2.3.- SERVICE SPACE

Free space should be left to enable access for servicing, in order to check the installation of 

the cables, drainage connections, electrical installation and cleaning fi lters, as well as to give 
easy access to the unit.

2.4.- DRAINAGE

All units have a 3/4” steel threaded drainage pipe welded to the condensation tray.
Drainage pipes will be fi tted for each tray through a siphon with a height difference of 80 
mm. to avoid drainage problems from the depression formed by the fans. The pipes should 
have a 2% slope to enable condensation to be drained easily.

Also tip the unit slightly (2%) toward the drainage side. Check that the condensation trays are clean 
and free of dirt and other debris from the installation work and that water drains correctly.

UNIT

Min. 80 mm

Inspection and cleaning cap.

2.5.- REFRIGERANT CONNECTIONS
The unit is supplied with gas and liquid lines, sealed with copper caps.

THE UNITS ARE SUPPLIED WITH NITROGEN GAS. THIS MUST BE REMOVED BEFORE PROCEEDING AS FOLLOWS:

1  Remove the nitrogen gas through the top and bottom 5/16” service ports, leaving a vacuum as a safety measure.
2  Remove the caps from the connecting pipes.
3  Braze the connecting pipes. 
  (When brazing refrigerant pipes, nitrogen gas must be supplied through the service ports into the pipes to remove 

any air).

DURING INSTALLATION OPERATIONS, KEEP GAS AND LIQUID PIPES COVERED, IN ORDER TO PREVENT HUMIDITY AND 
DIRT FROM GETTING INTO THEM.
TAKE SPECIAL CARE TO ENSURE THAT  REFRIGERANT PIPES ARE INSULATED.
AVOID COLLAPSE ON PIPE LINES INSTALLATION. 

- 100D and 120D units model use different sizes of pipe connections: big size 
for circuit 1 and small size for circuit 2.

Please be sure to connect indoor unit circuits C1 and C2 to the corresponding C1 and C2 circuits of the outdoor unit.

2. INSTALLATION

Legislation does not allow refrigerant gas emissions to the atmosphere, so the refrigerants have to be recycled to avoid being 
released to the atmosphere. Those recycled refrigerants shall be processed afterwards by an authorized waste manager.

Those components derived from the recycling of the unit have to be managed by authorized waste manager or be left in local 
waste facilities according the local normative in each country. 

Содержание AIRCOOLAIR CIC 020S

Страница 1: ...lennoxemeia com COMPACTAIR CSC CSH CDC CDH Installation operating and maintenance Indoor unit MIL121E 0613 11 2014 Translation of original manual...

Страница 2: ...available to third parties without the prior written agreement of Lennox INSTALLATION OPERATION MAINTENANCE MANUAL TABLE OF CONTENTS AIRCOOLAIR COMPACTAIR INDOOR UNITS POINTS TO BEAR IN MIND Manufactu...

Страница 3: ...he user with the equipment reproduced photocopied transferred or transmitted to third parties without prior written authorization from Lennox Data published in the operating instructions are based on...

Страница 4: ..._____________________________________________________ CHECKS __________________________________________________________________________________ ________________________________________________________...

Страница 5: ...6 48 8 60 8 60 11 1 11 1 6 44 13 0 13 0 17 3 26 4 26 4 26 4 35 6 60 2 60 2 81 81 3N 400V 50 Hz 3 400V 50Hz M 400V 3 50 1 GENERAL CHARACTERISTICS 1 1 PHYSICAL DATA Type of unit COMPACTAIR AIRCOOLAIR I...

Страница 6: ...0D MAP MC MAP MC MAP MC 0 0 0 0 0 0 1 32 2 5 1 32 2 5 2 41 4 2 3 73 6 7 5 06 8 6 3 74 6 1 3 73 6 7 5 06 8 6 6 38 11 1 2 65 4 5 5 3 9 5 3 9 3 63 6 5 5 06 8 6 6 38 11 1 20 28 6 27 39 27 39 27 39 40 57 8...

Страница 7: ...16250 160 117 75 34 n a 16725 149 105 63 20 n a 100D 750 710 670 630 591 17350 237 202 167 133 101 18875 223 185 149 115 81 20400 168 131 94 59 22450 100 63 25 120D 750 710 670 630 591 19300 207 169 1...

Страница 8: ...223 177 132 88 16250 253 203 154 107 60 16725 244 193 144 95 48 100D 837 792 748 704 659 17350 323 279 236 196 157 18875 310 264 221 180 140 20400 296 248 204 162 121 22450 178 133 90 120D 837 792 74...

Страница 9: ...371 307 245 183 16250 418 349 282 215 150 16725 408 338 270 202 135 100D 937 888 838 788 738 17350 477 419 364 312 262 18875 469 410 354 299 248 20400 458 398 341 284 232 22450 440 379 319 261 206 120...

Страница 10: ...64 387 315 16250 609 526 445 367 289 16725 602 518 436 357 279 100D 1041 986 931 876 820 17350 606 537 469 407 346 18875 599 529 461 396 334 20400 592 519 451 384 321 22450 504 433 364 299 120D 1041 9...

Страница 11: ...300 381 343 305 268 232 21000 380 340 300 263 227 22700 380 337 297 257 220 24750 373 330 287 245 205 140D 766 725 684 644 603 21000 380 340 300 263 227 22700 380 337 297 257 220 24750 373 330 287 245...

Страница 12: ...frigerant connections Electrical power supply Access to motor Drainage outside thread 3 4 VERTICAL DISCHARGE OPTIONAL Refrigerant connections Electrical power supply HORIZONTAL DISCHARGE STANDARD Acce...

Страница 13: ...hread 3 4 VERTICAL DISCHARGE OPTIONAL Drainage outside thread 3 4 Transportation support HORIZONTAL DISCHARGE STANDARD VERTICAL DISCHARGE OPTIONAL Electrical power supply Electrical power supply Refri...

Страница 14: ...late will always be visible since this data will be necesary to assure proper maintenance The units are designed to be installed with ducts calculated by quali ed technical staff The joints to be used...

Страница 15: ...Remove the nitrogen gas through the top and bottom 5 16 service ports leaving a vacuum as a safety measure 2 Remove the caps from the connecting pipes 3 Braze the connecting pipes When brazing refrige...

Страница 16: ...L DIAGRAM SUPPIED WITH THE UNIT CONNECTION OF CONTROL ELEMENTS VOLTAGE OPERATING LIMITS 342 462V To be connected by installer POWER SUPPY COMPONENT Nr WIRES X SECTION Discharge sensor STANDARD 2 x 1 m...

Страница 17: ...of the electrical heater once installed Support A HEATING COIL FROZEN DUE TO LOW AMBIENT CONDITIONS IS NOT COVERED BY THE WARRANTY INDOOR UNIT FREE COOLING 1 OPERATION The control compares the values...

Страница 18: ...R MIXING SECTION INDOOR UNIT OUTDOOR UNIT RETURN AIR DUCT FRESH AIR INTAKE ELECTRICAL BOX AIR FILTER 5x1 Shielded 2x1 Shielded 2x1 Shielded 5x1 Shielded 3x1 Shielded 3x1 Shielded 2x1 Shielded 5x1 Shie...

Страница 19: ...5x1 Shielded 2x1 Shielded 2x1 Shielded 5x1 Shielded 3x1 Shielded 3x1 Shielded 2x1 Shielded ELECTRICAL BOX MIXING SECTION ELECTRICAL BOX 2x1 Shieled 6x1 5 4x2 5 With EFM 5x1 5 Standard version OUTDOOR...

Страница 20: ...5D 070D 085D INDOOR UNIT SECTION OF FLEXIBLE DUCT TO BE INSTALLED BY THE CUSTOMER 2100 x 698mm2 OUTDOOR AIR DAMPER MIXING SECTION DISCHARGE FRAME 490x508x40 EXHAUST FAN OPTION RETURN AIR An exhaust fa...

Страница 21: ...INSTALLED BY THE CUSTO MER 1626 x 679mm2 SECTION OF FLEXIBLE DUCT TO BE INSTALLED BY THE CUSTOMER 2100 x 698 mm2 DISCHARGE FRAME DISCHARGE AIR DIMENSIONS FREE COOLING WITH RETURN FAN MODELS 055D 070D...

Страница 22: ...ter which should be in its housing and correctly positioned the metal grille should be facing inwards 5 Check with your hand that the fan turns freely SKETCH FOR THE STANDARD UNIT CONFIGURATION IN DOU...

Страница 23: ...g or changing the air lters will depend on the quality air in the area fumes vapors suspended dust particles etc Remember that the metal grille should always be toward the inside of the unit SIDE REMO...

Страница 24: ...EMBOURG FRANCE GERMANY ITALY NETHERLANDS POLAND PORTUGAL Due to Lennox s ongoing commitment to quality the speci cations ratings and dimensions are subject to change without notice and without incurri...

Отзывы: