background image

Page 16 of 24

506468-01

Issue  1946

on the control board mounted inside the unit control box. 

This feature is optional for the homeowner, but may impact 

testing performance.

Defrost Operation

The defrost control system has three basic operational 

modes: normal, calibration, and defrost.

•  Normal Mode—

The demand defrost system monitors 

the O line, to determine the system operating mode 

(heat/cool), outdoor ambient temperature, coil 

temperature (outdoor coil) and compressor run time to 

determine when a defrost cycle is required.

•  Calibration Mode—

The board is considered 

uncalibrated when power is applied to the board, 

after cool mode operation, or if the coil temperature 

exceeds the termination temperature when it is in heat 

mode.
Calibration of the board occurs after a defrost cycle 

to ensure that there is no ice on the coil. During 

calibration, the temperature of both the coil and 

the ambient sensor are measured to establish the 

temperature  differential  which  is  required  to  allow  a 

defrost cycle.

•  Defrost Mode—

The following paragraphs provide a 

detailed description of the defrost system operation.

Defrost Cycles

The demand defrost control board initiates a defrost cycle 

based on either frost detection or time.

•  Frost Detection

—If the compressor runs longer than 

30  minutes  and  the  actual  difference  between  the 

clear coil and frosted coil temperatures exceeds the 

maximum difference allowed by the control, a defrost 

cycle will be initiated.

IMPORTANT

 - 

The demand defrost control board will 

allow a greater accumulation of frost and will initiate 

fewer defrost cycles than a time/ temperature defrost 

system.

•  Time

—If 6 hours of heating mode compressor run time 

has elapsed since the last defrost cycle while the coil 

temperature remains below 35°F (2°C), the demand 

defrost control will initiate a defrost cycle.

Actuation

When the reversing valve is de-energized, the Y1 circuit is 

energized, and the coil temperature is below 35°F (2°C), 

the board logs the compressor run time. If the board is not 

calibrated, a defrost cycle will be initiated after 30 minutes 

of heating mode compressor run time. The control will 

attempt to self-calibrate after this (and all other) defrost 

cycle(s).

Calibration success depends on stable system 

temperatures during the 20-minute calibration period. If 

the board fails to calibrate, another defrost cycle will be 

initiated after 45 minutes of heating mode compressor 

run time. Once the control board is calibrated, it initiates 

a  demand  defrost  cycle  when  the  difference  between 

the clear coil and frosted coil temperatures exceeds the 

maximum  difference  allowed  by  the  control  OR  after  6 

hours of heating mode compressor run time has been 

logged since the last defrost cycle.

NOTE: 

If ambient or coil fault is detected, the board will not 

execute the “TEST” mode.

Termination

The defrost cycle ends when the coil temperature exceeds 

the termination temperature or after 14 minutes of defrost 

operation. If the defrost is terminated by the 14-minute 

timer, another defrost cycle will be initiated after 30 minutes 

of run time.

Control Board Diagnostics and Test Mode

Control Board Diagnostics

See control board diagnostic LED table (Table 6) to 

determine control board operational conditions and to 

diagnose cause and solution to problems. 

Test Mode

When Y1 is energized and 24V power is being applied 

to the board, a test cycle can be initiated by placing the 

termination temperature jumper across the “Test” pins for 

2 to 5 seconds. If the jumper remains across the “Test” pins 

longer than 5 seconds, the control will ignore the test pins 

and revert to normal operation. The jumper will initiate one 

cycle per test.

Enter the “TEST” mode by placing a shunt (jumper) across 

the “TEST” pins on the board after power-up. (The “TEST” 

pins are ignored and the test function is locked out if the 

shunt is applied on the “TEST” pins before power-up). Board 

timings are reduced, the low pressure switch is ignored 

and the board will clear any active lockout condition.

Each test pin shorting will result in one test event.

 

For each “TEST” the shunt (jumper) must be removed for 

at  least  1  second  and  reapplied.  Refer  to  flow  chart  for 

“TEST” operation.

NOTE: 

The Y1 input must be active (ON) and the “O” room 

thermostat terminal into board must be inactive.

Содержание Allied Air Enterprises BHP16L

Страница 1: ...l as well as the instructions supplied in separate equipment before starting the installation Observe and follow all warnings cautions instructional labels and tags Failure to comply with these instru...

Страница 2: ...when lifting avoid contact with sharp edges Installation NOTE In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment Locate unit away from wi...

Страница 3: ...cted by a wall or other barrier Table 2 Clearances 30 around Control Box 24 6 NOTE See Table 2 for specific minimum clearance guidelines Figure 2 DO LOCATE THE UNIT With proper clearances on sides and...

Страница 4: ...Size 12 ft 25 ft 50 ft 75 ft 100 ft 24 000 3 4 7 8 3 4 7 8 7 8 36 000 7 8 7 8 7 8 7 8 1 1 8 48 000 7 8 7 8 7 8 1 1 8 1 1 8 60 000 1 1 8 1 1 8 1 1 8 1 1 8 1 1 8 For lines longer than 50 ft refer to lo...

Страница 5: ...UNIT VAPOR LINE SERVICE VALVE VAPOR LIQUID 1 A B C D A Cylinder with clean R 410A positioned to deliver liquid refrigerant to the vapor service valve B Refrigerant gauge set low side to the liquid lin...

Страница 6: ...il Shown Sensing bulb insulation is required if mounted external to the coil casing sensing bulb installation for bulb positioning STUB END TEFLON RING LIQUID LINE ASSEMBLY WITH BRASS NUT DISTRIBUTOR...

Страница 7: ...ound Do not crimp end of the line Remove service cap and core from both the vapor and liquid line service ports 1 2 LIQUID LINE SERVICE VALVE SERVICE PORT CORE SERVICE PORT CAP SERVICE PORT CORE SERVI...

Страница 8: ...ES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WRAP SERVICE VALVES To help protect service valve seals during brazing wrap water saturated cloths around service valve bodies and co...

Страница 9: ...of the manifold gauge set in order to pressurize the line set and the indoor unit E After a few minutes open one of the service valve ports and verify that the refrigerant added to the system earlier...

Страница 10: ...id refrigerant Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit G Perform the following Close manifold gauge valves Shut off HFC 410A cylinder R...

Страница 11: ...nch with a hex head extension to back the stem out counterclockwise as far as it will go Use a 3 16 hex head extension for liquid line service valves and a 5 16 extension for suction line service valv...

Страница 12: ...ring 2 Ground unit at unit disconnect switch or to an earth ground To facilitate conduit a hole is in the bottom of the control box Connect conduit to the control box using a proper conduit fitting Un...

Страница 13: ...e 4 for refrigerant charge adjustment A blank space is provided on the unit rating plate to list the actual field charge Table 4 Refrigerant Charge Adjustment Liquid Line Set Diameter Oz Per 5 ft adju...

Страница 14: ...he compressor during test mode High Pressure Switch HI PS When the high pressure switch trips the control board will cycle off the compressor and the strike counter in the board will count one strike...

Страница 15: ...rost mode Units are shipped with jumper installed on DELAY pins NOTE The 30 second compressor delay feature known as the quiet shift must be deactivated during any unit performance testing The feature...

Страница 16: ...e will be initiated after 30 minutes of heating mode compressor run time The control will attempt to self calibrate after this and all other defrost cycle s Calibration success depends on stable syste...

Страница 17: ...n system 3 Improper metering device installed or incorrect operation of metering device 4 Incorrect or improper sensor location or connection to system 1 Remove any blockages or restrictions from coil...

Страница 18: ...Page 18 of 24 506468 01 Issue 1946 24V No 24V...

Страница 19: ...he control board without experiencing nuisance alerts Thermostat Wiring The diagnostic module requires a thermostat demand signal to operate properly See Figure 6 for connections The thermostat signal...

Страница 20: ...mer is overloaded 2 Low line voltage contact utility if voltage at disconnect is low Check wiring conditions Table 7 Diagnostic Module Codes Mis wired Module Troubleshooting Mis wired Module Indicatio...

Страница 21: ...ent fins may affect unit operation SHARP OBJECT HAZARD Condenser coils have sharp edges Wear adequate body protection on body extremities e g gloves FAILURE TO FOLLOW THIS WARNING COULD RESULT IN BODI...

Страница 22: ...he defrost cycle In case of extended power outage If the outdoor temperature is below 50 F and power to your outdoor unit has been interrupted for one hour or longer observe the following when restori...

Страница 23: ...506468 01 Page 23 of 24 Issue 1946 Figure 9 Two Stage Wiring Diagram 24 36 48 Models Only...

Страница 24: ...Page 24 of 24 506468 01 Issue 1946 Figure 10 Two Stage Wiring Diagram 60 Model Only...

Отзывы: