BLOWER DATA

80UHG2-45, 80UHG2-60 AND 80UHG2-75 BLOWER PERFORMANCE

External Static

Air Volume at Various Blower Speeds

External Static

Pressure

High

MediumĆHigh

MediumĆLow

Low

in. w.g.

Pa

cfm

L/s

cfm

L/s

cfm

L/s

cfm

L/s

0

0

1270

600

980

460

770

365

570

270

.05

12

1245

590

975

460

770

365

565

265

.10

25

1220

575

975

460

770

365

565

265

.15

37

1195

565

965

455

765

360

560

265

.20

50

1170

550

960

455

760

360

560

265

.25

62

1140

540

950

450

760

360

555

260

.30

75

1110

525

940

445

760

360

550

260

.40

100

1060

500

910

430

750

355

545

255

.50

125

990

465

880

415

740

350

540

255

.60

150

900

425

810

380

690

325

530

250

.70

175

800

380

740

350

630

295

520

245

NOTE Ċ All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished) in place. Also see Filter Air Resistance table

80UHG3-60 AND 80UHG3-75 BLOWER PERFORMANCE

External Static

Air Volume at Various Blower Speeds

External Static

Pressure

High

MediumĆHigh

MediumĆLow

Low

in. w.g.

Pa

cfm

L/s

cfm

L/s

cfm

L/s

cfm

L/s

0

0

1425

670

1240

585

1000

470

800

380

.05

12

1415

670

1230

580

995

470

800

380

.10

25

1400

660

1220

575

990

465

795

375

.15

37

1385

655

1200

565

985

465

795

375

.20

50

1370

645

1180

555

980

460

790

375

.25

62

1350

635

1160

545

970

460

780

370

.30

75

1330

630

1140

540

955

450

770

365

.40

100

1280

605

1095

515

925

435

750

355

.50

125

1210

570

1040

490

900

425

720

340

.60

150

1135

535

985

465

860

405

680

320

.70

175

1070

505

920

435

800

380

630

300

NOTE Ċ All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished) in place. Also see Filter Air Resistance table

80UHG4-75, 80UHG3/4-100 AND 80UHG3/4-120 BLOWER PERFORMANCE

External Static

Air Volume at Various Blower Speeds

External Static

Pressure

High

MediumĆHigh

Medium

MediumĆLow

Low

in. w.g.

Pa

cfm

L/s

cfm

L/s

cfm

L/s

cfm

L/s

cfm

L/s

0

0

1830

865

1600

755

1325

625

1070

505

880

415

.05

12

1815

855

1585

750

1320

625

1070

505

880

415

.10

25

1800

850

1570

740

1315

620

1070

505

880

415

.15

37

1875

885

1550

730

1310

620

1065

505

875

415

.20

50

1750

825

1530

720

1300

615

1060

500

875

415

.25

62

1725

815

1515

715

1290

610

1050

495

870

410

.30

75

1700

800

1500

710

1275

600

1040

490

870

410

.40

100

1650

780

1460

690

1245

590

1020

480

860

405

.50

125

1600

755

1420

670

1210

570

1000

470

840

395

.60

150

1550

730

1380

650

1170

550

980

460

820

385

.70

175

1480

700

1330

630

1130

535

960

455

790

375

NOTE Ċ All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished) in place. Also see Filter Air Resistance table

Содержание 80UHG Series

Страница 1: ...itrogen Oxides NOx Standards and California Sea8 sonal Efficiency requirements All units use a redundant gas valve to assure safety shut off as required by A G A or C G A Units may be installed in upf...

Страница 2: ...46J66 15 lbs 8 kg SPECIFICATIONS Model No 80UHG3 4 X 100 80UHG4 5 X 100 80UHG3 4 X 120 80UHG4 5 X 120 Input Btuh kW 100 000 29 3 120 000 35 2 Output Btuh kW 82 000 24 0 98 400 28 8 A F U E 80 1 80 0...

Страница 3: ...375 20 50 1370 645 1180 555 980 460 790 375 25 62 1350 635 1160 545 970 460 780 370 30 75 1330 630 1140 540 955 450 770 365 40 100 1280 605 1095 515 925 435 750 355 50 125 1210 570 1040 490 900 425 72...

Страница 4: ...lace Also see Filter Air Resistance table FILTER AIR RESISTANCE cfm L s in w g Pa 0 0 0 00 0 200 95 0 01 2 400 185 0 03 7 600 280 0 04 10 800 375 0 06 15 1000 470 0 09 22 1200 560 0 12 30 1400 655 0 1...

Страница 5: ...BOX SECONDARY LIMITS FRONT ACCESS PANEL DOOR INTERLOCK SWITCH CONTROL BOARD TRANSFORMER PROVE SWITCH 80UHG PARTS IDENTIFICATION FIGURE 2 HEAT EXCHANGER COMBUSTION AIR INDUCER MANIFOLD ROLLOUT SWITCH...

Страница 6: ...protect the furnace s electronic controls Precautions will help to avoid control exposure to electrostatic dis charge by putting the furnace the control and the technician at the same electrostatic po...

Страница 7: ...be open the combustion air inducer is energized When the differ8 ential in the prove switch is great enough the prove switch closes and a 15 second pre purge begins If the prove switch is not proven...

Страница 8: ...ed OR Pressure switch closed prior to activation of combustion air blower ALTERNATING SLOW FLASH ALTERNATING SLOW FLASH Watchguard burners fail to ignite SLOW FLASH OFF Flame sensed without gas valve...

Страница 9: ...nal is sensed NOTE The 80UHG furnace contains electronic components that are polarity sensitive Make sure that the furnace is wired correctly and is properly grounded PARK TERMINAL DESIGNATIONS COOL H...

Страница 10: ...ts If the primary or secondary heating limits open the control de energizes the main gas valve and combustion air blower while the indoor blower remains en ergized When the limit automatically resets...

Страница 11: ...is a heating demand On Flash Primary or Secondary Limit Switch Open Auto Reset Switch Flash Off Pressure Switch Watchguard pressure switch opened during operation Alternate Flash Alternate Flash Watch...

Страница 12: ...P 1 2 1 3 1 4 5MFD 370V 5MFD 370V 7 5MFD 370V 80UHG5 6 80UHG4 80UHG4 5 1 2 7 5MFD 370V 3 4 40MFD 370V 3 4 40MFD 370V FIGURE 11 SUPPLY AIR BLOWER AND SECONDARY LIMITS Front Bottom Right Left Top Back B...

Страница 13: ...t point will be printed on the limit Two limits are supplied in each furnace 80UHG3 80UHG4 and 80UHG4 5 model units built prior to Apri 1999 will have one each of style shown in figures 13 and 14 If s...

Страница 14: ...ODEL SHOWN FIGURE 18 SPARK ELECTRODE SPARK ELECTRODE TO BURNER GAP 80UHG 1 MODEL SHOWN BURNER FLAME SENSOR TO BURNER GAP BURNER FLAME SENSOR SPARK ELECTRODE 5 16 in 7 mm 5 16 in 7 mm 13 Combustion Air...

Страница 15: ...ard 80UHG 1 units are equipped with a direct spark igni tion system Do not attempt to light manually 1 STOP Read the safety information at the beginning of this section 2 Set thermostat to lowest sett...

Страница 16: ...to check for gas leaks D Testing Gas Supply Pressure When testing supply gas pressure connect test gauge to inlet pressure tap field provided See figure 20 Check gas line pressure with unit firing at...

Страница 17: ...roamp DC meter is needed to check the flame signal on the ignition control Flame microamp signal is an electrical current which passes from the furnace control through the sensor during unit opera tio...

Страница 18: ...mperature is too low decrease blower speed If temperature is too high first check the firing rate Provided the firing rate is acceptable in crease blower speed to reduce temperature To change blower s...

Страница 19: ...in the heat exchanger clean ing is not recommended Removal is for inspection only NOTE Use papers or protective covering in front of fur nace while cleaning furnace To clean burners 1 Remove screws ho...

Страница 20: ...ting in gas leaks fire or explosion C Supply Air Blower 1 Check and clean blower wheel 2 Motors used on the Lennox 80UHG series units are permanently lubricated and need no further lu brication D Flue...

Страница 21: ...n control energizes the combustion air inducer B6 When the combustion air inducer nears full speed combustion air prove switch S18 closes Switch must close within 2 1 2 minutes or control goes into 5...

Страница 22: ...OR BLOWER WITH DELAY OFF DIAG CODE 1 OFF 2 FLASHING C A B PRESSURE SWITCH OPEN IS 5 MINUTE RESET PERIOD COMPLETE INDOOR AIR BLOWER ON Fixed 45 second delay PRIMARY SECONDARY LIMITS MONITORED IN HEAT C...

Страница 23: ...RMOSTAT CONTROL ENERGIZES SYSTEM FAN AT HEATING SPEED ACC TERMINAL ENERGIZED THERMOSTAT CALLS FOR HEAT LED Slow flash rate REMAINS UNCHANGED THROUGHOUT SEQUENCE THERMOSTAT CALLS FOR COOLING SYSTEM FAN...

Страница 24: ...hguard Pressure Switch delay Once S18 closes a 15 second pre purge follows 4 SureLight control energizes ignitor A 20 second warm up period begins 5 Gas valve opens for a 4 second trial for ignition i...

Страница 25: ...AS VALVE OFF COMBUSTION AIR INDUCER ON INDOOR BLOWER ON HEATING SPEED LED 1 SLOW FLASH LED 2 OFF GAS VALVE OFF COMBUSTION AIR INDUCER OFF INDOOR BLOWER OFF WITH DELAY LED 1 OFF LED 2 SLOW FLASH Sequen...

Страница 26: ...CONTROL FAILED TO SENSE FLAME FOR FIVE CONSECUTIVE TRIES DURING A SINGLE HEAT DEMAND WATCHGUARD MODE GAS VALVE OFF COMBUSTION AIR INDUCER OFF INDOOR BLOWER OFF WITH DELAY LEDs SIGNAL WATCHGUARD FAILU...

Страница 27: ...D SLOW FLASH RATE REMAINS UNCHANGED THROUGHOUT COOLING CYCLE THERMOSTAT CALLS FOR COOLING COMPRESSOR CONTACTOR AND SYSTEM FAN ENERGIZED WITH 0 SECOND DELAY COOLING SPEED EAC H TERM ENERGIZED COMPRESSO...

Страница 28: ...THERMOSTAT CALLS FOR HEAT W THERMOSTAT CALLS FOR COOLING THERMOSTAT OPENS SYSTEM FAN SWITCHED TO COOL H SPEED EAC H TERM REMAINS ON THERMOSTAT OPENS MANUAL FAN SELECTION MADE AT THERMOSTAT CONTROL G...

Страница 29: ...he roll out switch by pushing the top button ACTION 2 Determine the cause of the roll out switch activation before leaving furnace code 1 2 2 Roll out switch failure ACTION 1 Check continuity across r...

Страница 30: ...WER DOES NOT ENERGIZE Condition Possible Cause Corrective Action Comments 2 1 Unit operates with a cooling or con tinuous fan demand Combustion air inducer will not start with a Heating demand Diagnos...

Страница 31: ...e pressure switch failure code 2 5 minutes after heating demand 3 1 2 Pressure switch does not close due to obstructions in the pressure lines ACTION 1 Remove any obstructions from the the pressure li...

Страница 32: ...ch code LED 1 Off LED 2 Slow Flash 5 1 1 Low pressure differential at the pres sure switch ACTION 1 Check for restricted exhaust vent Remove all blockage ACTION 2 Check for proper vent sizing See inst...

Страница 33: ...3 4 Burners are not properly located in the burner box ACTION 1 Check that the burners are firing into the center of the heat exchanger openings Cor rect the location of the burners if necessary 5 4...

Страница 34: ...Action Comments 7 0 Indoor blower fails to operate in continuous fan cooling or heating mode 7 1 1 Miswiring of furnace or improper con nections at control or indoor blower motor ACTION 1 Correct wir...