background image

506468-01

Page 17 of 24

Issue  1946

Control Board Diagnostic LEDs

DS2 

Green

DS1 

Red

Condition / Code

Possible Cause(s)

Solution

Off

Power problem

No power (24V) to board 

terminals R & C or board 

failure.

1

 Check control transformer power (24V). 

2

 If power is available to board and LED(s) do not light, 

replace board.

Simultaneous 

SLOW flash

Normal operation

Unit operating normally or in 

standby mode.

None required.

Alternating 

SLOW flash

5-minute anti-short cycle 

delay

Initial power up, safety trip, 

end of room thermostat 

demand.

None required (Jumper TEST pins to override)

Simultaneous 

FAST flash

Ambient sensor problem

Sensor being detected open or shorted or out of temperature range. Board will revert 

to time/temperature defrost operation. (System will still heat or cool)

Alternating 

FAST flash

Coil sensor problem

Sensor being detected open or shorted or out of temperature range. Board will not 

perform demand or time/temperature defrost operation. (System will still heat or cool)

On

Circuit board failure

Indicates that board has internal component failure. Cycle 24V power to board. If 

code does not clear, replace board.

Fault & Lockout Codes (Each fault adds 1 strike to that code’s counter; 5 strikes per code = LOCKOUT)

Off

SLOW 

flash

Low pressure fault

1. 

Restricted air flow over 

indoor or outdoor coil.

2.  Improper refrigerant 

charge in system.

3.  Improper metering device 

installed or incorrect 

operation of metering 

device.

4.  Incorrect or improper 

sensor location or 

connection to system.

1.  Remove any blockages or restrictions from coils 

and/or fans. Check indoor and outdoor fan motor 

for proper current draws.

2.  Check system charge using approach & sub-

cooling temperatures.

3.  Check system operating pressures and compare 

to unit charging charts.

4.  Make sure all pressure switches and sensors 

have secure connections to system to prevent 

refrigerant leaks or errors in pressure and 

temperature measurements.

Off

On

Low pressure LOCKOUT

SLOW 

flash

Off

High pressure fault

On

Off

High pressure LOCKOUT

SLOW 

flash

On

Discharge line 

temperature fault

This code detects shorted sensor or high discharge temperatures. If the discharge 

line temperature exceeds a temperature of 300°F (148°C) during compressor 

operation, the board will de-energize the compressor contactor output (and 

the defrost output if active). The compressor will remain off until the discharge 

temperature has dropped below 225°F (107°C).

FAST 

flash

On

Discharge Line 

Temperature LOCKOUT

Off

FAST 

flash

Discharge sensor fault

The board detects open sensor or out of temperature sensor range. This fault is 

detected by allowing the unit to run for 90 seconds before checking sensor resistance. 

If the sensor resistance is not within range after 90 seconds, the board will count one 

fault. After 5 faults, the board will lockout.

FAST 

flash

Off

Discharge sensor 

LOCKOUT

Table 6. Control Board Diagnostic LEDs

Содержание Allied Air Enterprises BHP16L

Страница 1: ...l as well as the instructions supplied in separate equipment before starting the installation Observe and follow all warnings cautions instructional labels and tags Failure to comply with these instru...

Страница 2: ...when lifting avoid contact with sharp edges Installation NOTE In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment Locate unit away from wi...

Страница 3: ...cted by a wall or other barrier Table 2 Clearances 30 around Control Box 24 6 NOTE See Table 2 for specific minimum clearance guidelines Figure 2 DO LOCATE THE UNIT With proper clearances on sides and...

Страница 4: ...Size 12 ft 25 ft 50 ft 75 ft 100 ft 24 000 3 4 7 8 3 4 7 8 7 8 36 000 7 8 7 8 7 8 7 8 1 1 8 48 000 7 8 7 8 7 8 1 1 8 1 1 8 60 000 1 1 8 1 1 8 1 1 8 1 1 8 1 1 8 For lines longer than 50 ft refer to lo...

Страница 5: ...UNIT VAPOR LINE SERVICE VALVE VAPOR LIQUID 1 A B C D A Cylinder with clean R 410A positioned to deliver liquid refrigerant to the vapor service valve B Refrigerant gauge set low side to the liquid lin...

Страница 6: ...il Shown Sensing bulb insulation is required if mounted external to the coil casing sensing bulb installation for bulb positioning STUB END TEFLON RING LIQUID LINE ASSEMBLY WITH BRASS NUT DISTRIBUTOR...

Страница 7: ...ound Do not crimp end of the line Remove service cap and core from both the vapor and liquid line service ports 1 2 LIQUID LINE SERVICE VALVE SERVICE PORT CORE SERVICE PORT CAP SERVICE PORT CORE SERVI...

Страница 8: ...ES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WRAP SERVICE VALVES To help protect service valve seals during brazing wrap water saturated cloths around service valve bodies and co...

Страница 9: ...of the manifold gauge set in order to pressurize the line set and the indoor unit E After a few minutes open one of the service valve ports and verify that the refrigerant added to the system earlier...

Страница 10: ...id refrigerant Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit G Perform the following Close manifold gauge valves Shut off HFC 410A cylinder R...

Страница 11: ...nch with a hex head extension to back the stem out counterclockwise as far as it will go Use a 3 16 hex head extension for liquid line service valves and a 5 16 extension for suction line service valv...

Страница 12: ...ring 2 Ground unit at unit disconnect switch or to an earth ground To facilitate conduit a hole is in the bottom of the control box Connect conduit to the control box using a proper conduit fitting Un...

Страница 13: ...e 4 for refrigerant charge adjustment A blank space is provided on the unit rating plate to list the actual field charge Table 4 Refrigerant Charge Adjustment Liquid Line Set Diameter Oz Per 5 ft adju...

Страница 14: ...he compressor during test mode High Pressure Switch HI PS When the high pressure switch trips the control board will cycle off the compressor and the strike counter in the board will count one strike...

Страница 15: ...rost mode Units are shipped with jumper installed on DELAY pins NOTE The 30 second compressor delay feature known as the quiet shift must be deactivated during any unit performance testing The feature...

Страница 16: ...e will be initiated after 30 minutes of heating mode compressor run time The control will attempt to self calibrate after this and all other defrost cycle s Calibration success depends on stable syste...

Страница 17: ...n system 3 Improper metering device installed or incorrect operation of metering device 4 Incorrect or improper sensor location or connection to system 1 Remove any blockages or restrictions from coil...

Страница 18: ...Page 18 of 24 506468 01 Issue 1946 24V No 24V...

Страница 19: ...he control board without experiencing nuisance alerts Thermostat Wiring The diagnostic module requires a thermostat demand signal to operate properly See Figure 6 for connections The thermostat signal...

Страница 20: ...mer is overloaded 2 Low line voltage contact utility if voltage at disconnect is low Check wiring conditions Table 7 Diagnostic Module Codes Mis wired Module Troubleshooting Mis wired Module Indicatio...

Страница 21: ...ent fins may affect unit operation SHARP OBJECT HAZARD Condenser coils have sharp edges Wear adequate body protection on body extremities e g gloves FAILURE TO FOLLOW THIS WARNING COULD RESULT IN BODI...

Страница 22: ...he defrost cycle In case of extended power outage If the outdoor temperature is below 50 F and power to your outdoor unit has been interrupted for one hour or longer observe the following when restori...

Страница 23: ...506468 01 Page 23 of 24 Issue 1946 Figure 9 Two Stage Wiring Diagram 24 36 48 Models Only...

Страница 24: ...Page 24 of 24 506468 01 Issue 1946 Figure 10 Two Stage Wiring Diagram 60 Model Only...

Отзывы: