Lennox EMEA FRIGA-BOHN eCO2Boost XS 1 Скачать руководство пользователя страница 13

eCO2Boost XS 2

13

10.1. CO

2

 charging process

 

9.3. Service valves connexion and handling   

1.Untightened 
the protection caps 

3.Untightened  
the compression packing 

4.Service valve handling   

2.Connect the CDU 
 to the  manifold 

Outlet  Male G 3/8’’  

Example of connexion 
Inlet G 3/8’’ female 
Outlet  

¼

’’ SAE 

1.

Check CO

2

 amount for each evaporator and piping  volume from graph. (see page 20) 

2.

Set CO

2

 vessel on the weight scale, purge air inside charge tube, and 0 setting scale before 

charging. 

3.

Vacuum breakage (gas state) 

4.

Charge CO

2

 without compressor running (liquid state) (charging from suction side service valve). 

5.

Compressor start running(push operation SW) if CO

2

 charging stop before reaching target 

weight. 

6.

Close service valve after CO

2

 weight reaching target amount. 

7.

Keep & check cooling operation until evaporator air or cabinet temperature is reached at target 
temperature. 

8.

Check low pressure until reaching target & operation conditions(both of CO

2

 & air side) are 

stable. 

9.

Compare actual high pressure & discharge pressure from the target table.  

10.

Charge more 50g CO

2

 if high pressure is lower or discharge temperature is higher than table 

value.  

11.

Continue “5.10” process until operation status within ±0.2MPa in pressure, ±5K in discharge 
temperature for each target value. 

  

Содержание FRIGA-BOHN eCO2Boost XS 1

Страница 1: ...eCO2Boost XS 2 1 Split System eCO2Boost XS 2 INSTALLATION INSTRUCTIONS www lennoxemea com N IN0043100 A 04 2019...

Страница 2: ...eCO2Boost XS 2 2...

Страница 3: ...10 C 5 C 5 C Cooling capacity 2 0kW 2 16 kW 4 33 kW 4 87 kW 5 6kW Electric power input 2 11kW 2 13 kW 2 62 kW 2 76 kW 2 78kW Operation temperature Evaporation Min Max 35 5 C Ambient Min Max 25 43 C D...

Страница 4: ...eCO2Boost XS 2 4 2 Product diagram...

Страница 5: ...diagram MT application 1 2 3 4 5 6 7 8 9 5 1 2 3 4 Loop A Loop C OFF MT Te 5 T ambiant 10 Loop A CLA Loop C CHC 5 1 2 3 4 6 7 8 9 Loop A Loop C MT Te 5 T ambiant 25 CDU 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6...

Страница 6: ...00cc 3 Cooling capacity 4 Performance drop Please follow requirement to avoid performance drop and ensure good lubrication of the compressor Requirement for CDU installation design conditions 4 1 Inst...

Страница 7: ...pment to direct sunlight is unavoidable protect the device with a canopy 3 Choose a location where the noise produced by the refrigerating unit will not disturb any close neighbors The noisiest parts...

Страница 8: ...ight is not evenly distributed In particular take care to avoid any shocks and sudden movements when transporting and raising the equipment 6 1 Piping connection Pipe slope 1 Optimal distance between...

Страница 9: ...CDU has its own expansion valve Add just thermostat device with defrost control 9 Remarks Expansion valve for each evaporator One Pressure sensor by loop Evaporator volume MT 15000cc if more risk of...

Страница 10: ...owcase Tev Tair_sc T 3 CDU EEV control the high pressure of each cycle optimal value as function of ambient temperature 4 Showcase EEV control the superheat of the refrigerant at the evaporator outlet...

Страница 11: ...st KA1 RES 1 21 22 5 6 AKCC AKVH 12 14 10 11 CDU CLA 2 1 21 22 Remarks The contact of auxiliary relay KA NO must be wiring in parallel on the CDU contact CLA Mandatory to supply 1 of the AKVH during t...

Страница 12: ...2 Charge Nitrogen gas in 80bar or 55bar if using 60bar relief valve 2 3 Check brazed part using leakage detector or leakage test liquid formability 3 Vacuuming 3 1 Set R744 CO manifold vacuuming pump...

Страница 13: ...sor running liquid state charging from suction side service valve 5 Compressor start running push operation SW if CO2 charging stop before reaching target weight 6 Close service valve after CO2 weight...

Страница 14: ...35 5 00 5 00 5 00 5 00 5 00 5 00 5 00 5 00 5 00 5 00 Target discharge temperature T_dis Ambient temperature T_amb 40 35 30 25 20 15 10 5 0 5 Evaporating temperature T_e 5 93 3 93 3 89 1 81 8 74 1 64 4...

Страница 15: ...rom normal display 2 CLA blinking on display A parameter 3 Press DOWN or UP if changing each parameter set as CHC 4 Press right button if entering each parameter A00 A01 5 Press DOWN or UP if changing...

Страница 16: ...eCO2Boost XS 2 16 11 3 Reading parameters list...

Страница 17: ...1 9337 20 16 2 1 2 2237 1012 8 58 816 163 14 436 44 0 86593 1 9287 21 15 2 2 2 2908 1008 60 728 165 34 436 27 0 87421 1 9237 22 14 2 3 2 3593 1003 1 62 697 167 55 436 09 0 88249 1 9187 23 13 2 3 2 429...

Страница 18: ...dirt inside the CDU clean the outdoor heat exchangers with soft brush or vacuum cleaner 3 Water can be used in case of clogged heat exchanger Noted CDU operation should be stopped when using water cle...

Страница 19: ...eCO2Boost XS 2 19...

Страница 20: ...eCO2Boost XS 2 20 LENNOX EMEA reserves itself the right to make changes at any time without preliminary notice www lennoxemea com...

Отзывы: