background image

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

9

CHIMNEY 30

°

 OFFSET THROUGH FLOOR

OR CEILING

It may be necessary to assemble the chimney at
30

°

 when passing through the floor or ceiling

area. Use the F8FS30-2 firestop spacer as shown
in 

Figures 21 and 22. Support the chimney at

floor or ceiling penetration with a FTF8 stabi-
lizer if distance of chimney below ceiling is 10'
or more. Maintain 2" minimum air space to
combustibles from chimney sections.

Figure 21

Figure 22

Step 4.

 Note: Chimney sections are constructed

with a unique locking tab design, which en-
sures an immediate, tight assembly between
sections. Plan your chimney requirements care-
fully before assembly as chimney is difficult to
disassemble after installation. If disassembled,
the tabs might become damaged. Be certain
tabs are properly formed to ensure locking
tabs engage properly.

Security's FTF8 and FTF10 chimney systems
are two piece chimneys, which snap together
from the fireplace up. Start with the inner flue
section. With the lanced end up, snap lock it into
the matching collar on top of the fireplace.

At all subsequent joints, the upper flue section
fits into the preceding flue section. Each piece
snaps together by means of locking tabs (9
locking tabs per joint). Check each piece by
pulling up slightly from the top to ensure proper
engagement before installing the next section.
If the flue has been installed correctly, it will not
separate when you test it. Also, the inner flue
joint where each section is joined should be
tight and flat without gaps (

Figure 23 ).

F8FS30-2

Firestop Spacer

FTF8-S4 Stabilizer

2" Min.

Air Space

30

°

 Firestop

And Attic Above

10'

Max.

Attic Space

2" Min.

Air Space

F8FS30-2

Firestop Spacer

FTF8-S4 Stabilizer

30

°

 Firestop

And Room Above

10'

Max.

Room Above

2" Min.

Air Space

2" Min.

Air Space

Figure 23

Outer pipe section installs in just the opposite
way; the lanced end goes down and each new
section goes OVER the outside of the previous
section installed (

Figure 24 ).

Locking

Tabs

(Lances)

Always maintain 2" (51 mm) minimum air space
to combustible materials and always check
each chimney joint (inner and outer) to ensure
proper engagement (

See **Note). Check verti-

cal alignment of chimney so that it projects
from the roof in true vertical position.

Note: Assemble one component of chimney at
a time (inner section first, then outer section
last) before proceeding with the next complete
section.

Continue to assemble the chimney up through
framed opening. Assemble just enough to pene-
trate the roof flashing openings (

Figure 25 ).

Figure 25

Figure 24

Security's chimney sections do not need to be
screwed together. Additional reinforcement is
not necessary except in certain offset condi-
tions (refer to page 14, 

Figure 36 ).

Step 5. The height of vertical chimney pipe
supported only by the fireplace must not ex-
ceed 30' (9.1 m). Chimney heights above 30'
(9.1 m) must be supported by a Model F8-S4 or
Model F10-S4 stabilizer installed at 30' (9.1 m)
intervals.

Note: The Model F8-S4 and Model F10-S4 add
3" (76 mm) net effective height to the total
chimney system.

Install Model F8-S4 or F10-S4 stabilizer by
fitting inner section down into respective sec-
tion of proceeding flue pipe and locking outer
stabilizer section into place over the outer
chimney pipe. Position for proper clearance
through framed opening and nail straps se-
curely (under tension in “shear”) into place on
framing. Use 8d nails or equivalent. Attach
successive lengths of chimney pipe directly to
stabilizer using same techniques as described
in Step 4 (

Figure 26 ).

Figure 26

** Note: 1"  (25 mm) when installed with FTF10
in the U.S. only.

2" (51mm)** (

See **Note)

Min. Air Space to

Combustibles

Stabilizer

Содержание Merit CR-3835L

Страница 1: ...y circumstances Any modification or alteration of the fireplace system including but not limited to the fireplace chimney components and accessories may void the warranty listings and approvals of thi...

Страница 2: ...afe distance from the fireplace 8 NEVER leave children unattended when there is a fire burning in the fireplace 9 Always keep flue damper open when heat is present in the fireplace 10 Before servicing...

Страница 3: ...BOCA Basic National Codes the Standard Me chanicalCodeandtheUniformBuildingCodes When complete these fireplace systems con sists of five basic sub systems 1 The Fireplace 2 The Chimney and Termination...

Страница 4: ...re firestopping at the ceiling levels for outside chase installa tions However it is recommended for safety and the reduction of heat loss Figure 5 Chase Enclosure A chase is a vertical box like struc...

Страница 5: ...n Each installation is unique however and might require a different sequence 1 Position firebox prior to framing or into prepared framing 2 Install the chimney system 3 Connect house wiring to the fir...

Страница 6: ...2 mm Class 0 air duct provided to the collar on the chimney collarenclosurewiththescrewsprovidedinthe hardware kit IMPORTANT UNDER NO CIRCUMSTANCES CAN THE FIREPLACE TOP SPACERS FIGURE 6 BE REMOVED OR...

Страница 7: ...432mm 610 mm 483mm 660 mm Perpendicular to roof ridge A B Ceiling Framing C D Roof Framing Framing Without False Header Header B A C Outside Corner C A Back Wall of Chase Encloslure Including Finishi...

Страница 8: ...W MINIMUM 2 51 MM CHIMNEY AIR SPACE TO COMBUSTIBLE FRAMING MEMBERS THROUGHOUT VERTI CAL OR OFFSET CHIMNEY INSTALLATION SEE NOTE A minimum 2 51 mm air space must be reserved for all combustible materia...

Страница 9: ...om Above 10 Max Room Above 2 Min Air Space 2 Min Air Space Figure 23 Outer pipe section installs in just the opposite way the lanced end goes down and each new section goes OVER the outside of the pre...

Страница 10: ...ote Do not caulk or seal the ventilating openings Step 7 Secure flashing by nailing along the perimeter into roof using 8d nails If shingled roof slide upper end and sides of roof flashing under shing...

Страница 11: ...smoke free opera tion Trees buildings adjoining roof lines ad verse wind conditions etc may require a taller chimney should the fireplace not draft properly see Figure 32 MULTIPLE TERMINATIONS If more...

Страница 12: ...ng Do not puncture the inner flue Maximum offset of chimney system is 30 Two offsets must not be assembled to form a 60 offset However two sets of offset and return elbows may be used on a single flue...

Страница 13: ...imney Components Chimney Only Inches Feet Inches 12 18 24 36 48 S4 Meters 247 20 7 0 1 0 0 5 6 29 253 21 1 0 0 1 0 5 6 44 257 21 5 1 1 0 0 5 6 55 263 21 11 1 0 1 0 5 6 70 269 22 5 0 1 1 0 5 6 85 275 2...

Страница 14: ...hes Feet Inches 12 18 36 MM M 461 38 5 0 1 13 11722 11 72 465 38 9 2 0 13 11824 11 82 471 39 3 1 1 13 11976 11 98 479 39 11 0 0 14 12179 12 18 489 40 9 1 0 14 12433 12 43 495 41 3 0 1 14 12586 12 59 4...

Страница 15: ...1 1073 2064 44 85 1 1 0 1 1 1 0 1124 2159 45 86 1 1 0 0 1 0 1 1149 2197 47 90 1 1 0 0 2 1 0 1200 2286 48 91 1 1 0 0 0 2 0 1226 2330 49 93 1 1 0 2 1 1 0 1251 2381 51 97 1 1 0 1 4 0 0 1308 2470 53 100 1...

Страница 16: ...59 1 0 0 1 1 743 1505 31 63 1 0 2 0 1 794 1600 32 65 1 0 4 1 0 826 1651 34 68 1 0 1 1 1 870 1734 36 71 1 0 3 0 1 921 1822 37 73 1 0 0 2 1 946 1861 38 75 1 0 0 0 2 972 1905 39 77 1 0 2 1 1 997 1956 41...

Страница 17: ...stall the same as chimney sections First snap the inner section INTO the preceding inner section of flue Check connec tion by pulling up slightly to ensure a tight fit Next the outer sections snap loc...

Страница 18: ...ed with all fireplaces It is to protect the combustible floor in front of the fireplace from both radiant heat and sparks The hearth extension must extend 8 beyond both sides of the fireplace opening...

Страница 19: ...3 85 3 7 8 Super Firetemp M Johns Manville 61 1 64 73 3 4 Super Firetemp L Johns Manville 54 1 85 64 5 8 Face brick 9 00 111 10 71 10 3 4 Common brick 5 00 20 5 95 6 Cement mortar 5 00 20 5 95 6 Cera...

Страница 20: ...T BE SEALED WITH A NON COMBUSTIBLE MATERIAL Calculating Minimum Thickness if Multiple Materials are Used At times it is important to know what combination of materials are acceptable for use as floor...

Страница 21: ...e Combination 63L28 FTF8 OR15 Offset Return Elbow 63L34 FTF10 OR15 Starter Section 8345 FTF8 SS Attic Shield Assembly Firestop Spacer 63L67 FTF8 FSAS Canada Only 63L68 FTF10 FSAS 63L10 FTF8 12 63L13 F...

Страница 22: ...r Flat 63L36 F10FS 2 Outside Combustion Air Kits with duct 81L87 FOAK without duct 81L88 FOAK LD 63L25 FTF8 S4 Stabilizer 63L26 FTF10 S4 Chimney Pack Conventional 63L70 FTF8 CP7 Contains 3 FTF8 36 1 F...

Страница 23: ...NOTE DIAGRAMS ILLUSTRATIONS NOT TO SCALE 23 NOTES...

Страница 24: ...850 048M REV N C 01 2007 1110 West Taft Avenue Orange CA 92865 The manufacturer reserves the right to make changes at any time without notice in design materials specifications prices and also to disc...

Отзывы: