ELECTRICAL CONNECTIONS
- Before making any electrical connections, be sure that all circuit breakers are open.
- In order to carry out the electrical connections, follow the electrical diagram suppied with the unit.
Note: The length of all cables for connection with indoor
unit must be less than 65 m.
To be connected by installer
OUTDOOR SECTION
Electrical box
VOLTAGE OPERATING LIMITS: 342-462V
CONNECTION OF CONTROL ELEMENTS:
COMPONENT
Split unit
Condensing unit
Discharge sensor
STANDARD
2 x 1 mm² (shielded)
Outdoor sensor
STANDARD
Remote ambient sensor
Remote duct sensor
OPTION
Duct remote sensor for enthalpic free-cooling
5 x 1 mm² (shielded)
CO2 Air quality probe. (Available only with
enthalpic free-cooling)
4 x 1 mm² (shielded)
Air differential pressure transducer
3 x 1 mm² (shielded)
Outdoor sensor for enthalpic free-cooling
5 x 1 mm² (shielded)
Remote ambient sensor for enthalpic free-
cooling
5 x 1 mm² (shielded)
Dirty fi lter sensor
2 x 1,5 mm²
Long distance connection
3 x 1,5 mm² (1 circuit units)
2 x (3 x 1,5 mm²) (2 circuits units)
Smoke detector
7 x 1,5 mm²
Hot water coil
5 x 1,5 mm²
INDOOR SECTION