Stages
nominal air flow
035
040
045
050
Table 4.47
24
2 stages
stage 1
#
6°C
stage 2
#
11,9°C
36
2 stages
stage 1
#
9°C
stage 2
#
17,9°C
48
0 - 100%
50%
#
11,9°C
100%
#
23,9°C
27
2 stages
stage 1
#
3,9°C
stage 2
#
11,8°C
45
2 stages
stage 1
#
7,8°C
stage 2
#
19,6°C
54
0 - 100%
50%
#
11,8°C
100%
#
23,5°C
27
2 stages
stage 1
#
3,4°C
stage 2
#
10,4°C
45
2 stages
stage 1
#
7,0°C
stage 2
#
17,4°C
54
0 - 100%
50%
#
10,4°C
100%
#
20,9°C
27
2 stages
stage 1
#
3,1°C
stage 2
#
9,4°C
45
2 stages
stage 1
#
6,3°C
stage 2
#
15,7°C
54
0 - 100%
50%
#
9,4°C
100%
#
18,8°C
GAS BURNER
BGK
= Cooling only rooftop with gas fired heater
BDK
= Heat pump rooftop with gas fired heater
ACCESSORIES HEATING CAPACITIES