TABLE 4

Multiple Appliance for Interior and Exterior Masonry Chimney

Type B Double Wall Vent Connectors Serving a Single 80AF1UH, ML180UH, EL280UH or SL280UH Furnace

with Masonry Chimney Vent Adapter Kit and One or More Drafthood−Equipped Appliances

Vent

Height

H

(ft)

Connector

Rise

R

(ft)

Type B Double Wall Connector Diameter − (inches)

6 in.

7 in.

8 in.

Appliance  Input Rate in Thousands of Btu per Hour

NAT
Max

NAT
Max

NAT
Max

6

1
2
3

101
124
143

141
173
203

201
232
270

8

1
2
3

105
127
145

148
179
206

210
240
276

10

1
2
3

108
129
148

153
184
209

216
247
281

15

1
2
3

114

134
153

164
192
215

229
260
292

20

1
2
3

119

138
157

173
199
222

239
270
301

30

1
2
3

127
145
163

187
209
233

255
287
317

35

1
2
3

131
149
167

194
216
240

265
297
332

TABLE 5

Multiple Appliance for Interior and Exterior Masonry Chimney

MASONRY CHIMNEY INTERNAL AREA

Height

H

(ft)

Minimum Internal Area of Chimney (Square Inches)

38

50

63

Combined Appliance Input Rating in Thousands of Btu Per Hour

NAT

+NAT

NAT

+NAT

NAT

+NAT

6

103

143

188

8

119

163

218

10

131

177

236

15

152

212

283

20

172

243

325

30

198

278

381

35

NR

291

401

NR − Not recommended for vent configuration.

Содержание 18M7901

Страница 1: ...80AF1UH ML180UH EL280UH and SL280UH units installed in masonry chimney vent applications in accordance with limitations set by NFPA 54 and the International Mechanical Code The included vent tables a...

Страница 2: ...10 F 12 C Pittsburgh 1 F 17 C Salt Lake City 3 F 16 C St Louis 2 F 17 C Requirements The room temperature surrounding the furnace and vent connectors must be at least 60 F 16 C The space surrounding t...

Страница 3: ...nector per table 3 and figure 2 when a single appliance is being vented into an interior masonry chimney Size the chimney and vent connector per tables 4 and 5 and figure 3 when using an interior or e...

Страница 4: ...le Lined Masonry Chimney Serving a Single 80AF1UH ML180UH EL280UH or SL280UH Furnace Equipped with Vent Adapter Kit and One or More Drafthood Equipped Appliances Typical Application Shown FIGURE 3 TIL...

Страница 5: ...70 8 1 2 3 105 127 145 148 179 206 210 240 276 10 1 2 3 108 129 148 153 184 209 216 247 281 15 1 2 3 114 134 153 164 192 215 229 260 292 20 1 2 3 119 138 157 173 199 222 239 270 301 30 1 2 3 127 145 1...

Страница 6: ...sing mortar or brick must be replaced Tile liner and top seal must be in good condition If necessary make repairs All debris mortar tile fuel oil residue etc must be removed from chimney clean out Til...

Страница 7: ...g sheet metal screws to firmly secure the vent adapter assembly to the round collar of the unit flue transition Drive one self drilling screw through the front and one through each side of the vent ad...

Страница 8: ...al setting 11 Test the furnace for proper draft and spillage a Inspect the venting system for proper size and horizontal pitch Determine that there is no blockage restriction leakage corrosion or othe...

Отзывы: