iComfort Wi-Fi
®
Flex Thermostat / Page 16
FEATURES - ICOMFORT WI-FI® FLEX THERMOSTAT
INSTALLER SETTINGS
ADJUST SYSTEM DEVICES SCREEN
Use the up / down arrows to scroll through available
system devices.
Touch any line and touch
Edit
to adjust a device’s
setting. Touch
resetAll
to reset all system devices.
Bold
indicates default setting.
NOTE - “Reset ALL” resets all devices back to original
factory default settings. Each individual device can be
also reset to factory settings on the selected equipment
screen.
Equipment Name - Press “edit” button to change
equipment name, use keyboard tool to change.
System
•
Equipment Name (Keyboard tool)
•
Filter 1 Timer Selection (
Calendar
or Run Time
)
•
Filter 2 Timer Selection (
Calendar
or Run Time
)
•
UV Bulb Timer Selection (
Calendar
or Run Time
)
•
Humidifier Pad Timer Selection (
Calendar
or Run Time
)
•
PureAir Timer Selection (
Calendar
or Run Time
)
•
Smooth Setback Recovery (
Enabled
/Disabled
)
•
Gas Heat Control Mode (
Staged
)
•
Number of Gas Heating Stages (
1, 2, 3, or 4,
default is
4
)
Staged
• Auto Changeover – Temp Deadband (
3 to 9°F,
default is
3°F
)
•
Max. Heat Setpoint (
40 to 90°F, default is
90°F
)
•
Min. Cool Setpoint (
60 to 99°F, default is
60°F
)
•
Heat Cool Stages Locked In (
Enabled/
Disabled
)
•
1st Stage Differential (
0.5 to 3.0°F, default is
1.0°F
)
•
2nd and 3rd Stage Differential (
0.5 to 8.0°F, default
is
0.5°F
)
•
Staged Delay Timers (
Enabled
/Disabled
)
•
2nd and 3rd Stage Delay (
5 to 120 min. in 5 min.
increments, default is
20 min.
)
Number of heating stages shown depends on equipment
installed. Electric heat is staged at every 2 elements.
• Balance Point Control (
Enabled/
Disabled
)
•
High Balance Point (
–17 to 75°F, default is
50°F
)
• Low Balance Point (
–20 to 72°F, default is
25°F
)
Heat Pump
•
Min Dehumidification Setpoint (
40 to 60°F, default is
40°F
)
•
Humidification Control Mode (
Display Only
,
Precision, Precision Dew Point Control, Basic, Basic
Dew Point Control
)
• Dew Point Adjustment (
–15 to 15°F, default is
0
)
•
Max. Humidification Setpoint (
15 to 45% RH, default
is
45%
)
•
Auto Changeover Humidification Deadband (
5 to 10%
RH, default is
5%
)
Humidifier
•
Outdoor Temperature Reading Calibration (
–10 to
10°F, default is
0
)
•
HP Heating Lockout Time (
60 to 240 min., default is
120 min.
)
D. Fuel
•
Reset Button (resets system back to factory default
settings)
NOTE - Depending on type of system (conventional
heating/cooling or heat pump system) and optional
equipment not all system settings will be displayed.
Air Conditioner or Heat Pump
•
Equipment Name (Keyboard tool)
•
Compressor Short Cycle Delay (
60 to 300 sec.,
default is
300 sec.
)
•
Defrost Termination Temp (Heat Pump only) (
50 to
100°F, default is
50°F
)
•
Compressor Shift Delay (Heat Pump only) (
On/Off,
default is
On
)