DirecDoor Installation Guide
37
CHAPTER 5
Reader Interface
The DirecDoor reader interface provides:
•
four (4) supervised Device Inputs (DI)
–
two (2) alarm DIs and
–
two (2) exit DIs,
•
two (2) reader LED outputs, and
•
two (2) door strike DO relays.
Note:
The DDSDC supports only one door strike DO relay, one alarm DI, and one exit DI on
Connector J2.
The reader voltage is 12 VDC only.
The reader interface is limited to only one type of reader technology:
•
Wiegand,
•
F/2F, or
•
Supervised F/2F.
The reader interface has built-in pull-up resistors to accommodate cable lengths over 500 feet
(152.40 m). External pull-up resistors are not required for the reader interface.
In Supervised F/2F mode, the DI (alarm point) is available at the reader or at the controller on
Supervised F/2F readers that support DIs and Exit DIs.
Setting the DIP Switches
Set DIP switches as described in the tables below before installing and wiring readers.
Reader Technology (SW1-1 through SW1-4)
Reader Technology
SW1-1
SW1-2
SW1-3
SW1-4
Not Valid
Содержание DirecDoor
Страница 1: ...7 4 DirecDoor Installation Guide...
Страница 4: ......
Страница 8: ...Table of Contents 8 DirecDoor Installation Guide...
Страница 14: ...Introduction 14 DirecDoor Installation Guide...
Страница 19: ...DirecDoor Installation Guide 19 Mounting DirecDoor Mounting Template...
Страница 22: ...Installation Planning and Mounting 22 DirecDoor Installation Guide...
Страница 56: ...DDIO Interface 56 DirecDoor Installation Guide Resistances Detected by PXNplus...
Страница 58: ...DO Interface 58 DirecDoor Installation Guide Wiring Output Device to DO Interface...
Страница 76: ...Controller Firmware Tools 76 DirecDoor Installation Guide...
Страница 79: ...DirecDoor Installation Guide 79 CE Regulatory Notice CE Regulatory Notice...
Страница 89: ...DirecDoor Installation Guide 89 Index...