BLOWER DATA 

CB(X)26UH−018 BLOWER PERFORMANCE

External Static

Pressure

Air Volume at

Specific Blower Taps

Pressure

High

Low

in. w.g.

Pa

cfm

L/s

cfm

L/s

.10

25

1020

460

755

340

.20

50

960

435

715

325

.30

75

885

400

675

305

.40

100

800

365

625

285

.50

125

690

315

570

260

.60

150

525

250

500

235

NOTE − All air data measured external to unit with dry coil and 1 inch non−pleated air
filter in place.
Electric heaters have no appreciable air resistance.

CB(X)26UH−024 BLOWER PERFORMANCE

External Static

Pressure

Air Volume at

Specific Blower Taps

Pressure

High

Low

in. w.g.

Pa

cfm

L/s

cfm

L/s

.10

25

1040

470

1000

455

.20

50

980

445

940

425

.30

75

905

410

870

395

.40

100

815

370

785

355

.50

125

705

320

680

310

.60

150

535

250

530

250

NOTE − All air data measured external to unit with dry coil and 1 inch non−pleated air
filter in place.
Electric heaters have no appreciable air resistance.

CB(X)26UH−030 BLOWER PERFORMANCE

External Static

Pressure

Air Volume at

Specific Blower Taps

Pressure

High

Low

in. w.g.

Pa

cfm

L/s

cfm

L/s

.10

25

1350

610

1145

520

.20

50

1290

585

1090

495

.30

75

1225

555

1030

465

.40

100

1150

520

960

435

.50

125

1065

485

875

395

.60

125

965

455

775

365

NOTE − All air data measured external to unit with dry coil and 1 inch non−pleated air
filter in place.
Electric heaters have no appreciable air resistance.

CB(X)26UH−036 BLOWER PERFORMANCE

External Static

Pressure

Air Volume at

Specific Blower Taps

Pressure

High

Low

in. w.g.

Pa

cfm

L/s

cfm

L/s

.10

25

1560

705

1405

635

.20

50

1480

670

1340

610

.30

75

1390

630

1270

575

.40

100

1290

585

1185

540

.50

125

1170

530

1090

495

.60

150

1015

480

975

460

NOTE − All air data measured external to unit with dry coil and 1 inch non−pleated air
filter in place.
Electric heaters have no appreciable air resistance.

CB(X)26UH−042 BLOWER PERFORMANCE

External Static

Pressure

Air Volume at

Specific Blower Taps

Pressure

High

Low

in. w.g.

Pa

cfm

L/s

cfm

L/s

.10

25

1940

880

1785

810

.20

50

1845

835

1705

775

.30

75

1745

790

1615

730

.40

100

1630

740

1515

685

.50

125

1495

680

1400

635

.60

150

1330

630

1265

595

NOTE − All air data measured external to unit with dry coil and 1 inch non−pleated air
filter in place.
Electric heaters have no appreciable air resistance.

CB(X)26UH−048 BLOWER PERFORMANCE

External Static

Pressure

Air Volume at

Specific Blower Taps

Pressure

High

Low

in. w.g.

Pa

cfm

L/s

cfm

L/s

.10

25

1945

880

1870

850

.20

50

1860

845

1790

810

.30

75

1765

800

1700

770

.40

100

1660

155

1600

725

.50

125

1540

700

1485

675

.60

150

1395

660

1350

635

NOTE − All air data measured external to unit with dry coil and 1 inch non−pleated air
filter in place.
Electric heaters have no appreciable air resistance.

CB(X)26UH−060 BLOWER PERFORMANCE

External Static

Pressure

Air Volume at

Specific Blower Taps

Pressure

High

Low

in. w.g.

Pa

cfm

L/s

cfm

L/s

.10

25

2160

980

2075

940

.20

50

2065

935

1985

900

.30

75

1960

890

1885

855

.40

100

1845

835

1775

805

.50

125

1710

775

1645

745

.60

150

1550

730

1495

705

NOTE − All air data measured external to unit with dry coil and 1 inch non−pleated air
filter in place.
Electric heaters have no appreciable air resistance.

Содержание Air Handler CB26UH

Страница 1: ... CB26UH and CBX26UH cabinets Information contained in this manual is intended for use by ex perienced HVAC service technicians only All specifications are subject to change Procedures outlined in this manual are pre sented as a recommendation only and do not supersede or re place local or state codes IMPORTANT Improper installation adjustment alteration service or maintenance can cause property da...

Страница 2: ...ns Suction Vapor line o d in mm sweat 7 8 22 2 7 8 22 2 7 8 22 2 Liquid line o d in mm sweat 3 8 9 5 3 8 9 5 3 8 9 5 Condensate in mm fpt 2 3 4 19 2 3 4 19 2 3 4 19 Blower Wheel nominal diameter x width in mm 11 x 8 279 x 203 11 x 8 279 x 203 11 1 2 x 9 292 x 229 Blower motor output hp W 1 3 249 1 2 373 1 2 373 1 Filters Size of filter in mm 18 x 25 x 1 457 x 635 x 25 18 x 25 x 1 457 x 635 x 25 18...

Страница 3: ... cfm L s cfm L s 10 25 1560 705 1405 635 20 50 1480 670 1340 610 30 75 1390 630 1270 575 40 100 1290 585 1185 540 50 125 1170 530 1090 495 60 150 1015 480 975 460 NOTE All air data measured external to unit with dry coil and 1 inch non pleated air filter in place Electric heaters have no appreciable air resistance CB X 26UH 042 BLOWER PERFORMANCE External Static Pressure Air Volume at Specific Blo...

Страница 4: ...e The units come with factory installed check and expansion valve for all applications The TXV valve has been installed internally for a cleaner installation and is accessible if required ELECTROSTATIC DISCHARGE ESD Precautions and Procedures CAUTION Electrostatic discharge can affect electronic components Take precautions during unit instal lation and service to protect the unit s electronic cont...

Страница 5: ...n heating speed refer to unit wiring diagram 3 Time Delay Relay The blower time delay is a 24 volt N O relay wired to the blower relay See unit diagram The delay is between 10 and 60 seconds and delays the blower on and off time in the cooling cycle BLOWER ASSEMBLY FIGURE 3 B Blower Motor B3 CB26UH and CBX26UH units use single phase direct drive blower motors with a run capacitor Figure 3 shows th...

Страница 6: ...ions Each stage of the 208 230 electric heat is protected by a primary high temperature limit Each stage uses the same style of limit The primary limit is wired in series with a heat element When either limit opens the corre sponding heat element is de energized All other heating elements remain energized The primary high temperature limit opens at 150_F 5_F 65 5_C 2 8_C on a temperature rise and ...

Страница 7: ...W 1 Btuh Amps Circuit 1 Circuit 2 Circuit 1 Circuit 2 5 kW ECB26 5 99M64 Terminal Block ECB26 5CB 99M65 Ci it B k 208 3 8 12 800 1 6 19 6 30 ECB26 5CB 99M65 Circuit Breaker 220 4 2 14 300 1 5 22 3 30 230 4 6 15 700 1 5 22 3 30 240 5 0 17 100 1 5 22 3 30 7 5 kW ECB26 7 99M66 Terminal Block ECB26 7CB 99M67 Ci it B k 208 5 6 19 200 1 6 28 7 45 ECB26 7CB 99M67 Circuit Breaker 220 6 3 21500 1 5 32 8 45...

Страница 8: ...l Load A 2 Minimum Circuit Ampacity 3 Maximum Overcurrent Protection Volt kW 1 Btuh Amps Circuit 1 Circuit 2 Circuit 1 Circuit 2 5 kW ECB26 5 99M64 Terminal Block C 26 C 99 6 C 208 3 8 12 800 1 9 20 0 30 ECB26 5CB 99M65 Circuit Breaker 220 4 2 14 300 1 8 22 6 30 230 4 6 15 700 1 8 22 6 30 240 5 0 17 100 1 8 22 6 30 7 5 kW ECB26 7 99M66 Terminal Block C 26 C 99 6 C 208 5 6 19 200 1 9 29 0 45 ECB26 ...

Страница 9: ...l Load Amps 2 Minimum Circuit Ampacity 3 Maximum Overcurrent Protection Volt kW 1 Btuh Amps 240V Circuit 1 Circuit 2 Circuit 1 Circuit 2 5 kW ECB26 5 99M64 Terminal Block C C C 208 3 8 12 800 4 1 22 2 30 ECB26 5CB 99M65 Circuit Breaker 220 4 2 14 300 3 9 24 7 30 230 4 6 15 700 3 9 24 7 30 240 5 0 17 100 3 9 24 7 30 7 5 kW ECB26 7 99M66 Terminal Block C 26 C 99 6 C 208 5 6 19 200 4 1 31 2 45 ECB26 ...

Страница 10: ...cation Set unit so that it is level Connect return and supply air plenums as re quired using sheet metal screws 4 Install units that have no return air plenum on a stand that is at least 14 from the floor This will allow proper air return FIGURE 6 Upflow Configuration HORIZONTAL DRAIN PAN Remove for best upflow performance UPFLOW DRAIN PAN UPFLOW DRAIN CONNECTIONS Both sides use on side or other H...

Страница 11: ...ne assembly from the air handler 4 Remove the drain plugs from back of horizontal drain pan and reinstall in the front holes 5 Remove two screws and blowoff prevention bracket BP BRACKET in figure 10 Rotate the bracket 180º and reinstall using the same screws 6 Move horizontal drain pan to the opposite side of the coil Plugged drain holes will now be toward the back of the unit see figure 11 7 Re ...

Страница 12: ...drain 4 Install a 3 trap in both the primary and secondary drain lines as close to the unit as practical see figure 13 Make sure the top of the trap is below the connection to the drain pan to allow complete drainage of the pan FIGURE 13 Typical Condensate Drain Connection AIR HANDLER DRAIN CONNECTION DRAIN LINE ANTI SIPHON AIR VENT DRAIN TRAP Secondary Drain Not Shown 3 Min 1 Min 12 Max DRAIN PAN...

Страница 13: ...UTO or ON and move the system selection switch to COOL Adjust the thermostat to a setting far enough below room temperature to bring on the compressor Compressor will start and cycle on de mand from the thermostat After a 30 second time delay approximate the indoor blower will energize 2 The refrigerant circuit is charged with R 22 or R 410 refrigerant See condensing unit rating plate for cor rect...

Страница 14: ...nels before operating Failure to do so can result in death or electrical shock 1 Disconnect all power supplies 2 Remove the air handler access panel 3 Locate pin number 2 on the blower relay Two black wires are connected to this terminal pin One connects to pin number 5 on the blower relay one connects to an inline splice connecting to a red or blue wire 4 Remove the wire going to the 4 pin blower...

Страница 15: ...LIMIT SWITCH 1 LIMIT SWITCH 2 HE3 HE4 LIMIT SWITCH 3 LIMIT SWITCH 4 14 Y L2 14 BK L1 208V 240V COM 24V 24 C 4 3 1 2 H H HE1 HE2 HEATER ELEMENTS USED 5KW HE1 7 5 10KW HE1 HE2 15KW HE1 HE2 HE3 20KW HE1 HE2 HE3 HE4 4 1 3 8 9 7 6 6 A ECB26UH ECBX26UH SEQUENCE OF OPERATION FIRST STAGE HEAT 1 Line voltage is routed to transformer and blower relay 2 24VAC is supplied to indoor thermostat and electric hea...

Отзывы: