INSTALLATION INSTRUCTIONS FOR LIQUID CHARGE COMPENSATOR KIT (13U57; 614407-01

USED ON LGH/LCH 036, 048, 060, 072, 074 ROOFTOP UNITS

Litho U.S.A.

507559-01
7/2015
Supersedes 6/2015

2015

LIQUID CHARGE

COMPENSATOR KIT

PACKAGED UNITS KITS
AND ACCESSORIES

Shipping and Packing List

Package 1 of 1 contains:

 1- Liquid charge compensator

 1- Copper tube 1/4”

 1- Copper tube 3/8”

 1- Template

 2- Straps

 1- Grommet (used on 036 & 048 units only)

 4- Screws

Application

The liquid charge compensator kit is used to maintain

system pressures when compressors start after long

extended periods without a cooling demand.

CAUTION

Danger of sharp metallic edges. Can cause injury.
Take care and wear protective clothing when
servicing unit to avoid accidental contact with
sharp edges.

Installation

1- Disconnect all power to unit.

2- Use an approved method of recovery to remove

refrigerant from the system.

IMPORTANT

The Clean Air Act of 1990 bans the intentional vent­
ing of refrigerant (CFC's and HCFC's) as of July 1,
1992. Approved methods of recovery, recycling or
reclaiming must be followed. Fines and/or incar­
ceration may be levied for non-compliance.

3- Remove the compressor access panel, corner

mullion, fan guard and fan blades.

4- Unbraze and cut the liquid line as shown in figure 1.

WARNING

Improper installation, adjustment, alteration, ser­
vice or maintenance can cause property damage,
personal injury or loss of life. Installation and ser­
vice must be performed by a licensed professional
HVAC installer or equivalent, service agency, or the
gas supplier

REMOVE SECTION OF LIQUID LINE

FIGURE 1

13-1/4”

CUT THE

LIQUID LINE

UNBRAZE

THE LIQUID

LINE

COMPRESSOR

SUCTION LINE

DISCHARGE

LINE

Содержание 13U57

Страница 1: ...l contact with sharp edges Installation 1 Disconnect all power to unit 2 Use an approved method of recovery to remove refrigerant from the system IMPORTANT The Clean Air Act of 1990 bans the intention...

Страница 2: ...048 Unit Only Cut a hole in the panel as shown in figure 2 Install the grommet provided CUT HOLE IN PANEL 036 048 UNITS ONLY FIGURE 2 VIEW A 16 1 2 1 3 4 CUT HOLE CUT A HOLE APPROXIMATELY HERE SEE VI...

Страница 3: ...id line See figure 3 Month Dec Jan A Feb B Mar C etc 5 6 1 4 L Year 2014 Serial Number Example 7 Fit the shortened liquid line back in place but do NOT braze into place REMOVE 4 FROM LIQUID LINE UNITS...

Страница 4: ...4 COPPER TUBE ORIENT HOLE IN TUBING TO THE RIGHT 9 Insert the template through the fan orifice and onto the back side of the control area See figure 5 Mark the four screw holes 10 Use the provided str...

Страница 5: ...Page 5 INSTALL COMPENSATOR AND TUBING FIGURE 6 ROUTE TUBING THROUGH RECTANGULAR OPENING OR HOLE CUT PREVIOUSLY SECURE COMPENSATOR TO PANEL WITH STRAPS AND TWO SCREWS ON EACH SIDE STRAPS...

Страница 6: ...ing into the hole on the liquid line See figure 8 IMPORTANT Make sure the tubing is inserted just inside the liquid line do not block refrigerant flow by inserting the line too far ROUTE TUBING FIGURE...

Страница 7: ...oxygen to pressurize the refrigerant system Oxygen and oil can combine to cause an explosion CAUTION Danger of equipment damage Avoid deep vacuum operation Do not use com pressors to evacuate a syste...

Страница 8: ...t Controller Installation and Set Up Guide provided with each unit for more detail 4 Connect the USB flash drive to the USB port on the lower left side of the Unit Controller 5 Navigate to the followi...

Отзывы: