NETWORK REPEATER KIT

CONTROLS

INSTALLATION INSTRUCTIONS FOR NETWORK REPEATER (11W30; LB−113402)

USED WITH L CONNECTION

®

 NETWORK

Shipping and Packing List

Package 1 of 1 contains:

 1− Repeater

 1− Wiring diagram

 1− 12VDC Power supply

Check items for shipping damage. Receiving party should
contact last carrier immediately if shipping damage is found.

These instructions are intended as a general guide and do
not supersede local codes in any way. Authorities having
jurisdiction should be consulted before installation.

Application

The Network Repeater is required when communication
cable length exceeds 4000 ft. (1219m) or when cable is
run between buildings.

WARNING

Improper installation, adjustment, alteration, ser-
vice or maintenance can cause property damage,
personal injury or loss of life. Installation and ser-
vice must be performed by a qualified installer or
service agency.

CAUTION

Danger of sharp metallic edges. Can cause injury.
Take care when servicing unit to avoid accidental
contact with sharp edges.

Installation

Install repeater in unit or mechanical room with access to
a 120V outlet. When used between buildings, install a
repeater before the first controller on each building. Use
field provided DIN rail if desired.

Wiring

 1− Make communication wiring connections to repeater

as shown in figures 1 and 2.

 2− Plug power source into a 120V outlet and connect to

the repeater as shown in figures 1 and 2.

 3− Affix wiring diagram on inside unit panel near other

wiring diagrams.

FIGURE 1

NETWORK REPEATER

12VDC

POWER IN

SysBus or

ZoneBus

SysBus or

ZoneBus

FIGURE 2

REPEATER WIRING

SysBus or

ZoneBus

G

D−

D+

G

D−

D+

TOP VIEW

V+

V−

Black

Red

SysBus or

ZoneBus

Black

Red

Black

Red

12VDC

From

Power

Supply