506550-01
Page 21 of 66
Issue 1230
5.
On field supplied terminations for sidewall exit, exhaust
piping may extend a maximum of 12 inches (305 mm)
for 2” PVC and 20 inches (508 mm) for 3” (76 mm) PVC
beyond the outside wall. Intake piping should be as
short as possible. See Figures 24 and 25.
6.
On field supplied terminations, a minimum distance
between the end of the exhaust pipe and the end of the
intake pipe without a termination elbow is 8” and a
minimum distance of 6” with a termination elbow. See
Figures 24 and 25.
7.
If intake and exhaust piping must be run up a side wall
to position above snow accumulation or other
obstructions, piping must be supported every 24” (610
mm) as shown in Figures 24 and 25. In addition, close
coupled wall termination must be extended for use in
this application. See Figures 24 and 25. When exhaust
and intake piping must be run up an with pipe sized per
Table 6. The intake piping may be equipped with a 90°
elbow turndown. Using turndown will add 5 feet (1.5 m)
to the equivalent length of the pipe.
DIRECT VENT CONCENTRIC ROOFTOP TERMINATION
71M80, 69M29 or 60L46 (US)
44W92 or 44W93 (Canada)
Figure 26
EXHAUST PIPE TERMINATION SIZE REDUCTION
Table 6
See venting Table 5 for maximum venting lengths with this
arrangement.
* Use wall support every 24” (610 mm). Use two wall supports if
extension is greater than 24” (610 mm) but less than 48” (1219 mm).
NOTE:
One wall support must be 6” (152 mm) from top of each pipe
(intake and exhaust).
FIELD SUPPLIED WALL TERMINATION
with INTAKE ELBOW
Figure 25
Содержание Allied Air A96UHMV
Страница 3: ...506550 01 Page 3 of 66 Issue 1230 A96UHMV Exploded View Figure 1...
Страница 16: ...506550 01 Page 16 of 66 Issue 1230 Table 5 MAXIMUM ALLOWABLE VENT LENGTH feet...
Страница 30: ...506550 01 Page 30 of 66 Issue 1230 Low Voltage Field Wiring Table 11 R required on some units...
Страница 31: ...506550 01 Page 31 of 66 Issue 1230 Low Voltage Field Wiring Table 11 R required on some units...
Страница 32: ...506550 01 Page 32 of 66 Issue 1230 Low Voltage Field Wiring Table 11 2 Stage Single Stage...
Страница 33: ...506550 01 Page 33 of 66 Issue 1230 TYPICAL WIRING DIAGRAM Figure 40...
Страница 34: ...506550 01 Page 34 of 66 Issue 1230 Integrated Control Figure 41...
Страница 38: ...506550 01 Page 38 of 66 Issue 1230 BLOWER DATA...
Страница 39: ...506550 01 Page 39 of 66 Issue 1230 BLOWER DATA...
Страница 40: ...506550 01 Page 40 of 66 Issue 1230 BLOWER DATA...
Страница 41: ...506550 01 Page 41 of 66 Issue 1230 BLOWER DATA...
Страница 42: ...506550 01 Page 42 of 66 Issue 1230 BLOWER DATA...
Страница 43: ...506550 01 Page 43 of 66 Issue 1230 BLOWER DATA...
Страница 44: ...506550 01 Page 44 of 66 Issue 1230 BLOWER DATA...
Страница 45: ...506550 01 Page 45 of 66 Issue 1230 BLOWER DATA...
Страница 46: ...506550 01 Page 46 of 66 Issue 1230 BLOWER DATA...
Страница 47: ...506550 01 Page 47 of 66 Issue 1230 COOLING OPERATING SEQUENCE A96UHMV and Single Stage Outdoor Unit Table 19...
Страница 48: ...506550 01 Page 48 of 66 Issue 1230 COOLING OPERATING SEQUENCE A96UHMV and Two Stage Outdoor Unit Table 20...
Страница 58: ...506550 01 Page 58 of 66 Issue 1230 Configuring Unit Size Codes...
Страница 63: ...506550 01 Page 63 of 66 Issue 1230 Troubleshooting Cooling Sequence of Operation Call for Cooling...