background image

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

6

Step 3.  Keep the combustion air damper and 

the  by-pass  damper  opened  for  10  minutes 

before closing it. It will ensure sufficient tem-

peratures for combustor light-off. 
To refuel the Villa Vista™ fireplace when the 

unit is still hot (Some burning fuel remaining 

or a glowing combustor)
Step 1.  Open  the  by-pass  and  air  controls 

fully. 
Step 2.  Open the door approximately 1 inch, 

wait five seconds until the draft is stable and 

then open it completely. Load the fuel, close 

the door and by-pass (temperatures within the 

firebox should be enough to maintain catalytic 

operation)

Smoking – Causes and Troubleshooting

To  reduce  the  likelihood  of  smoking  when 

opening the doors, set the air damper to the 

“accelerated  combustion”  position  and  open 

the by-pass damper before opening the doors. 

Your fireplace has been designed and tested to 

provide  smoke  free  operation.  Occasionally, 

there may be a small amount of smoking upon 

lighting the fire, until the chimney heats up but 

this should not continue.  If the fireplace does 

continue to smoke, it is probably for one of the 

following reasons:

1.  The door is partly open

Open the door fully.

2. Negative pressure in the house

As the fire burns, air goes up the chimney.  

This air must be replaced through leakage 

into the house or through the outside air 

duct.  When operating the Villa Vista fire-

place, open a nearby window temporarily 

to check if there is adequate air replace-

ment.

3. Fans operating (e.g. range hood)

These fans draw air out of the house and 

may actually cause a negative pressure in 

the house.  Turn off all fans and open a 

nearby window to determine if this is the 

cause of the problem.

4. Wet wood 

Wet or tarred wood will smoulder and smoke 

instead of burn properly.

5. Dirty or blocked chimney

Check to make sure the chimney is clear 

and reasonably clean.

6. Chimney not long enough

The minimum chimney height is 12 feet, not 

including the fireplace height.  The chimney 

must extend at least 3 feet (915 mm) above 

its point of contact with the roof and at least 

2 feet (610 mm) higher than any roof or 

wall within 10 feet (3 m) of it.  

7. Poor chimney draft

With  no  fire,  there  should  be  sufficient 

draft to exhaust cigarette smoke introduced 

under the baffle.  Chimneys installed against 

an  outside  wall  without  protection  may 

generate  back  draft  problems  which  will 

cause start-up problems.  To prevent this, 

open a nearby window, roll up a piece of 

paper and light it. 

Then, hold it in the upper part of the firebox 

to warm up the chimney.  Wait until the draft 

is sufficient, then start the fire.

Important Notes

1.  Do not block the hot air vents of the fire-

place as this will cause the fireplace to 

overheat.

2.  Never start a fire using gasoline, kero-

sene, charcoal lighter fluid or any other 

combustible liquid.

3.  Do not burn coal.  The sulphur in coal will 

corrode the firebox.

4.  Do  not  burn  driftwood  which  has  been 

in the ocean or salt water.  The salt will 

corrode the firebox and chimney.

5.  Do not operate the unit with the door partly 

open since this may cause smoke to be 

drawn into the room.

6.  Do not burn wood in the area in front of 

the log retainers.

7.  Do not abuse the unit by burning paper, 

or cardboard or construction material 

such  as  pressed  wood,  plywood  or 

lumber.

8.  Do not allow the wood to smoulder or burn 

without  flame,  since  this  will  produce 

excessive creosote in the unit.

MAINTAINING YOUR FIREPLACE

Creosote

When wood is burned slowly, it produces tar 

and other organic vapors which combine with 

expelled moisture to form a black deposit called 

creosote which accumulates on the flue lining.  

When ignited, this creosote makes an extremely 

hot fire.  If the creosote accumulation is large, 

a creosote fire in the chimney can damage the 

chimney and overheat the surrounding wood 

framing.  Creosote formation in a chimney can 

be minimized by making small hot fires rather 

than slow burning, smouldering fires and by 

proper refuelling techniques.

Chimney Maintenance

Regular chimney inspection and maintenance 

combined with proper operation will prevent 

chimney fires. Keep your chimney clean.  Do not 

allow more than 1/16" creosote build up in your 

chimney.  The amount of creosote will depend 

on variables such as frequency of use and type 

of fire.  We recommend that you:

1.  Initially inspect the chimney system weekly.  

From this, you will learn how often it will 

be necessary to clean your chimney.

2.  Have your chimney cleaned by a qualified 

chimney  sweep.    If  you  wish  to  clean  it 

yourself, we recommend using a stiff plastic 

or non-metallic brush.  If a metal brush is 

used, its size should be slightly smaller than 

the flue to avoid damaging the chimney.  

Do not use a brush that will scratch the 

stainless steel interior of the chimney.

3.  Do not expect chemical cleaners to keep 

your chimney clean.  The rain cap can be 

removed for inspection and/or cleaning of 

the chimney.  Using gloves, firmly grip the 

lower portion of the rain cap.  Turn the cap 

1/8 of a turn counter-clockwise and lift it 

off the chimney.

Dealing With A Chimney Fire

Regular chimney maintenance and inspection 

can prevent chimney fires.  If you have a chimney 

fire, follow these steps:

1.  Close the fireplace doors and the combus-

tion air damper.

2.  Alert your family of the possible danger.

3.  If  you  require  assistance,  alert  your  fire 

department.

4.  If possible, use a dry chemical fire extin-

guisher, baking soda or sand to control the 

fire.  Do not use water as it may cause a 

dangerous steam explosion.

5.  Check outside to ensure that sparks and hot 

embers coming out of the chimney are not 

igniting the roof.

6.  Do not use the fireplace again until your 

chimney and fireplace have been inspected 

by  a  qualified  chimney  sweep  or  a  Fire 

Department Inspector.

Catalytic Combustor

The Villa Vista™ fireplace is designed with a 

catalytic combustor which will reduce pollution 

emissions and creosote build up while improv-

ing thermal efficiency.  In order to optimize and 

maintain the combustor performance, it is im-

portant to visually check the combustor at least 

3 times during the heating season to determine 

if physical degradation has occurred.

Catalytic combustors require little maintenance.  

Cleaning the combustor once a year, preferably 

when your flue system is serviced, is sufficient 

for most users.  

       WARNING 

To prevent damage to your com-

bustor, do not:

• 

 

Drop the combustor (which is 

fragile compared to the rest 

of the unit – so handle with 

care)

• 

 

Run water or compressed air 

through the combustor

• 

 

Try  to  clean  the  combustor 

with any sharp tool

Содержание Villa Vista

Страница 1: ... same room as appliance Wood Burning Fireplaces P N 850 028M REV J 11 2008 Villa Vista VILLA VISTA This installation manual will enable you to obtain a safe efficient and dependable installation of your fireplace system Please read and understand these instructions before beginning your installation Donotalterormodifythefireplaceoritscomponentsunderanycircum stances Anymodificationoralterationofth...

Страница 2: ...l systems generalconstructionconditions inadequate chimney heights adverse wind conditions and or unusualenvironmentalfactorsor conditions beyond our control WARNING The Villa Vista fireplace must be installed with an outside air kitintake whichisincludedwith the fireplace WARNING THE FIREPLACE MUST BE OPER ATED WITH THE DOORS FULLY OPENEDORDOORSFULLYCLOSED IF THE DOORS ARE LEFT PARTLY OPENED GASA...

Страница 3: ...Multiple Terminations Page 20 Masonry Applications Page 21 Parts And Components List Page 22 Replacement Parts Page 25 Clearance To Combustible Page 25 Product Reference Information Page 26 THE FIREPLACE INTRODUCTION The Villa Vista fireplace is an energy efficient heat circulating close combustion fireplace using the catalytic technology You will receive a lifetime of comfort and enjoyment from y...

Страница 4: ...et off a smoke alarm located in the same room For this reason the room should be well ventilated for the first few fires Catalytic Combustor The Villa Vista fireplace is equipped with a catalytic combustor Unburned by products of the wood fire are burned at lower temperatures as they pass through the combustor resulting in less pollution reduced creosote and higher efficiency In order to have the ...

Страница 5: ...s includingchimney length and the moisture content of the wood This method of burning should be used only after operating the Villa Vista fireplace with the aircontrolopenedtoproduceahotfireforabout an hour Slow combustion can be used at night in order to reduce the heat output and prolong the burn The loading time will be between 6 10 hours Be aware that the glass will get dirty using this settin...

Страница 6: ...rs 7 Do not abuse the unit by burning paper or cardboard or construction material such as pressed wood plywood or lumber 8 Donotallowthewoodtosmoulderorburn without flame since this will produce excessive creosote in the unit MAINTAINING YOUR FIREPLACE Creosote When wood is burned slowly it produces tar and other organic vapors which combine with expelledmoisturetoformablackdepositcalled creosotew...

Страница 7: ...move the plug on the doortrapoftheashtrayusingglovesorapoker Sweep the ashes in the opening with a brush or any similar tool Reinstall the plug on the door trap and pull down the lever Refractory Replacement The intense heat of the fire will normally cause hairline cracks in the refractory These cracks canbeminimizedbypropercuringasdescribed in First Fires They will not normally dimin ish the effe...

Страница 8: ...e Figure 9 Figure 8 HINGE SCREWS GASKET ADJUSTEMENT SCREW DOOR HINGE SCREWS Figure 9 DO NOT USE CHEMICAL GLASS CLEANERS ON PAINTED SURFACES AS IT MAY CAUSE THE PAINT TO PEEL CAUTION DONOTALLOWWINDOWCLEANER TO GET IN CONTACT WITH DOOR GASKET OR PAINT ON FACADE OR DOOR ONCE CLOSED CONTACT OF GLASS CLEANER WITH THE FIREPLACE FACADE CAN PROVOKE PAINT PEELING OFF Gasket Replacement Remove the door from...

Страница 9: ...ith the house insulation material Cover the insula tion with drywall panels or any rigid material around the fireplace Hearth Extension Requirements The Villa Vista fireplace may be installed directly on a combustible floor The supplied safety metal strip must be positioned as fol lows One half under the front of the fireplace and the other half must extend on the floor over which the hearth exten...

Страница 10: ...nce From Back Spacer to Wall Figure 11 Framing Dimensions Notes Due to Lennox Hearth Products ongoing commitment to quality all specifications ratings and dimensions are subject to change without notice Allframingdimensionscalculatedfor1 2 dry wallatthefireplaceface Ifsheathingthechase or finishing with other thickness materials calculations will need to be made The fireplace must not be in contac...

Страница 11: ...ower lines etc A chase should be constructed and insulated just like any outside wall In a cold climate we recommend the base of the chase should also beinsulatedbetweenthesolidcontinuousfloor beneath the fireplace and the chase bottom Chase insulation in a cold climate installation is not required for safety Note Do not insulate the chase cavity with blown or fill type insulation materials Note L...

Страница 12: ...the unit 38 and a height of 54 from the base of the appliance see Figure 15 3 Non combustible materials such as brick stone or ceramic tile may project in front of and onto the fireplace facing see Figure 14 Mantel The mantel must be installed at least 54 1372 mm above the base of the fireplace see Figure 13 NOTE Mantel can be reduced to 48 1219 mm if the Clean Face Panel option is installed with ...

Страница 13: ...mm Maximum length See Figure 17 The height of the louver must be measured from the base of the Villa Vista fireplace to the middle point of the louver When installing the double outlet system the hotairoutletscanbeinstalledinthesameroom as the fireplace or one or both of the outlets can be installed in adjacent or upper rooms Installing the ducts at different elevations will tend to exhaust more h...

Страница 14: ...air ducts to a central heating system Malfunction of the heating system s fan will cause the furnace duct to overheat A furnace duct is only single wall and not double wall as is required for the Villa Vista fireplace hot air exhaust 7 Use only Lennox Hearth Products grills and components as described in this manual Othergrillsorregisters forexample maybe toorestrictiveandmayoverheatthefireplace o...

Страница 15: ... basement or garage 4 The air intake register should be installed where it is not likely to be blocked by snow or exposed to extreme wind and well away fromautomobileexhaustfumes gasmeters and other vents 5 Theductandregistermaybeinstalledabove or below floor level Outside Air Installation Make a 4 1 4 110 mm hole in the outside wall of the house at the chosen location From outside place the outsi...

Страница 16: ...he fireplace top collar Use H3805 ACBI7SBA or H3806 ACBI7SB30 3 A chimney venting a fireplace shall not vent any other appliance 4 The minimum chimney height is 12 feet 3 7 m In altitude add 18 450 mm to the chimney for every 2000 feet 600 m above sea level 5 All chimney installations must include at least one support The maximum chimney lengththatcanbesupportedbythefireplace is 20 feet 8m for ACB...

Страница 17: ...3 ACBI Every 20 feet and at the roof level installauniversalsupportfasteningthestrapsto the surrounding joists ASHT Install support as required see Chimney Support Installation Section on Page 20 4 Puttheroofflashinginplaceandsealthejoint between the roof and the flashing with roofing pitch seeFigures25and26 Forslopingroofs place the flashing under the upper shingles and on top of the lower shingl...

Страница 18: ... the offset 6 Continue with the regular installation Figure 27 FLASHING COLLAR CHIMNEY Starter Section Straps Support ACBI7RS Straps Chimney ACBI UNIVERSAL SUPPORT AC10SU After reaching the location requiring the elbow proceed as follows 1 Install the first elbow Turn it in the required direction ACBI To lock it in place turn 1 8 of a turn Fasten the straps attached to the elbow to the surrounding...

Страница 19: ...mm 12 1 2 318 mm 618 mm 24 1 4 241 mm 9 1 2 30 886 mm 13 1 4 337 mm 54 1 4 1378 mm 12 36 S2100 CHIMNEY 7 ELBOW DEVIATION LENGTH DEVIATION LENGTH DEVIATION LENGHT TWO LENGTHS BETWEEN ELBOWS ONE LENGTH BETWEEN ELBOWS 29 1 2 749 mm 10 1 4 260 mm 1391 mm 54 3 4 413 mm 18 1 4 75 1 2 1918 mm 3 76 mm 16 1 2 419 mm 8 527 mm 20 3 4 191 mm 7 1 2 24 813 mm 33 184 mm 7 1 4 15 1 2 394 mm 34 3 4 883 mm 45 635 m...

Страница 20: ...10mm CHIMNEY SUPPORT INSTALLATION Universal Roof Support This support has two possible uses 1 For ASHT it must be used on a roof to support the chimney 2 It may be used on a floor ceiling or roof above an offset to support the chimney above the offset 3 It may be used on a floor ceiling or roof above as a supplementary support when the chimney height exceeds 15 feet 4 6 m Table 6 gives maximum hei...

Страница 21: ...l drill a hole in the masonry chimney at 45 or 30 Note 45 offsets allowed in Canada only 3 Increase the size of the hole until a 45º or 30º Tubinox liner elbow can be easily slipped through 4 Slide the liner down from the top of the masonry chimney until you reach the hole level 5 Slip through the hole a 45 or 30 liner elbow and connect it to the liner 6 Add a small liner section to the liner elbo...

Страница 22: ...uver Kit DEL SOL Diamante Louver Kit DIAMANTE Fiori Louver Kit FIORI Luna Louver Kit LUNA Strada Louver Kit STRADA Panel for Clean Face Option BPCF Blower UZY5 Blower Motor Speed Control VRUW Rigid Firescreen BPZN Fireplace Model VILLA VISTA Approved Venting Components 7 Diameter Chimney Model ASHT S2100 HT6000 HT6103 or ACBI manufactured by Security Chimneys International only 7 Diameter Chimney ...

Страница 23: ...s are required if installing ACBI Chimney Outside Air Kit chimney 4 I D flex x 10 long insulation outside register and coupling ACZI H1967 Outside Air Coupler for AC Chimney 4 I D UACZI H3274 Supports Support Section 10 long ACBI7SL H3263 Universal Support AC10SU H3265 Roof Flashings 1 12 7 12 5 30 Adjustable ACBI7FAR H3276 8 12 12 12 30 45 Adjustable ACBI7FBR H3277 Flat Roof Flashing includes spa...

Страница 24: ...7RSM 7RSM Insulated Wall Radiation Shield 30 7RSMI30 7RSMI30 TUBINOX or PROJET SS Chimney For Relining a Masonry Chimney 7 Diameter Listed to ULC S635M JL 1777 and ULC S640M at 2100 F Description Cat Part No Length 6 7LL6 7LL6 Length 12 7LL12 7LL12 Length 24 7LL24 7LL24 Length 36 7LL36 7LL36 Length 48 7LL48 7LL48 Adjustable Length 7 to 11 7L7A 7L7A Split Base Tee 7LT 7LT Tee Cap 7TCS 7TCS Twist Lo...

Страница 25: ...ng clearances meet the minimum requirements for a safe installation Side wall 24 610 mm measured from the doors edge Ceiling 6 8 2032 mm measured from the base of the fireplace Fireplace enclosure Bottom 0 Side 0 to spacer Back 0 to spacer Top Do not fill the space above the fireplace with any material 7 feet measured from the base of the fireplace Chimney ASHT 2 50mm ACBI 1 25mm at ceiling roof l...

Страница 26: ... Products dealer please call 1 800 9 LENNOX Replacement parts See Page 25 for a complete replacement parts list Use only parts sup plied from the manufacturer Normally all parts should be ordered through your Lennox Hearth Products distributor or dealer Parts will be shipped at prevailing prices at time of order When ordering repair parts always give the following information 1 The model number of...

Отзывы: